| Plan Review Stops For Permit 16020584 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-05-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-05-28 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-05-28 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2016-05-28 12:25:50 | PROVISO - PROVIDE SLAB CUT PATCH DETAIL AT INSPECTION | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-16 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-03-16 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2016-03-16 17:22:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. REVISION 15100067 WAS NEVER ISSUED. PLEASE ADDRESS. | | | BUILDING REVIEW FAILED BECAUSE THE SIGNATURE DOCUMENTS | | | WHICH WERE SUBMITTED DO NOT MATCH THE ISSUED PERMITS | | | 14120908, 14120909 (FMEP). IT IS RECOMMENDED THAT THE | | | ISSUED PERMITS (14120908, 14120909) ARE DOWNLOADED IN | | | THE FORM THAT THEY WERE ISSUED, AND A REDUCED PLAN | | | SIGNED AND SEALED TO ADDRESS THIS ISSUE. | | | | | | 2. IT APPEARS THAT SOME OF THE SHEETS SUBMITTED ARE THE | | | SAME AS THE SHEETS SUBMITTED FOR 15100067. FOR SHEETS | | | WHICH HAVE ALREADY PASSED PLAN REVIEW IN REVISION | | | 15100067, DELETE FROM THIS REVISION. A REVIEW WILL BE | | | PERFORMED AFTER THIS IS DONE. A SUBMITTAL LETTER MAY BE | | | REQUIRED IF CHANGES ARE NOT IMMEDIATELY APPARENT. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-06-06 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-06-06 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-06-06 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2016-03-01 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-03-01 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2016-03-01 10:34:09 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1.PLEASE NOTE THAT THE AMENDED CONSTRUCTION DOCUMENTS | | | SUBMITTED DO NOT REFLECT A BULLETIN NUMBER INDICATING | | | THE CHANGES MADE. PROVIDE EITHER A NARRATIVE SHEET | | | INDICATING THE CHANGE OR CLOUD AND ASSIGN A BULLETIN TO | | | DRAWINGS FOR EASE OF REVIEW. FBC 107.4, 107.3.5 | | | 2.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL; PLEASE | | | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-06-01 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-06-01 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-06-01 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-03-16 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-03-16 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-03-16 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2016-03-16 08:43:07 | MOST SHEETS DO NOT INDICATE A REVISION CLOUD OR DELTA | | | INDICATING WHAT HAS BEEN CHANGED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-06-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-06-21 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-23 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-03-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-16 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-25 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-06-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-06-21 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-06-21 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-03-11 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2016-03-11 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-03-11 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2016-03-11 11:54:07 | 1ST REVIEW: FBC 2014 MECHANICAL | | | REISION PERMIT #16020584 | | | 3/11/16 | | | | | | 1) PLEASE SUBMIT A NARRATIVE ITEMIZING ALL REVISIONS | | | MADE TO THE ORIGINAL PLANS. IDENTIFY THOSE CHANGES WITH | | | DELTA SYMBOLS AND DATES ON EACH REVISED PLAN SHEET. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-06-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-06-15 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-06-15 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-03-07 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-07 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-03-07 |
Time |
06:16 |
Sent To |
|
|
| Notes |
| 2016-03-07 06:23:45 | 1)SUBMIT A NARRATIVE THAT CLEARLY EXPLAINS THE CHANGES | | | THAT ARE BEING MADE AND CLOUD ALL THE CHANGES ON THE | | | PLAN. FBC 107.2.1, 107.3.5, 107.4. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2016-06-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-06-22 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-06-22 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2016-05-28 12:13:29 | 5/28, VERIFIED DIGITAL SIGNATURES FOR ALL TRADES/PAGES | | | 1ST REVIEW (SH) | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2016-03-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-16 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-03-16 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2016-03-16 17:06:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IT IS MY UNDERSTANDING THAT ALL DESIGN PROFESSIONALS | | | HAVE A DIGITAL SIGNATURE. | | | | | | FOR THE MOST EXPEDITIOUS PROCESS, PLEASE UPLOAD ALL | | | PAGES SIGNED AND SEALED. | | | | | | IF THIS IS NOT DONE, AND A PAPER BACKUP OR OTHER | | | SUBMITTAL IS PROVIDED, IT IS POSSIBLE THAT THE | | | SIGNATURE REVIEW MAY TAKE A WEEK AFTER ALL PLAN REVIEWS | | | HAVE PASSED. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-06-16 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-06-16 |
Time |
09:37 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2016-06-16 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2016-06-16 09:38:12 | SEPARATE PERMITS AREL REQUIRED FOR THE LANDSCAPE, | | | IRRIGATION, BICYCLE RACKS AND CHANGES TO THE HARDSCAPE | | | AREAS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2016-03-15 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-03-15 |
Time |
10:09 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2016-03-15 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2016-03-15 10:13:35 | 1) IT APPEARS THAT SOME OF THE PLAN SHEETS EXACTLY | | | MIRROR THOSE SUBMITTED UNDER PERMIT 15100067 JUST WITH | | | A DIFFERENT DELTA NUMBER ON THE SAME CHANGE CLOUDS. | | | | | | 2) SEPARATE PERMITS ARE STILL REQUIRED FOR THE | | | LANDSCAPE, IRRIGATION, BICYCLE RACKS AND CHANGES TO THE | | | HARDSCAPE AREAS. |
|
|