Plan Review Details - Permit 16020539
Plan Review Stops For Permit 16020539
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-23 Cont ID  
Sent By shill Date 2016-05-23 Time 15:43 Rev Time 0.00
Received By shill Date 2016-05-23 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2016-03-24 Time 07:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-19 Cont ID  
Sent By jwitmer Date 2016-02-19 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2016-02-19 Time 06:17 Sent To  
Notes
2016-02-19 07:51:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020539
 ADD: 6901 OKEECHOBEE BLVD. SUITE # D-13
 CONT: ORANGEWOOD BUILDERS
 TEL: 863-452-6400
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB.19/ 2016
 ACTION: DENIED
  
  
 NOTICE: A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 1) PLEASE NOTE THE 6901 OKEECHOBEE BLVD ADDRESS PCN
 (74-42-43-22-08-001-0020) IS FOR THE PUBLIX STORE IN
 THIS SHOPPING CENTER. THE ADDRESS FOR THE STORES THAT
 SURROUND THE ANCHOR STORE PUBLIX IS 6907 OKEECHOBEE
 BLVD. SUITE D-13 WITH THE PCN
 (74-42-43-22-08-001-0010). PLEASE CORRECT THE ADDRESS
 AND PROPERTY CONTROL NUMBER ON THE PERMIT APPLICATION
 AND THE TENANT ADDRESS ON THE TITLEBLOCK OF THE PLANS.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT.
  
 2) PLEASE NOTE SHEET C.2 IN THE PLAN, LOCATION OF THIS
 PROJECT LIST IT AS VILLAGE LAKE RD. & SILVERLAKE PARK
 DR. WINDERMIRE. FL. ORANGE COUNTY. PLEASE CORRECT THE
 LOCATION OF WORK TO THE CORRECT ADDRESS.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT.
  
 3) DISCREPANCY IN PLANS, SHEET C.2 SHOWS THE JOB
 LOCATION AT A INSIDE CORNER WALKWAY OF THE BUILDING,
 WHEREAS SHEET P1 DOES NOT SHOW THE SAME LOCATION.
 PLEASE PROVIDE WHERE THE LOCATION IS ON SHEET P1 IN
 RELATIONSHIP TO THE REST OF THE SHOPPING CENTER,
 DEPICTED ON THE 2 SHEETS ARE 2 DIFFERENT LOCATIONS.
 SHEET P1 TITLE BLOCK IS FOR A LOCATION AT 1307 EAST OAK
 ST. ARCADIA, FL. 107..2.1.3 DISCREPANCY IN PLANS.
 ADDITIONAL INFORMATION REQUIRED.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT.
  
 4) SHEET C.2 THE COVERSHEET INDICATES THE SIZE OF THE
 TENANT SPACE AS 3,830 SQ. FT.AND A BUILDING TYPE
 III-PROTECTED. NOTE THE NOTATION PROTECTED REFLECTS TO
 TABLE 601 OF THE 2014 FBC-B AS TO HOW MANY HRS. THE
 STRUCTURAL FRAMING MEMBER ARE FIRE RATED. IT HAS
 NOTHING TO DO WITH FIRE SPRINKLERS. THE DESIGNER HAS
 DESIGNED THIS TO BE A BUILDING CONSTRUCTION TYPE IIIA,
 1 HOUR FIRE RATING ON STRUCTURAL MEMBERS, PLEASE
 PROVIDE COMPLIANCE FOR THE FIRE RATING.
 NOTE FOOTNOTE D . THE FIRE SPRINKLERS CAN BE
 SUBSTITUTED FOR THE 1 HOUR FIRE RATING IF NOT USED FOR
 AREA INCREASES. PLEASE SHOW THE SQUARE FOOTAGE OF THE
 BUILDING AND IF ANY AREA INCREASES WERE TAKEN FOR
 EITHER FRONTAGE OR FOR FIRE SPRINKLERS. NOTE SHEET P3
 DOES NOT SHOW ANY FIREPROOFING OF BARR JOIST OR METAL
 ROOF DECK.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-22 Cont ID  
Sent By vperez Date 2016-03-22 Time 08:40 Rev Time 0.00
Received By vperez Date 2016-03-22 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-24 Cont ID  
Sent By vperez Date 2016-02-24 Time 13:10 Rev Time 0.00
Received By vperez Date 2016-02-24 Time 13:10 Sent To  
Notes
2016-02-24 13:10:34APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE LABEL ON FLOOR PLAN THE CIRCUIT # FOR THE
 CORRIDOR LIGHTING SHOWN. FBC 107.3.5
 2.SHOW RECEPTACLE FOR THE SIGN OUTLET (CIRCUIT#24) ON
 FLOOR PLAN. FBC 107.3.5
 3.PROVIDE A GENERAL NOTE INDICATING LOW VOLTAGE TO BE
 PERMITTED SEPARATELY. FBC 107.3.5
 4.SHOW ON FLOOR PLAN THE EM EXIT LIGHTS AT EGRESS DOORS
 AND WHERE APPLICABLE. (CIRCUIT#21) FBC 107.3.5
 5.SHOW EXISTING RISER DIAGRAM SHOWING THE CONDUCTOR
 SIZE, OVERCURRENT SELECTION AND AIC RATING FOR THE NEW
 400A PANEL BOARD. FBC 107.3.5, NEC 310.15B16.
 6.CLARIFY IF VOLTAGE TO PANEL BOARD IS 120/240V DELTA 3
 PHASE AS SHOWN ON PANEL BOARD. IF SO COMPLY WITH NOTES
 INDICATING THE REQUIREMENTS OF NEC 408.3F1 HIGH LEG
 IDENTIFICATION.
 7.CLARIFY THE SELECTION OF #12 CONDUCTORS FOR THE RTU?S
 SHOWN ON THE PANEL SCHEDULE WITH 60A OVERCURRENT
 SELECTION. NEC 310.15B16. SHOW THE REQUIRED RECEPTACLE
 OUTLET ON FLOOR PLAN TO SERVICE THE UNITS. NEC 210.63
 8.PROVIDE A NOTE ON THE PANEL SCHEDULE FOR CIRCUIT
 #A-36 EMERGENCY LIGHTS TO HAVE A LOCK ON FEATURE PER
 NEC 700.12F EXCEPTION #1.
 9.SEE SITE SPECIFIC NOTES AND CLARIFY OR DELETE NON
 APPLICABLE NOTES NOT PERTAINING TO THIS PROJECT. SEE
 NOTE #2.
 10.ADD A NOTE TO SCHEDULE INDICATE THAT THE CEILING FAN
 BOXES ARE TO BE RATED AS PER NEC 314.27C
 11.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-30 Cont ID  
Sent By scaldero Date 2016-03-30 Time 11:11 Rev Time 0.00
Received By scaldero Date 2016-03-30 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-17 Cont ID  
Sent By scaldero Date 2016-02-17 Time 10:45 Rev Time 0.00
Received By scaldero Date 2016-02-17 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-05-23 Cont ID  
Sent By shill Date 2016-05-23 Time 15:42 Rev Time 0.00
Received By shill Date 2016-05-20 Time 14:04 Sent To  
Notes
2016-05-20 14:04:41RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-12 Cont ID  
Sent By ccole Date 2016-05-12 Time 07:47 Rev Time 0.00
Received By ccole Date 2016-05-09 Time 12:31 Sent To  
Notes
2016-05-10 12:31:56RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-27 Cont ID  
Sent By tklarge Date 2016-04-27 Time 05:17 Rev Time 0.00
Received By tklarge Date 2016-04-19 Time 10:13 Sent To  
Notes
2016-04-20 10:13:44RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-12 Cont ID  
Sent By tklarge Date 2016-04-12 Time 15:20 Rev Time 0.00
Received By tklarge Date 2016-03-21 Time 11:26 Sent To  
Notes
2016-03-21 11:27:32B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-24 Cont ID  
Sent By ccole Date 2016-02-24 Time 17:48 Rev Time 0.00
Received By ccole Date 2016-02-16 Time 16:17 Sent To  
Notes
2016-02-24 13:13:20TO B13
2016-02-16 16:17:10B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2016-03-24 Time 08:02 Sent To  
Notes
2016-03-24 08:04:43IMPACT FEES NOT REQUIRED, CALLED P. B. C. IMPACT FEE
 OFFICE, SPOKE WITH MICHELLE NOT REQUIRED FOR CHANGE OF
 OCCUPANCY IN A INLINE SHOPPING CENTER/ NOT A OUT PARCEL
 STAND ALONE BUILDING. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-02-19 Cont ID  
Sent By jwitmer Date 2016-02-19 Time 07:52 Rev Time 0.00
Received By jwitmer Date 2016-02-19 Time 07:52 Sent To  
Notes
2016-02-19 07:53:00BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2016-05-26 Cont ID  
Sent By ccole Date 2016-05-27 Time 12:03 Rev Time 0.00
Received By ccole Date 2016-05-26 Time 12:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2016-05-23 Cont ID  
Sent By ccole Date 2016-05-23 Time 14:41 Rev Time 0.00
Received By ccole Date 2016-05-23 Time 16:33 Sent To  
Notes
2016-05-23 14:44:16MECHANICAL PROVISOS
 PERMIT #16020539
 5/24/16
  
 PRIOR TO 1ST MECHANCIAL INSPECTION THE CONTRACTOR
 SHALL:
  
 1) SUBMIT REVISED ENERGY CALCULATIONS
 2) SUBMIT AN AHRI CERTIFICATE FOR THE NEW RTU-1.
 3) SUBMIT ENGINEERED TIE DOWN DETAILS FOR ANCHORING
 RTU-1 TO THE CURB AND ROOF STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-05-12 Cont ID  
Sent By ccole Date 2016-05-12 Time 07:29 Rev Time 0.00
Received By ccole Date 2016-05-12 Time 07:29 Sent To  
Notes
2016-05-12 07:47:134TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 5/12/16
  
 1) M-1: REFER TO SECTION 401.2 FBC-14 MECHANICAL: EVERY
 OCCUPIED SPACE SHALL BE VENTILATED EITHER BY NATURAL OR
 MECHANICAL MEANS. THE CALCULATIONS SHOWN ON THE PLAN
 INDICATE BOTH METHODS ARE BEING COMBINED TO ACHIEVE THE
 REQUIRED 1058 CFM'S OF OUTDOOR AIR FOR THE PROPOSED
 OCCUPANCY. AS NOTED IN 2012 INTERNATIONAL CODE
 COMMENTARY "THERE ARE NO PROVISIONS IN THE CODE FOR A
 VENTILATION SYSTEM THAT DEPENDS SIMULTANEOUSLY ON BOTH
 NATURAL AND MECHANICAL VENTILATION". THE DESIGN
 PROFESSIONALS CALCULATIONS THE RTU'S ARE SUPPLYING A
 TOTAL OF 828 CFMS OF O/A WHICH IS APPROXIMATELY 230
 CFMS SHORT OF THE REQUIREMENT. PLEASE NOTE THE
 FOLLOWING: A) THE TERM "MAKE-UP" AIR SHOULD BE REPLACED
 ON THE PLAN WITH "VENTILATION AIR" AS NOTED IN SECTION
 401.2. B) REFER TO SECTION 402.1 NATURAL VENTILATION:
 NATURAL VENTILATION OF AN OCCUPIED SPACE SHALL BE
 THROUGH WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO
 THE OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS
 SHALL BE PROVIDED WITH READY ACCESS SO THAT THE
 OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING
 OCCUPANTS. THE PLANS APPEAR TO INDICATE THAT "NATURAL
 VENTILATION" WOULD NOT BE A REASONABLE WAY TO PROVIDE
 VENTILATION TO THE SPACE BECAUSE THERE ARE NO OPERABLE
 OPENINGS EXCEPT THE ENTRY DOORS WHICH WOULD TYPICALLY
 BE KEPT CLOSED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-04-21 Cont ID  
Sent By ccole Date 2016-04-21 Time 15:59 Rev Time 0.00
Received By ccole Date 2016-04-21 Time 15:59 Sent To  
Notes
2016-04-21 16:24:222ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 4/21/16
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: REFER
 TO TABLE 403.3 AND PROVIDE A O/A CALCULATION FOR THE
 STRENGTH TRAINING AREA AT 10 PERSONS PER 1000 SF. AT A
 RATE OF 20 CFM PER PERSON + .06 CFMS PER SF. OF THE
 AREA. PLEASE SEE THE CALCULATION RATES LISTED UNDER
 "OFFICES" IN THE TABLE FOR ALL OTHER ROOMS AND SPACES
 SHOWN ON THE PLANS.BASED.
 IN REGARD TO THE CALCULATIONS ON SHEET M-1, REFER TO
 SECTION 403.2 EXCEPTION: WHERE THE REGISTERED DESIGN
 PROFESSIONAL DEMONSTRATES THAT AN ENGINEERED
 VENTILATION SYSTEM DESIGN WILL PREVENT THE MAXIMUM
 CONCENTRATION OF CONTAMINANTS FROM EXCEEDING THAT
 OBTAINABLE BY THE RATE OF OUTDOOR AIR VENTILATION
 DETERMINED IN ACCORDANCE WITH SECTION 403.3, THE
 MINIMUM REQUIRED RATE OF OUTDOOR AIR SHALL BE REDUCED
 IN ACCORDANCE WITH SUCH ENGINEERED SYSTEM DESIGN. IF
 CHOOSING THIS EXCEPTION PROVIDE DETAILS AND
 SPECIFICATIONS FOR THE ENGINEERED SYSTEM. REFER TO
 SECTION 403.3 EXCEPTION: THE OCCUPANT LOAD IS NOT
 REQUIRED TO BE DETERMINED BASED ON THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE 403.3
 WHERE APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY
 OF AN ALTERNATE ANTICIPATED OCCUPANT DENSITY. IF
 CHOOSING THIS EXCEPTION, APPROVED STATISTICAL DATA
 DOCUMENTATION MUST BE PROVIDED.
  
 2) PLEASE CORRECT NOTE #7 TO INDICATE THE LOCATION OF
 THE DS DETECTOR TO BE IN THE RETURN AIR SYSTEM, AND
 PROVIDE A SYMBOL ON THE PLAN TO INDICATE COMPLIANCE.
 PLACE A NOTE INDICATING THAT BOTH UNITS WILL BE LINKED
 TOGETHER FOR FAN SHUT DOWN IF THE THE DS DETECTOR
 ACTIVATES.
  
 3) PROVIDE SHUTOFF DAMPERS FOR THE O/A INTAKE ON THE
 RTU'S AND INDICATE HOW THEY WILL BE CONTROLLED- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-25 Cont ID  
Sent By ccole Date 2016-03-25 Time 14:11 Rev Time 0.00
Received By ccole Date 2016-03-25 Time 14:11 Sent To  
Notes
2016-03-25 14:37:312ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 3/25/16
  
 1) SHEET M-1: THE O/A CALCULATIONS ARE BASED ON AN
 OCCUPANT LOAD THAT DOES NOT MATCH THE OCCUPANT LOAD ON
 THE PLANS OR TABLE 403.3. ADDITIONALLY, AIR
 INFILTRATION SHALL NOT BE USED TO PROVIDE AIR BALANCE
 OR PRESSURE EQUALIZATION- SECTION 501.4.
 2) PROVIDE AN EXHAUST FAN EQUIPMENT SCHEDULE ON THE
 PLANS AND SUBMIT AN MIAMI- DADE NOA OR FLORIDA PRODUCT
 APPROVAL FOR THE FAN OR LOUVER.
 3) INDICATE THE CLEARANCE DISTANCE MEASUREMENTS FOR THE
 EXHAUST DUCT TERMINATIONS AS REQUIRED BY SECTION
 501.3.1 FBC-14 MECHANICAL.
 4) INDICATE THE TYPE AND GAGE OF METAL BATHROOM/UTILITY
 ROOM EXHAUST DUCT TO BE USED- REFER TO CHAPTER 4 OF
 SMACNA, AND INDICATE THE EXHAUST CFMS AT THE EXHAUST
 INLET IN THE UTILITY ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-24 Cont ID  
Sent By ccole Date 2016-02-24 Time 17:17 Rev Time 0.00
Received By ccole Date 2016-02-24 Time 17:17 Sent To  
Notes
2016-02-24 17:18:161ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020539
 2/24/16
  
 1) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES OF THE NEW FITNESS CENTER-
 SEE TABLE 403.3 FBC-14 MECHANICAL.
 2) AC COOLING AND HEATING CALCULATIONS ARE REQUIRED FOR
 THE NEW RT SEE SECTION C403.2.1 CALCULATION OF HEATING
 AND COOLING LOADS, FBC-14 ENERGY CONSERVATION.
 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: THE PROPOSED NEW A3 OCCUPANCY IS A CHANGE
 OF OCCUPANCY FROM THE PREVIOUS B OCCUPANCY AND
 THEREFORE MUST BE IN COMPLIANCE WITH THE ENERGY CODE.
 PLEASE SEE SECTIONS C101.5.1 AND C101.5.1.1 AND SUBMIT
 COMPLIANCE FORMS USING EITHER THE PRECRIPTIVE OR
 PERFORMANCE- BASED METHOD.
 4) SHEET M-1: PLEASE LABEL EACH OF THE AC SYSTEMS SHOWN
 ON THE PLAN AND INDICATE WHETHER THEY ARE NEW OR
 EXISTING. INDICATE ON THE PLAN WHERE THE RTU'S ARE
 LOCATED AND SHOW OUTLINES OF THEIR SUPPLY AND RETURN
 PLENUMS
 5) M-1: INDICATE THE FLEX DUCT SIZES, AND ANY BRANCH
 DUCTS NOT SIZED.
 6) PROVIDE RETURN AIR SYSTEMS FOR BOTH OF THE RTU'S-
 SECTION 601.5 FBC-14 MECHANICAL.
 7) M-2: THE RTU MOUNTING DETAIL SHOWN AT THE TOP OF THE
 PLAN SHEET IS MISSING- NO DIAGRAM IS SHOWN.
 8) M-2: PLEASE CLARIFY IF TWO NEW RTU'S ARE BEING
 INSTALLED: THE TWO MOUNTING DETAILS ON THIS SHEET- ONE
 WITH CURB ADAPTOR, AND ONE WITHOUT- APPEAR TO INDICATE
 TWO DIFFERENT UNITS. CLARIFY IF A NEW ROOF OPENING IN
 THE STRUCTURE MUST BE ACCOMPLISHED TO INSTALL THE NEW
 RTU AND PROVIDE ENGINEERED STRUCTURAL DETAILS IF
 APPLICABLE.
 9) PROVIDE COMPLETE EQUIPMENT SCHEDULES FOR THE RTU'S
 10) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE
 RTU'S AND CLEARANCE DISTANCE MEASUREMENTS FROM ANY
 EXHAUST OR VENT OUTLETS TO THE AIR INTAKES.
 11) PLEASE NOTE THAT THERE MAY BE ADDITIONAL COMMENTS
 WHEN REVISED, CORRECTED PLANS HAVE BEEN SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-05-11 Cont ID  
Sent By tklarge Date 2016-05-11 Time 11:40 Rev Time 0.00
Received By tklarge Date 2016-05-11 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-04-27 Cont ID  
Sent By tklarge Date 2016-04-27 Time 05:17 Rev Time 0.00
Received By tklarge Date 2016-04-27 Time 04:19 Sent To  
Notes
2016-04-26 10:37:271) A FOLDING OR NON-FOLDING SEAT IS REQUIRED IN
 TRANSFER TYPE SHOWER COMPARTMENTS PER THE 2014
 FBC-ACCESSIBILITY SEC.608.4. YOUR RESPONSE TO MY
 PREVIOUS COMMENT DOES NOT MAKE SENSE TO ME AS YOU ARE
 REFERRING TO A CODE SECTION FOR ROLL-IN TYPE SHOWERS
 AND THE SIZE OF THE SHOWERS ON THE PLANS DO NOT COMPLY
 WITH THE MINIMUM DIMENSIONS REQUIRED FOR A ROLL-IN TYPE
 SHOWER PER THE FAC SEC.608.2.2. THE SIZES ON THE PLANS
 ARE FOR A TRANSFER TYPE SHOWER, NOT A ROLL-IN. 2ND
 REQUEST.
 2)THE SHOWER SEAT SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SEC.610.3. IN TRANSFER-TYPE SHOWERS,
 THE SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE
 TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND
 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH
 FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR 610.3.2. 2ND
 REQUEST
 3) SUBMIT AN ELEVATION OF THE WING WALLS AND SHOW THE
 HEIGHT. ANY PORTION OF THE WING WALL LOCATED GREATER
 THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE
 FINISH FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH PER 2014
 FAC SEC. 307.2. WHY NOT PUT AN OPTIONAL SKIRT ON THE
 HIGH SIDE DRINKING FOUNTAIN TO KEEP THE LEADING EDGE
 BELOW 27 INCHES?
 4) SHT. P-2 - THE SIDE WALL GRAB BAR FOR THE WATER
 CLOSET SHALL COMPLY WITH FAC SEC.604.5.1. SHOW THE
 DIMENSIONS ON THE PLANS.2ND REQUEST.
 5) THE GRAB BARS IN THE SHOWERS SHALL BE LOCATED ACROSS
 THE CONTROL WALL AND BACK WALL TO A POINT 18 INCHES
 FROM THE CONTROL WALL. SHOW THIS ON THE PLANS. SEE FAC
 FIGURE 608.3.1.
 6) THE SHOWER CONTROLS SHALL BE LOCATED A MAXIMUM OF 15
 INCHES FROM THE CENTERLINE OF THE REQUIRED SEAT TOWARD
 THE SHOWER OPENING. SHOW THIS ON THE PLANS.
 7) THE FIRST WATER CLOSET THAT IS CONNECTED TO THE
 BUILDING DRAIN CREATES PLUMBING CODE VIOLATIONS. THE
 LOCATION OF THE WATER CLOSETS CREATES A WET VENT FOR
 THE WATER CLOSETS AND THE FIXTURES DISCHARGING INTO THE
 WET VENT VIOLATES THE 2014 FBC-PLUMBING SEC.912.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-12 Cont ID  
Sent By tklarge Date 2016-04-12 Time 15:20 Rev Time 0.00
Received By tklarge Date 2016-04-11 Time 04:08 Sent To  
Notes
2016-04-12 15:02:481) THE SHOWER SEAT SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SEC.610.3. IN TRANSFER-TYPE SHOWERS,
 THE SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE
 TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND
 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH
 FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR 610.3.2.
 2) SUBMIT AN ELEVATION DETAIL FOR THE DRINKING
 FOUNTAINS. THE FOUNTAINS SHALL COMPLY WITH FAC SEC. 307
 FOR PROTRUDING OBJECTS. 307.2 PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH. AN
 OPTIOAAL SKIRT MAY BE REQUIRED FOR THE HIGH SIDE
 DRINKING FOUNTAIN.
 3) SHT. P.1 - THE DOOR IN THE MEN'S ROOM SWINGS INTO
 THE CLEAR FLOOR SPACE FOR THE SHOWER AND THE LAVATORY
 AND THE DOOR IN THE WOMEN'S RESTROOM SWINGS INTO THE
 CLEAR FLOOR SPACEFO THE LAVATORY. THE DOOR SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE PER THE 2014 FAC SEC, PER THE FAC SEC.603.2.3..
 REFERE TO EXCEPTION #2.
 4) THE WATER CLOSETS SHALL BE LOCATED A MINIMUM OF 16
 INCHES AND A MAXIMUM OF 18 INCHES TO THE CENTERLINE OF
 THE WATER CLOSET TO AN ADJACENT WALL. 2014 FAC
 SEC.604.2. SHOW THIS ON THE ENLARGED PLANS ON SHT.P.2.
 5) THE LOCATION OF THE GRAB BARS FOR THE WATER CLOSETS
 SHALL COMPLY WITH FAC SEC.604.5 THROUGH 604.5.2 &
 FIGURES 604.5.1 & 604.5.2.
 6) SHOW THE INSIDE CLEAR DIMENSIONS ( LENGTH X WIDTH)
 OF BOTH TOILET ROOMS. THE DIMENSIONS SHOWN ON SHTS. P.1
 & P.2 ARE NOT INSIDE DIMENSIONS.
 7) SHT. P.2 - 608.2.1 TRANSFER TYPE SHOWER
 COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED. THE PLANS SHOW THE CLEAR FLOOR SPACE MEASURED
 FROM THE WALL OPPOSITE THE CONTROLS.
 8) GRAB BARS ARE REQUIRED IN THE SHOWERS PER FAC
 SECS.608.3, 608.3.1.
 9) THE SHOWER CONTROLS SHALL COMPLY WITH FAC
 SEC.608.5.1, 309.4, 608.6.SUBMIT DETAIL FOR REVIEW.
 10) THE SHOWER THRESHOLD SHALL COMPLY WITH FAC
 SEC.608.7.
 11 ) SHT. PL.2 - THE MINIMUM SIZE OF THE WATER HEATER
 PAN DRAIN SHALL BE 3/4 INCH PER THE 2014 FPC
 SEC.504.7.1.THE PLAN SHOWS 1/2".
 12) THE HEATE PAN SHALL BE A MINIMUM OF 1 1/2 INCHES
 DEEP PER THE 2014 FPC SEC.504.7.1.
 13) THE WATER RISER APPEARS TO HAVE THE HOT AND COLD
 WATER LINES REVERSED. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-23 Cont ID  
Sent By gjohnson Date 2016-02-23 Time 06:31 Rev Time 0.00
Received By gjohnson Date 2016-02-19 Time 18:13 Sent To  
Notes
2016-02-23 06:57:21 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P-1 THE FLOOR PLAN DOES NOT MATCH THE REST OF
 THE PLAN AND IS ADDRESSED DIFFERENTLY PLEASE CLARIFY.
 PER WPB AMEND. TO FBC 107.2.1
  
 2. SHT. HC.1 THE TEXT IS PRINTED VERY BLURRY AND IS
 UNCLEAR PLEASE PROVIDE A SHEET THAT IS PRINTED CLEARLY
 PER WPB AMEND. TO FBC SEC. 107.2.1.4
  
 3. SHT. PL.1 WATER FOUNTAIN CAN NOT TIE INTO THE WET
 VENT OF BATHROOM GROUP
 PER. FBC PL SEC. 912.1
  
 4. SHT. PL.1 REFERENCES A 40 GAL. WATER HEATER FIXTURE
 SCHEDULE ON PL.2 REFERENCES A 50 GAL. PLEASE CLARIFY.
 PER WPB AMEND. TO FBC 107.2.1
  
 5. SHOWER SEAT SHALL COMPLY WITH FBC ACC. SEC 610
 PLEASE SHOW ON PLAN.
 PER WPB AMEND. TO FBC 107.2.1
  
 6. SHT. SHOW WATER HAMMER ARRESTORS ON WATER RISER
 DIAGRAM.
 PER WPB AMEND. TO FBC 107.2.1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved