Plan Review Details - Permit 16020590
Plan Review Stops For Permit 16020590
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-03-02 Cont ID  
Sent By skennedy Date 2016-03-02 Time 17:21 Rev Time 0.00
Received By skennedy Date 2016-02-25 Time 17:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-02 Cont ID  
Sent By skennedy Date 2016-03-02 Time 17:21 Rev Time 0.00
Received By skennedy Date 2016-02-16 Time 17:10 Sent To  
Notes
2016-03-02 17:37:251ST REVIEW: FBC 2010
  
 THIS IS A LIMITED REVIEW OF STRUCTURAL COMPONENTS FOR
 THE TENDER LEVEL ABOVE ELEVATION 54.95. ALL PORTIONS OF
 THE STRUCTURE HAVE BEEN PREVIOUSLY COMPLETED UNDER FDOT
 JURISDICTION. AT THIS TIME, COMPLIANCE WITH FBC ENERGY
 CONSERVATION 2010 IS CONSIDERED UNDER FDOT
 JURISDICTION, AS DOCUMENTS PER FBCE 103 THOUGH
 REQUESTED HAVE NOT BEEN SUBMITTED.
  
 ADDITIONALLY, PLEASE PROVIDE EVIDENCE OF REVIEW BY THE
 DESIGNERR OF RECORD, PCL, FOR REVIEW OF THE DELEGATED
 TRUSS ENGINEERING SUBMITTAL.
  
 BE ADVISED THAT WELDING PRECEEDURES/CERTIFICATION MAY
 BE REQUESTED BY THE INSPECTOR FOR THE MARK C-1 COLUMNS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  