Plan Review Details - Permit 16020618
Plan Review Stops For Permit 16020618
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By jgomez Date 2016-04-11 Time 09:44 Rev Time 0.00
Received By jgomez Date 2016-04-11 Time 09:43 Sent To  
Notes
2016-04-11 09:44:57BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) NEW "HARTLEY SIDING" AS SPECIFIED ON SHEET A-2.
  
 B) ENTRY DOOR WITH SIDELITES THAT MEETS THE DESIGN
 PRESSURES SHOWN ON SHEET A-3.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-14 Cont ID  
Sent By jgomez Date 2016-03-14 Time 17:35 Rev Time 0.00
Received By jgomez Date 2016-03-14 Time 16:30 Sent To  
Notes
2016-03-14 18:01:13RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE IS A DISCREPANCY IN THE DESIGN CRITERIA.
 ARCHITECTURAL PLANS CALL FOR EXPOSURE "D", WHILE
 STRUCTURAL PLANS CALL FOR EXPOSURE "C". REVISE AS
 REQUIRED TO MATCH. AND REVISE THE DESIGN PRESSURES FOR
 ALL DOORS AND WINDOWS, INCLUDING THE NEW GARAGE DOORS.
 NOTE: ACCORDING TO SEC. R301.2.1.4.3 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) THIS PROPERTY IS
 LOCATED IN EXPOSURE "D".
  
 2- PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW GARAGE
 OVERHEAD DOORS, INCLUDING STRUCTURAL BUCK DETAIL AND
 SPECIFICATIONS. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 3- PROVIDE COMPLETE FRAMING DETAILS FOR NEW SLIDING
 GLASS DOORS. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 4- GARAGE DOOR LEADING TO THE MAIN HOUSE NEEDS TO
 COMPLY WITH SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). INCLUDING SELF CLOSING DEVICE.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE FIBERGLASS EXTERIOR DOOR THAT MEETS THE
 CALCULATED DESIGN PRESSURES. NOTE: COORDINATE WITH ITEM
 # 1 ABOVE. FLORIDA PRODUCT APPROVAL FL15180.11
 SUBMITTED DOESN'T MEET THE CALCULATED DESIGN PRESSURES.
  
 B) NEW "HARTLEY SIDING" AS SPECIFIED ON SHEET A-2.
  
 C) ENTRY DOOR WITH SIDELITES AS SHOWN ON PLANS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. OR
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 E) GARAGE OVERHEAD DOORS AS SHOWN ON PLANS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By vperez Date 2016-04-05 Time 11:11 Rev Time 0.00
Received By vperez Date 2016-04-05 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By rlecky Date 2016-03-07 Time 12:22 Rev Time 0.00
Received By rlecky Date 2016-03-04 Time 14:11 Sent To  
Notes
2016-03-07 12:24:34PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 UPDATE THE LOAD CALCULATION TO INCLUDE THE ADDITIONAL
 APPLIANCE BRANCH CIRCUITS, DRYERS, OVENS, MOTORS AND
 THE FIRST 10 K OF THE GENERAL LIGHTING LOAD. NEC
 220.82, FBC R E3704.4
  
 PROVIDE THE LOCATION OF THE POOL PANEL AND ELECTRIC
 SERVICE. NEC 215.5, FBC R E3704
  
 THE SWIMMING POOL PUMP REQUIRES GFCI PROTECTION. NEC
 680.21(C), FBC R E4203.1.3
  
 A GFCI RECEPTACLE IS REQUIRED ON THE PATIO MORE THAN
 SIX FEET FROM THE POOL. NEC 680.22(A) 3, FBC R
 E4203.1.2
  
 PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2);
 FBC R E3703.3
  
 VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12;
 FBC R E3902.12
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.2; FBC R E4002.14
  
 VERIFY RECEPTACLES ARE PROPERLY PLACED TO SERVICE ALL
 AREAS INCLUDING WALL SPACES TWO FEET OR MORE IN WIDTH.
 NEC 210.52 (A), FBC R E3901.2
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-11 Cont ID  
Sent By jgomez Date 2016-04-11 Time 09:45 Rev Time 0.00
Received By jgomez Date 2016-04-01 Time 11:15 Sent To  
Notes
2016-04-04 11:16:03RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-14 Cont ID  
Sent By jgomez Date 2016-03-14 Time 17:35 Rev Time 0.00
Received By jgomez Date 2016-02-17 Time 11:12 Sent To  
Notes
2016-02-17 11:12:27R02

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-26 Cont ID  
Sent By gjohnson Date 2016-02-26 Time 16:46 Rev Time 0.00
Received By gjohnson Date 2016-02-26 Time 16:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-13 Cont ID  
Sent By sholder Date 2017-02-13 Time 11:47 Rev Time 0.00
Received By sholder Date 2017-02-13 Time 11:47 Sent To  
Notes
***NONE***