Plan Review Details - Permit 16020572
Plan Review Stops For Permit 16020572
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-07-08 Cont ID  
Sent By jgomez Date 2016-07-08 Time 09:30 Rev Time 0.00
Received By jgomez Date 2016-07-08 Time 09:27 Sent To Z
Notes
2016-07-08 09:34:30BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE
 INFORMATION PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR
 DELAYS):
  
 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE ADDITION ROOF VENTILATION SEC. R806
 FBC-RESIDENTIAL, 5TH EDITION (2014).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-06-17 Cont ID  
Sent By jgomez Date 2016-06-17 Time 12:32 Rev Time 0.00
Received By jgomez Date 2016-06-17 Time 11:35 Sent To P
Notes
2016-06-17 11:37:45RESIDENTIAL (R3) ADDITION/ALTERATION, THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR ICYNENE
 INSULATION SPECIFIED ON PLANS. ARCHITECT OF RECORD TO
 REVIEW AND APPROVE IN WRITING PRIOR TO SUBMITTAL. SEC.
 R316 OF FBC-RESIDENTIAL, 5TH EDITION (2014),
  
 RESPONSE: INSULATION WAS CHANGED TO R30 BATT
 INSULATION. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW COMPLYING WITH THE ROOF VENTILATION SEC.
 R806 FBC-RESIDENTIAL, 5TH EDITION (2014). REPEAT
 COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- PROVIDE COMPLETE AND CLEAR INFORMATION FOR WINDOWS
 AND DOORS. SPECIFY SIZE FOR ALL DOORS AND WINDOWS TO
 VERIFY COMPLIANCE WITH THE PRODUCT APPROVALS SUBMITTED.
 . AND SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS
 TO BE REPLACED TO VERIFY COMPLIANCE WITH SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014). NOTE: NEW
 BEDROOM WINDOWS NEED TO COMPLY WITH SEC. R310 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014),
  
 RESPONSE: UNABLE TO VERIFY EGRESS REQUIREMENTS FOR THE
 FIRST FLOOR MASTER BEDROOM. SIZE SPECIFIED ON PLANS IS
 NOT LISTED ON THE PRODUCT APPROVAL SUBMITTED. PROVIDE
 MANUFACTURER'S CUT SHEETS FOR THE SPECIFIED SIZE SHOWN
 ON FLOOR PLAN AND TYPE OF WINDOW SHOWN ON THE EXTERIOR
 ELEVATION (UNEQUAL LITES) TO VERIFY COMPLIANCE WITH
 EGRESS.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 RESPONSE: NOA 14-0903.03 SUBMITTED IS FOR 4", 6" & 12"
 WIDE LINTELS. THIS IS NOT THE SIZE SPECIFIED ON PLANS.
 PROVIDE CORRECT PRODUCT APPROVAL FOR 8" LINTELS.
  
 ORIGINAL COMMENT:
 B) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. FLORIDA PRODUCT
 APPROVAL FL15371-R2 SUBMITTED DOESN'T MEET THE DESIGN
 PRESSURES SHOWN ON SHEET S0.1.
  
 RESPONSE: NOT ADDRESSED (TWICE).
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.4.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 5- SPECIFY ATTIC ACCESS LOCATION AND SIZE AT NEW GARAGE
 ADDITION. SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 RESPONSE: SIZE WAS NO SPECIFIED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS TO NEW RESUBMITTED SET. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-20 Cont ID  
Sent By jgomez Date 2016-05-20 Time 14:49 Rev Time 0.00
Received By jgomez Date 2016-05-20 Time 14:48 Sent To  
Notes
2016-05-20 14:54:50RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO.
 CONTRACTOR MAY SUBMIT THE REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED AND BEFORE INSPECTIONS. REVISION
 FEES MAY APPLY. CONTRACTOR TO ADVICE IS PROVISO OPTION
 IS PREFERRED AT THIS TIME.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO
 THE LIVING AREA TO SHOW COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014), INCLUDING SELF CLOSING DEVICE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR ICYNENE
 INSULATION SPECIFIED ON PLANS. ARCHITECT OF RECORD TO
 REVIEW AND APPROVE IN WRITING PRIOR TO SUBMITTAL. SEC.
 R316 OF FBC-RESIDENTIAL, 5TH EDITION (2014),
 RESPONSE: INSULATION WAS CHANGED TO R30 BATT
 INSULATION. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW COMPLYING WITH THE ROOF VENTILATION SEC.
 R806 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 3- PROVIDE COMPLETE AND CLEAR INFORMATION FOR WINDOWS
 AND DOORS. SPECIFY SIZE FOR ALL DOORS AND WINDOWS TO
 VERIFY COMPLIANCE WITH THE PRODUCT APPROVALS SUBMITTED.
 . AND SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS
 TO BE REPLACED TO VERIFY COMPLIANCE WITH SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014). NOTE: NEW
 BEDROOM WINDOWS NEED TO COMPLY WITH SEC. R310 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014),
 RESPONSE: UNABLE TO VERIFY SIZES FOR BEDROOM EGRESS
 REQUIREMENTS. THERE IS NOT RELATIONSHIP BETWEEN THE
 WINDOWS PRODUCT APPROVAL SUBMITTED AND THE WAY WINDOWS
 ARE SPECIFIED ON PLANS. NOTE: CLEARLY SPECIFY ON PLANS
 WHICH EXISTING DOORS AND WINDOWS ARE GOING TO BE
 REPLACED AND PROVIDE EXISTING TYPE AND SIZE OF EXISTING
 BEDROOM WINDOWS TO BE REPLACED TO VERIFY THE EGRESS
 REQUIREMENTS. COORDINATE INFORMATION WITH THE
 DEMOLITION PLANS.
  
 ORIGINAL COMMENT:
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF DECORATIVE SHUTTERS SHOWN ON EXTERIOR
 ELEVATIONS. SPECIFY MATERIALS AND SHUTTERS INSTALLATION
 TO RESIST THE WINDOW LOADS OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- NEW COVERED PATIO ROOF PITCH SHOWN ON EAST ELEVATION
 ON SHEET B-202 IS INCORRECT. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 FL158-R7 WAS SUBMITTED. PROVIDE COMPLETE INFORMATION
 THAT SHOWS SPECIFIED LINTELS.
  
 B) SLIDING GLASS DOOR SIZE (9076) SHOWN IN THE DINING
 ROOM. FLORIDA PRODUCT APPROVAL FL14138-R4 SUBMITTED
 DOESN'T COVER DOORS WITH THE WIDTH SPECIFIED FOR THIS
 DOOR.
  
 C) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. FLORIDA PRODUCT
 APPROVAL FL15371-R2 SUBMITTED DOESN'T MEET THE DESIGN
 PRESSURES SHOWN ON SHEET S0.1.
 RESPONSE: NOT ADDRESSED.
  
 D) SWINGING EXTERIOR DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. FLORIDA
 PRODUCT APPROVAL FL15180-R1 SUBMITTED DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES ON SHEET S0.1. AND, NEED
 SIZE OF EXTERIOR SWINGING DOORS IN PLANS TO VERIFY
 COMPLIANCE WITH PRODUCT APPROVALS SUBMITTED.
 RESPONSE: NOT ADDRESSED.
  
 E) ENTRY DOOR AS SHOWN ON PLANS (IF REPLACED).
 RESPONSE: NOT CLEAR IF REPLACING DOOR OR NOT. SEE DEMO
 PLANS.
  
 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.4.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 8- FLAT ROOF NOA 13-1217.01 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014),
 RESPONSE: NOT ADDRESSED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED, IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES.
 RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 9- SPECIFY ATTIC ACCESS LOCATION AND SIZE AT NEW GARAGE
 ADDITION. SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE: NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 10- ENERGY CALCULATIONS SUBMITTED:
 A) COMPLETE ALL THE INFORMATION ON THE ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC.
 R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: NOT ADDRESSED.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE
 SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD SET FOR REFERENCE. DON"T STAPLE
 OLD DRAWINGS TO NEW SET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By jgomez Date 2016-03-11 Time 12:01 Rev Time 0.00
Received By jgomez Date 2016-03-11 Time 11:10 Sent To  
Notes
2016-03-11 12:03:25RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ALL PLANS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD AS REQUIRED BY CHAPTER 481 F.S.
 AND, TITLE BLOCK TO PROVIDE ARCHITECT'S COMPLETE
 INFORMATION AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE
 SEC. 61G1-16.004
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO
 THE LIVING AREA TO SHOW COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014), INCLUDING SELF CLOSING DEVICE.
  
 4- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR ICYNENE
 INSULATION SPECIFIED ON PLANS. ARCHITECT OF RECORD TO
 REVIEW AND APPROVE IN WRITING PRIOR TO SUBMITTAL. SEC.
 R316 OF FBC-RESIDENTIAL, 5TH EDITION (2014),
  
 5- PROVIDE COMPLETE AND CLEAR INFORMATION FOR WINDOWS
 AND DOORS. SPECIFY SIZE FOR ALL DOORS AND WINDOWS TO
 VERIFY COMPLIANCE WITH THE PRODUCT APPROVALS SUBMITTED.
 . AND SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS
 TO BE REPLACED TO VERIFY COMPLIANCE WITH SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014). NOTE: NEW
 BEDROOM WINDOWS NEED TO COMPLY WITH SEC. R310 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014),
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF DECORATIVE SHUTTERS SHOWN ON EXTERIOR
 ELEVATIONS. SPECIFY MATERIALS AND SHUTTERS INSTALLATION
 TO RESIST THE WINDOW LOADS OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- NEW COVERED PATIO ROOF PITCH SHOWN ON EAST ELEVATION
 ON SHEET B-202 IS INCORRECT. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 8- SHEET S0.1: PROVIDE ROOFING MATERIALS WIND LOADS FOR
 THE FLAT ROOF ON THE NEW COVERED PATIO. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE: ROOFING
 WIND LOADS SHOWN SEEM TO BE FOR ROOF ZONE #2 AND #3 FOR
 HIP ROOFS).
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH CONNECTOR.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) FLORIDA PRODUCT APPROVAL FL14138-R4 SUBMITTED IS FOR
 SLIDING GLASS DOORS. PLANS DON'T SHOW ANY SLIDING GLASS
 DOORS. CLARIFY WHY SUBMITTING THIS PRODUCT APPROVAL.
  
 D) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. FLORIDA PRODUCT
 APPROVAL FL15371-R2 SUBMITTED DOESN'T MEET THE DESIGN
 PRESSURES SHOWN ON SHEET S0.1.
  
 E) SWINGING EXTERIOR DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. FLORIDA
 PRODUCT APPROVAL FL15180-R1 SUBMITTED DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES ON SHEET S0.1. AND, NEED
 SIZE OF EXTERIOR SWINGING DOORS IN PLANS TO VERIFY
 COMPLIANCE WITH PRODUCT APPROVALS SUBMITTED.
  
 F) ENTRY DOOR AS SHOWN ON PLANS (IF REPLACED).
  
 G) FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS.
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.4.1
 CITY AMENDMENTS.
  
 11- FLAT ROOF NOA 13-1217.01 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014),
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED, IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES.
  
 12-SPECIFY ATTIC ACCESS LOCATION AND SIZE AT NEW GARAGE
 ADDITION. SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 13- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO CERTIFY AT THE BOTTOM OF THE COVER
 PAGE AS REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF COVER FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION. SEC. R101.5.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5 TO
 MATCH PLANS. SEC. R101.5.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) CEILING R VALUE SHOWN ON PAGE 3 OF 5 DOESN'T MATCH
 CEILING INFORMATION SHOWN ON PAGE 1 OF 5. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 E) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION SHOWN
 ON PAGE 3 OF 5 TO MATCH PLANS AND ELEVATIONS. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) COMPLETE ALL THE INFORMATION ON THE ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC.
 R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE
 SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 14- INFORMATION SHOWN ON PLANS AND ENERGY CALCULATIONS
 NEED TO MATCH. REVISE INSULATION R-VALUE FOR WALLS,
 CEILING, ETC, TO MATCH. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 15- ARCHITECTURAL PLANS AND STRUCTURAL PLANS DON'T SHOW
 DIMENSIONS FOR THE WIDTH OF THE NEW COVERED PATIO.
 PROVIDE ALL DIMENSIONS. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD SET FOR REFERENCE. DON"T STAPLE
 OLD DRAWINGS TO NEW SET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-10 Cont ID  
Sent By vperez Date 2016-05-10 Time 09:31 Rev Time 0.00
Received By vperez Date 2016-05-10 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By albarran Date 2016-03-03 Time 17:40 Rev Time 0.00
Received By albarran Date 2016-03-03 Time 14:28 Sent To  
Notes
2016-03-03 17:42:101ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. CURRENT APPLICABLE CODES SHALL BE MARKED ON THE
 PLANS: FBC 2014 & NEC 2011.
 2. NEC 210.12B - OUTLETS TO BE AFCI PROTECTED AS PER
 CODE.
 3. NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 4. NEC 210.70(A)(2)(B): A WALL SWITCH CONTROLLED LIGHT
 IS REQUIRED ON THE OUTSIDE OF THE FRONT DOOR OR FOYER.
 5. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
 6. NEC 110.33(B) A PERMANENT LADDER OR STAIRWAY SHALL
 BE PROVIDED TO GIVE SAFE ACCESS TO THE WORKING SPACE
 AROUND ELECTRICAL EQUIPMENT INSTALLED ON PLATFORMS,
 BALCONIES, OR MEZZANINE FLOORS OR IN ATTIC OR ROOF
 ROOMS SPACES.
 7. IN THE INTEREST OF ENERGY CONSERVATION, I SUGGEST
 THAT ATTIC LIGHT SWITCHES HAVE A PILOT INDICATOR AND BE
 INSTALLED IN A READILY VISIBLE LOCATION.
 8. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 9. NEC 404.4. WHERE SWITCHES CONTROLLING LIGHTING LOADS
 SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE GROUNDED
 BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING
 CIRCUIT SHALL BE PROVIDED AT THE SWITCH.
 10. NEC 300.50 UNDERGROUND INSTALLATIONS. (F) WHERE A
 RACEWAY ENTERS FROM AN UNDERGROUND SYSTEM, THE ENDS
 SHALL BE SEALED WITH A LISTED COMPOUND TO PREVENT THE
 ENTRANCE OF MOISTURE OR GASES CONTACTING LIVE PARTS.
 11. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 12. FBC-R404.1 A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By gjohnson Date 2016-06-20 Time 16:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-05-23 Cont ID  
Sent By gjohnson Date 2016-05-23 Time 10:18 Rev Time 0.00
Received By gjohnson Date 2016-05-23 Time 10:17 Sent To  
Notes
2016-05-23 10:30:522ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. PROVIDE SIZE AND LENGTH OF PIPE DOWN STEAM OF
 REGULATOR ON GAS LOG. FBC-2014 FUEL GAS, SECS. 402.4.1,
 402.4.2.
  
  
 2.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR COOK TOP
 AND GAS LOG. PER THE FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SHOW ALL REGULATORS . FBC GAS SEC. 410.2 MP
 REGULATORS. MP PRESSURE REGULATORS SHALL COMPLY WITH
 THE FOLLOWING: 5. A TEE FITTING WITH ONE OPENING CAPPED
 OR PLUGGED SHALL BE INSTALLED BETWEEN THE MP REGULATOR
 AND ITS UPSTREAM SHUTOFF VALVE. SUCH TEE FITTING SHALL
 BE POSITIONED TO ALLOW CONNECTION OF A
 PRESSURE-MEASURING INSTRUMENT AND TO SERVE AS A
 SEDIMENT TRAP
2016-05-20 14:47:46NEW REVISED DRAWINGS SUBMITTED. JG.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-02-26 Cont ID  
Sent By gjohnson Date 2016-02-26 Time 16:19 Rev Time 0.00
Received By gjohnson Date 2016-02-26 Time 16:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-07-13 Cont ID  
Sent By cpuell Date 2016-07-13 Time 10:30 Rev Time 0.00
Received By cpuell Date 2016-06-29 Time 14:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-29 Cont ID  
Sent By cpuell Date 2016-06-29 Time 13:59 Rev Time 0.00
Received By cpuell Date 2016-05-31 Time 14:00 Sent To  
Notes
2016-05-31 14:01:07R27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-23 Cont ID  
Sent By gjohnson Date 2016-05-23 Time 10:31 Rev Time 0.00
Received By gjohnson Date 2016-05-23 Time 10:31 Sent To  
Notes
2016-05-02 17:15:46R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-11 Cont ID  
Sent By jgomez Date 2016-03-11 Time 18:41 Rev Time 0.00
Received By jgomez Date 2016-02-16 Time 15:43 Sent To  
Notes
2016-02-16 15:45:33R31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-05-20 Cont ID  
Sent By jgomez Date 2016-05-20 Time 15:12 Rev Time 0.00
Received By jgomez Date 2016-05-20 Time 15:12 Sent To  
Notes
2016-05-20 15:12:31NO FEES DUE. SEE STAMPED PLAN WITH MU-2016-10299.
 PERMIT TECH D.B.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By jgomez Date 2016-03-11 Time 13:08 Rev Time 0.00
Received By jgomez Date 2016-03-11 Time 13:08 Sent To  
Notes
2016-03-11 13:10:311- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2016-07-13 Cont ID  
Sent By rcaranci Date 2016-07-13 Time 08:43 Rev Time 0.00
Received By rcaranci Date 2016-07-13 Time 08:43 Sent To Z
Notes
2016-07-13 08:45:19SEPARATE LANDSCAPE PERMIT REQUIRED, BRIAN WILL SUBMIT
 APPLICATION WITH LANDSCAPE PLANS SEPARATED FROM MAIN
 PERMIT SO MAIN PERMIT CAN PROCEED THROUGH REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-20 Cont ID  
Sent By jgomez Date 2016-05-20 Time 19:06 Rev Time 0.00
Received By jgomez Date 2016-05-20 Time 19:06 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By jgomez Date 2016-03-11 Time 18:41 Rev Time 0.00
Received By jgomez Date 2016-03-11 Time 18:41 Sent To  
Notes
2016-03-11 19:13:28RESIDENTIAL (R3) ALTERATIONS, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SHEET M-001:
 TRANSFER DUCT SIZE IN MASTER BEDROOM DOESN'T COMPLY
 WITH THE BALANCED RETURN AIR SEC. M1602.4 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE: NEED TO
 CONSIDER ALL THE SUPPLY AIR GOING INTO THE MASTER
 BEDROOM TO SIZE THE TRANSFER DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINE
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-20 Cont ID  
Sent By gjohnson Date 2016-06-20 Time 16:50 Rev Time 0.00
Received By gjohnson Date 2016-06-20 Time 16:50 Sent To  
Notes
2016-06-17 11:28:14REVISED DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By gjohnson Date 2016-05-23 Time 10:16 Rev Time 0.00
Received By gjohnson Date 2016-05-23 Time 10:16 Sent To  
Notes
2016-05-20 14:47:05NEW REVISED DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-26 Cont ID  
Sent By gjohnson Date 2016-02-26 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2016-02-26 Time 16:18 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-06-17 Cont ID  
Sent By jgomez Date 2016-06-17 Time 16:34 Rev Time 0.00
Received By jgomez Date 2016-06-17 Time 16:34 Sent To  
Notes
2016-06-17 16:36:25APPROVED PRODUCT APPROVAL:
  
 1- SHINGLES FL14134-R3
  
 2- POLYGLASS MODIFIED BITUMEN ROOF SYSTEM FL1654-R8.
 (SELECTED SYSTEM W-141 FOR -135 PSF)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-05-20 Cont ID  
Sent By jgomez Date 2016-05-20 Time 18:36 Rev Time 0.00
Received By jgomez Date 2016-05-20 Time 18:36 Sent To  
Notes
2016-05-20 18:39:22ORIGINAL COMMENT:
 1- FLAT ROOF NOA 13-1217.01 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014),
 RESPONSE: NOT ADDRESSED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED, IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES.
 RESPONSE: NOT ADDRESSED.
  
  
 APPROVED PRODUCT APPROVAL:
 SHINGLES FL14134-R3

Review Stop Z ZONING
Rev No 4 Status P Date 2016-07-13 Cont ID  
Sent By llouie Date 2016-07-13 Time   Rev Time 0.00
Received By llouie Date 2016-07-13 Time   Sent To I
Notes
2016-07-13 09:56:47ZONING PASSED WITH THE FOLLOWING PROVISO:
  
 1.) SEPARATE LANDSCAPE PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 3 Status F Date 2016-06-13 Cont ID  
Sent By llouie Date 2016-06-13 Time 12:32 Rev Time 0.00
Received By llouie Date 2016-06-10 Time 16:52 Sent To  
Notes
2016-06-13 12:34:05** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT FROM 2/29/16 AND 5/6/16: THE VALUE
 OF THE CONSTRUCTION ($300,000) EXCEEDS 50 PERCENT OF
 THE STRUCTURE'S VALUE ($81,605) ACCORDING TO THE P.B.C.
 PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO
 SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 2.) LANDSCAPE CALCULATIONS PROVIDED IN THE LANDSCAPE
 PLAN NEED TO BE REVISED. THE CALCULATIONS DO NOT MEET
 THE MINIMUM STANDARDS OF ZLDR S.94-442(B)(2) FOR A
 SINGLE-FAMILY RESIDENCE.
  
 3.) INFORMATION PROVIDED IN THE LANDSCAPE PLAN IS NOT
 CLEAR. IS THE LANDSCAPING PROVIDED IN THE LANDSCAPE
 PLAN ALL EXISTING OR PROPOSED? IF ANY LANDSCAPING IS
 PROPOSED IN THE PLANS, THE LANDSCAPING MUST MEET THE
 MINIMUM STANDARDS OF ZLDR S.94-442(B)(2) FOR A
 SINGLE-FAMILY DWELLING UNIT AND A SEPARATE LANDSCAPE
 PERMIT FOR LANDSCAPING WILL BE REQUIRED.
  
 4.) REPEAT COMMENT FROM 2/29/16 AND 5/6/16:
 ARCHITECTURAL/BUILDING PLANS MUST BE SIGNED, DATED AND
 SEALED BY A FLORIDA LICENSED ARCHITECT. STAFF HAS
 NOTICED THAT THE PLANS ARE SIGNED AND DATED, BUT NOT
 SEALED. IN ORDER TO VALIDATE THE ARCHITECTURAL/BUILDING
 PLANS, THE FLOOR PLANS AND ELEVATIONS MUST ALSO BE
 SEALED BY THE ARCHITECT.
  
 5.) REPEAT COMMENT FROM 5/6/16: ILLUSTRATE LOCATION AND
 SETBACKS OF A/C UNIT IN THE SITE PLAN.
  
 6.) THE REMOVAL OF ANY TREES ON THE PROPERTY WILL
 REQUIRE A TREE ALTERATION PERMIT.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
 NOTE: SPOKE TO CONTRACTOR, BRYAN OF TEKTONICA
 INDUSTRIES, INC.; BRYAN REFERRED ME TO THE ARCHITECT OF
 THE PROJECT, LABERGE & MENARD, INC., CALLED ON 6/13/16.
 NO ANSWER, LEFT VOICE MESSAGE. RETURNED TO R27 SINCE
 THERE WAS NO ANSWER.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-05-06 Cont ID  
Sent By llouie Date 2016-05-06 Time   Rev Time 0.00
Received By llouie Date 2016-05-06 Time 12:13 Sent To  
Notes
2016-05-06 16:04:17** FAILED **
  
 1.) REPEAT COMMENT FROM 2/29/16: THE VALUE OF THE
 CONSTRUCTION ($300,000) EXCEEDS 50 PERCENT OF THE
 STRUCTURE'S VALUE ($81,605) ACCORDING TO THE P.B.C.
 PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO
 SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 2.) REPEAT COMMENT FROM 2/29/16: ARCHITECTURAL/BUILDING
 PLANS MUST BE SIGNED, DATED AND SEALED BY A FLORIDA
 REGISTERED ARCHITECT.
  
 3.) REPEAT COMMENT FROM 2/29/16: SEPARATE PERMIT
 APPLICATION REQUIRED FOR THE PROPOSED DRIVEWAY
 MODIFICATION. DRIVEWAY/WALKWAY MODIFICATION DETECTED;
 DRIVEWAY IN THE SURVEY DOES NOT MATCH THE SITE PLAN.
  
 4.) ILLUSTRATE LOCATION AND SETBACKS OF A/C UNIT IN THE
 SITE PLAN.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-29 Cont ID  
Sent By llouie Date 2016-02-29 Time 11:54 Rev Time 0.00
Received By llouie Date 2016-02-29 Time 11:54 Sent To  
Notes
2016-02-29 11:55:25** FAILED **
  
 1.) THE VALUE OF THE CONSTRUCTION ($300,000) EXCEEDS 50
 PERCENT OF THE STRUCTURE'S VALUE ($81,605) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 2.) ARCHITECTURAL/BUILDING PLANS MUST BE SIGNED, DATED
 AND SEALED BY A FLORIDA REGISTERED ARCHITECT.
  
 3.) SEPARATE PERMIT APPLICATION REQUIRED FOR THE
 PROPOSED DRIVEWAY MODIFICATION.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  