| Plan Review Stops For Permit 16020539 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-05-23 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-05-23 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-03-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-03-24 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-03-24 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-02-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-02-19 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-02-19 |
Time |
06:17 |
Sent To |
|
|
| Notes |
| 2016-02-19 07:51:58 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16020539 | | | ADD: 6901 OKEECHOBEE BLVD. SUITE # D-13 | | | CONT: ORANGEWOOD BUILDERS | | | TEL: 863-452-6400 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. FEB.19/ 2016 | | | ACTION: DENIED | | | | | | | | | NOTICE: A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, | | | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | 1) PLEASE NOTE THE 6901 OKEECHOBEE BLVD ADDRESS PCN | | | (74-42-43-22-08-001-0020) IS FOR THE PUBLIX STORE IN | | | THIS SHOPPING CENTER. THE ADDRESS FOR THE STORES THAT | | | SURROUND THE ANCHOR STORE PUBLIX IS 6907 OKEECHOBEE | | | BLVD. SUITE D-13 WITH THE PCN | | | (74-42-43-22-08-001-0010). PLEASE CORRECT THE ADDRESS | | | AND PROPERTY CONTROL NUMBER ON THE PERMIT APPLICATION | | | AND THE TENANT ADDRESS ON THE TITLEBLOCK OF THE PLANS. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE | | | PROJECT. | | | | | | 2) PLEASE NOTE SHEET C.2 IN THE PLAN, LOCATION OF THIS | | | PROJECT LIST IT AS VILLAGE LAKE RD. & SILVERLAKE PARK | | | DR. WINDERMIRE. FL. ORANGE COUNTY. PLEASE CORRECT THE | | | LOCATION OF WORK TO THE CORRECT ADDRESS. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE | | | PROJECT. | | | | | | 3) DISCREPANCY IN PLANS, SHEET C.2 SHOWS THE JOB | | | LOCATION AT A INSIDE CORNER WALKWAY OF THE BUILDING, | | | WHEREAS SHEET P1 DOES NOT SHOW THE SAME LOCATION. | | | PLEASE PROVIDE WHERE THE LOCATION IS ON SHEET P1 IN | | | RELATIONSHIP TO THE REST OF THE SHOPPING CENTER, | | | DEPICTED ON THE 2 SHEETS ARE 2 DIFFERENT LOCATIONS. | | | SHEET P1 TITLE BLOCK IS FOR A LOCATION AT 1307 EAST OAK | | | ST. ARCADIA, FL. 107..2.1.3 DISCREPANCY IN PLANS. | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE | | | PROJECT. | | | | | | 4) SHEET C.2 THE COVERSHEET INDICATES THE SIZE OF THE | | | TENANT SPACE AS 3,830 SQ. FT.AND A BUILDING TYPE | | | III-PROTECTED. NOTE THE NOTATION PROTECTED REFLECTS TO | | | TABLE 601 OF THE 2014 FBC-B AS TO HOW MANY HRS. THE | | | STRUCTURAL FRAMING MEMBER ARE FIRE RATED. IT HAS | | | NOTHING TO DO WITH FIRE SPRINKLERS. THE DESIGNER HAS | | | DESIGNED THIS TO BE A BUILDING CONSTRUCTION TYPE IIIA, | | | 1 HOUR FIRE RATING ON STRUCTURAL MEMBERS, PLEASE | | | PROVIDE COMPLIANCE FOR THE FIRE RATING. | | | NOTE FOOTNOTE D . THE FIRE SPRINKLERS CAN BE | | | SUBSTITUTED FOR THE 1 HOUR FIRE RATING IF NOT USED FOR | | | AREA INCREASES. PLEASE SHOW THE SQUARE FOOTAGE OF THE | | | BUILDING AND IF ANY AREA INCREASES WERE TAKEN FOR | | | EITHER FRONTAGE OR FOR FIRE SPRINKLERS. NOTE SHEET P3 | | | DOES NOT SHOW ANY FIREPROOFING OF BARR JOIST OR METAL | | | ROOF DECK. | | | | | | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-03-22 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-03-22 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-03-22 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-02-24 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-02-24 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-02-24 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2016-02-24 13:10:34 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1.PLEASE LABEL ON FLOOR PLAN THE CIRCUIT # FOR THE | | | CORRIDOR LIGHTING SHOWN. FBC 107.3.5 | | | 2.SHOW RECEPTACLE FOR THE SIGN OUTLET (CIRCUIT#24) ON | | | FLOOR PLAN. FBC 107.3.5 | | | 3.PROVIDE A GENERAL NOTE INDICATING LOW VOLTAGE TO BE | | | PERMITTED SEPARATELY. FBC 107.3.5 | | | 4.SHOW ON FLOOR PLAN THE EM EXIT LIGHTS AT EGRESS DOORS | | | AND WHERE APPLICABLE. (CIRCUIT#21) FBC 107.3.5 | | | 5.SHOW EXISTING RISER DIAGRAM SHOWING THE CONDUCTOR | | | SIZE, OVERCURRENT SELECTION AND AIC RATING FOR THE NEW | | | 400A PANEL BOARD. FBC 107.3.5, NEC 310.15B16. | | | 6.CLARIFY IF VOLTAGE TO PANEL BOARD IS 120/240V DELTA 3 | | | PHASE AS SHOWN ON PANEL BOARD. IF SO COMPLY WITH NOTES | | | INDICATING THE REQUIREMENTS OF NEC 408.3F1 HIGH LEG | | | IDENTIFICATION. | | | 7.CLARIFY THE SELECTION OF #12 CONDUCTORS FOR THE RTU?S | | | SHOWN ON THE PANEL SCHEDULE WITH 60A OVERCURRENT | | | SELECTION. NEC 310.15B16. SHOW THE REQUIRED RECEPTACLE | | | OUTLET ON FLOOR PLAN TO SERVICE THE UNITS. NEC 210.63 | | | 8.PROVIDE A NOTE ON THE PANEL SCHEDULE FOR CIRCUIT | | | #A-36 EMERGENCY LIGHTS TO HAVE A LOCK ON FEATURE PER | | | NEC 700.12F EXCEPTION #1. | | | 9.SEE SITE SPECIFIC NOTES AND CLARIFY OR DELETE NON | | | APPLICABLE NOTES NOT PERTAINING TO THIS PROJECT. SEE | | | NOTE #2. | | | 10.ADD A NOTE TO SCHEDULE INDICATE THAT THE CEILING FAN | | | BOXES ARE TO BE RATED AS PER NEC 314.27C | | | 11.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-03-30 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2016-03-30 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2016-03-30 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2016-02-17 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2016-02-17 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2016-02-17 |
Time |
10:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-05-23 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-05-20 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2016-05-20 14:04:41 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-05-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-12 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-09 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2016-05-10 12:31:56 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-04-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-04-27 |
Time |
05:17 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-04-19 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2016-04-20 10:13:44 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-04-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-04-12 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-03-21 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-02-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-24 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-16 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2016-02-24 13:13:20 | TO B13 | | 2016-02-16 16:17:10 | B13 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2016-03-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-03-24 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-03-24 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2016-03-24 08:04:43 | IMPACT FEES NOT REQUIRED, CALLED P. B. C. IMPACT FEE | | | OFFICE, SPOKE WITH MICHELLE NOT REQUIRED FOR CHANGE OF | | | OCCUPANCY IN A INLINE SHOPPING CENTER/ NOT A OUT PARCEL | | | STAND ALONE BUILDING. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-02-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-02-19 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-02-19 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2016-02-19 07:53:00 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2016-05-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-27 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-26 |
Time |
12:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-23 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-23 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2016-05-23 14:44:16 | MECHANICAL PROVISOS | | | PERMIT #16020539 | | | 5/24/16 | | | | | | PRIOR TO 1ST MECHANCIAL INSPECTION THE CONTRACTOR | | | SHALL: | | | | | | 1) SUBMIT REVISED ENERGY CALCULATIONS | | | 2) SUBMIT AN AHRI CERTIFICATE FOR THE NEW RTU-1. | | | 3) SUBMIT ENGINEERED TIE DOWN DETAILS FOR ANCHORING | | | RTU-1 TO THE CURB AND ROOF STRUCTURE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2016-05-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-12 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-12 |
Time |
07:29 |
Sent To |
|
|
| Notes |
| 2016-05-12 07:47:13 | 4TH REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020539 | | | 5/12/16 | | | | | | 1) M-1: REFER TO SECTION 401.2 FBC-14 MECHANICAL: EVERY | | | OCCUPIED SPACE SHALL BE VENTILATED EITHER BY NATURAL OR | | | MECHANICAL MEANS. THE CALCULATIONS SHOWN ON THE PLAN | | | INDICATE BOTH METHODS ARE BEING COMBINED TO ACHIEVE THE | | | REQUIRED 1058 CFM'S OF OUTDOOR AIR FOR THE PROPOSED | | | OCCUPANCY. AS NOTED IN 2012 INTERNATIONAL CODE | | | COMMENTARY "THERE ARE NO PROVISIONS IN THE CODE FOR A | | | VENTILATION SYSTEM THAT DEPENDS SIMULTANEOUSLY ON BOTH | | | NATURAL AND MECHANICAL VENTILATION". THE DESIGN | | | PROFESSIONALS CALCULATIONS THE RTU'S ARE SUPPLYING A | | | TOTAL OF 828 CFMS OF O/A WHICH IS APPROXIMATELY 230 | | | CFMS SHORT OF THE REQUIREMENT. PLEASE NOTE THE | | | FOLLOWING: A) THE TERM "MAKE-UP" AIR SHOULD BE REPLACED | | | ON THE PLAN WITH "VENTILATION AIR" AS NOTED IN SECTION | | | 401.2. B) REFER TO SECTION 402.1 NATURAL VENTILATION: | | | NATURAL VENTILATION OF AN OCCUPIED SPACE SHALL BE | | | THROUGH WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO | | | THE OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS | | | SHALL BE PROVIDED WITH READY ACCESS SO THAT THE | | | OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING | | | OCCUPANTS. THE PLANS APPEAR TO INDICATE THAT "NATURAL | | | VENTILATION" WOULD NOT BE A REASONABLE WAY TO PROVIDE | | | VENTILATION TO THE SPACE BECAUSE THERE ARE NO OPERABLE | | | OPENINGS EXCEPT THE ENTRY DOORS WHICH WOULD TYPICALLY | | | BE KEPT CLOSED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2016-04-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-04-21 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-04-21 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2016-04-21 16:24:22 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020539 | | | 4/21/16 | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: REFER | | | TO TABLE 403.3 AND PROVIDE A O/A CALCULATION FOR THE | | | STRENGTH TRAINING AREA AT 10 PERSONS PER 1000 SF. AT A | | | RATE OF 20 CFM PER PERSON + .06 CFMS PER SF. OF THE | | | AREA. PLEASE SEE THE CALCULATION RATES LISTED UNDER | | | "OFFICES" IN THE TABLE FOR ALL OTHER ROOMS AND SPACES | | | SHOWN ON THE PLANS.BASED. | | | IN REGARD TO THE CALCULATIONS ON SHEET M-1, REFER TO | | | SECTION 403.2 EXCEPTION: WHERE THE REGISTERED DESIGN | | | PROFESSIONAL DEMONSTRATES THAT AN ENGINEERED | | | VENTILATION SYSTEM DESIGN WILL PREVENT THE MAXIMUM | | | CONCENTRATION OF CONTAMINANTS FROM EXCEEDING THAT | | | OBTAINABLE BY THE RATE OF OUTDOOR AIR VENTILATION | | | DETERMINED IN ACCORDANCE WITH SECTION 403.3, THE | | | MINIMUM REQUIRED RATE OF OUTDOOR AIR SHALL BE REDUCED | | | IN ACCORDANCE WITH SUCH ENGINEERED SYSTEM DESIGN. IF | | | CHOOSING THIS EXCEPTION PROVIDE DETAILS AND | | | SPECIFICATIONS FOR THE ENGINEERED SYSTEM. REFER TO | | | SECTION 403.3 EXCEPTION: THE OCCUPANT LOAD IS NOT | | | REQUIRED TO BE DETERMINED BASED ON THE ESTIMATED | | | MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE 403.3 | | | WHERE APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY | | | OF AN ALTERNATE ANTICIPATED OCCUPANT DENSITY. IF | | | CHOOSING THIS EXCEPTION, APPROVED STATISTICAL DATA | | | DOCUMENTATION MUST BE PROVIDED. | | | | | | 2) PLEASE CORRECT NOTE #7 TO INDICATE THE LOCATION OF | | | THE DS DETECTOR TO BE IN THE RETURN AIR SYSTEM, AND | | | PROVIDE A SYMBOL ON THE PLAN TO INDICATE COMPLIANCE. | | | PLACE A NOTE INDICATING THAT BOTH UNITS WILL BE LINKED | | | TOGETHER FOR FAN SHUT DOWN IF THE THE DS DETECTOR | | | ACTIVATES. | | | | | | 3) PROVIDE SHUTOFF DAMPERS FOR THE O/A INTAKE ON THE | | | RTU'S AND INDICATE HOW THEY WILL BE CONTROLLED- SECTION | | | C403.2.4.4 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-03-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-03-25 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-03-25 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2016-03-25 14:37:31 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020539 | | | 3/25/16 | | | | | | 1) SHEET M-1: THE O/A CALCULATIONS ARE BASED ON AN | | | OCCUPANT LOAD THAT DOES NOT MATCH THE OCCUPANT LOAD ON | | | THE PLANS OR TABLE 403.3. ADDITIONALLY, AIR | | | INFILTRATION SHALL NOT BE USED TO PROVIDE AIR BALANCE | | | OR PRESSURE EQUALIZATION- SECTION 501.4. | | | 2) PROVIDE AN EXHAUST FAN EQUIPMENT SCHEDULE ON THE | | | PLANS AND SUBMIT AN MIAMI- DADE NOA OR FLORIDA PRODUCT | | | APPROVAL FOR THE FAN OR LOUVER. | | | 3) INDICATE THE CLEARANCE DISTANCE MEASUREMENTS FOR THE | | | EXHAUST DUCT TERMINATIONS AS REQUIRED BY SECTION | | | 501.3.1 FBC-14 MECHANICAL. | | | 4) INDICATE THE TYPE AND GAGE OF METAL BATHROOM/UTILITY | | | ROOM EXHAUST DUCT TO BE USED- REFER TO CHAPTER 4 OF | | | SMACNA, AND INDICATE THE EXHAUST CFMS AT THE EXHAUST | | | INLET IN THE UTILITY ROOM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-02-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-24 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-24 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2016-02-24 17:18:16 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020539 | | | 2/24/16 | | | | | | 1) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND | | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | OCCUPIED ROOMS AND SPACES OF THE NEW FITNESS CENTER- | | | SEE TABLE 403.3 FBC-14 MECHANICAL. | | | 2) AC COOLING AND HEATING CALCULATIONS ARE REQUIRED FOR | | | THE NEW RT SEE SECTION C403.2.1 CALCULATION OF HEATING | | | AND COOLING LOADS, FBC-14 ENERGY CONSERVATION. | | | 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY | | | CONSERVATION: THE PROPOSED NEW A3 OCCUPANCY IS A CHANGE | | | OF OCCUPANCY FROM THE PREVIOUS B OCCUPANCY AND | | | THEREFORE MUST BE IN COMPLIANCE WITH THE ENERGY CODE. | | | PLEASE SEE SECTIONS C101.5.1 AND C101.5.1.1 AND SUBMIT | | | COMPLIANCE FORMS USING EITHER THE PRECRIPTIVE OR | | | PERFORMANCE- BASED METHOD. | | | 4) SHEET M-1: PLEASE LABEL EACH OF THE AC SYSTEMS SHOWN | | | ON THE PLAN AND INDICATE WHETHER THEY ARE NEW OR | | | EXISTING. INDICATE ON THE PLAN WHERE THE RTU'S ARE | | | LOCATED AND SHOW OUTLINES OF THEIR SUPPLY AND RETURN | | | PLENUMS | | | 5) M-1: INDICATE THE FLEX DUCT SIZES, AND ANY BRANCH | | | DUCTS NOT SIZED. | | | 6) PROVIDE RETURN AIR SYSTEMS FOR BOTH OF THE RTU'S- | | | SECTION 601.5 FBC-14 MECHANICAL. | | | 7) M-2: THE RTU MOUNTING DETAIL SHOWN AT THE TOP OF THE | | | PLAN SHEET IS MISSING- NO DIAGRAM IS SHOWN. | | | 8) M-2: PLEASE CLARIFY IF TWO NEW RTU'S ARE BEING | | | INSTALLED: THE TWO MOUNTING DETAILS ON THIS SHEET- ONE | | | WITH CURB ADAPTOR, AND ONE WITHOUT- APPEAR TO INDICATE | | | TWO DIFFERENT UNITS. CLARIFY IF A NEW ROOF OPENING IN | | | THE STRUCTURE MUST BE ACCOMPLISHED TO INSTALL THE NEW | | | RTU AND PROVIDE ENGINEERED STRUCTURAL DETAILS IF | | | APPLICABLE. | | | 9) PROVIDE COMPLETE EQUIPMENT SCHEDULES FOR THE RTU'S | | | 10) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE | | | RTU'S AND CLEARANCE DISTANCE MEASUREMENTS FROM ANY | | | EXHAUST OR VENT OUTLETS TO THE AIR INTAKES. | | | 11) PLEASE NOTE THAT THERE MAY BE ADDITIONAL COMMENTS | | | WHEN REVISED, CORRECTED PLANS HAVE BEEN SUBMITTED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2016-05-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-05-11 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-05-11 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2016-04-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-04-27 |
Time |
05:17 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-04-27 |
Time |
04:19 |
Sent To |
|
|
| Notes |
| 2016-04-26 10:37:27 | 1) A FOLDING OR NON-FOLDING SEAT IS REQUIRED IN | | | TRANSFER TYPE SHOWER COMPARTMENTS PER THE 2014 | | | FBC-ACCESSIBILITY SEC.608.4. YOUR RESPONSE TO MY | | | PREVIOUS COMMENT DOES NOT MAKE SENSE TO ME AS YOU ARE | | | REFERRING TO A CODE SECTION FOR ROLL-IN TYPE SHOWERS | | | AND THE SIZE OF THE SHOWERS ON THE PLANS DO NOT COMPLY | | | WITH THE MINIMUM DIMENSIONS REQUIRED FOR A ROLL-IN TYPE | | | SHOWER PER THE FAC SEC.608.2.2. THE SIZES ON THE PLANS | | | ARE FOR A TRANSFER TYPE SHOWER, NOT A ROLL-IN. 2ND | | | REQUEST. | | | 2)THE SHOWER SEAT SHALL COMPLY WITH 2014 | | | FBC-ACCESSIBILITY SEC.610.3. IN TRANSFER-TYPE SHOWERS, | | | THE SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT | | | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE | | | TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND | | | 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH | | | FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR 610.3.2. 2ND | | | REQUEST | | | 3) SUBMIT AN ELEVATION OF THE WING WALLS AND SHOW THE | | | HEIGHT. ANY PORTION OF THE WING WALL LOCATED GREATER | | | THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE | | | FINISH FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES | | | MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH PER 2014 | | | FAC SEC. 307.2. WHY NOT PUT AN OPTIONAL SKIRT ON THE | | | HIGH SIDE DRINKING FOUNTAIN TO KEEP THE LEADING EDGE | | | BELOW 27 INCHES? | | | 4) SHT. P-2 - THE SIDE WALL GRAB BAR FOR THE WATER | | | CLOSET SHALL COMPLY WITH FAC SEC.604.5.1. SHOW THE | | | DIMENSIONS ON THE PLANS.2ND REQUEST. | | | 5) THE GRAB BARS IN THE SHOWERS SHALL BE LOCATED ACROSS | | | THE CONTROL WALL AND BACK WALL TO A POINT 18 INCHES | | | FROM THE CONTROL WALL. SHOW THIS ON THE PLANS. SEE FAC | | | FIGURE 608.3.1. | | | 6) THE SHOWER CONTROLS SHALL BE LOCATED A MAXIMUM OF 15 | | | INCHES FROM THE CENTERLINE OF THE REQUIRED SEAT TOWARD | | | THE SHOWER OPENING. SHOW THIS ON THE PLANS. | | | 7) THE FIRST WATER CLOSET THAT IS CONNECTED TO THE | | | BUILDING DRAIN CREATES PLUMBING CODE VIOLATIONS. THE | | | LOCATION OF THE WATER CLOSETS CREATES A WET VENT FOR | | | THE WATER CLOSETS AND THE FIXTURES DISCHARGING INTO THE | | | WET VENT VIOLATES THE 2014 FBC-PLUMBING SEC.912.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-04-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-04-12 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-04-11 |
Time |
04:08 |
Sent To |
|
|
| Notes |
| 2016-04-12 15:02:48 | 1) THE SHOWER SEAT SHALL COMPLY WITH 2014 | | | FBC-ACCESSIBILITY SEC.610.3. IN TRANSFER-TYPE SHOWERS, | | | THE SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT | | | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE | | | TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND | | | 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH | | | FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR 610.3.2. | | | 2) SUBMIT AN ELEVATION DETAIL FOR THE DRINKING | | | FOUNTAINS. THE FOUNTAINS SHALL COMPLY WITH FAC SEC. 307 | | | FOR PROTRUDING OBJECTS. 307.2 PROTRUSION LIMITS. | | | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM) | | | AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH | | | FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM) | | | MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH. AN | | | OPTIOAAL SKIRT MAY BE REQUIRED FOR THE HIGH SIDE | | | DRINKING FOUNTAIN. | | | 3) SHT. P.1 - THE DOOR IN THE MEN'S ROOM SWINGS INTO | | | THE CLEAR FLOOR SPACE FOR THE SHOWER AND THE LAVATORY | | | AND THE DOOR IN THE WOMEN'S RESTROOM SWINGS INTO THE | | | CLEAR FLOOR SPACEFO THE LAVATORY. THE DOOR SHALL NOT | | | SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY | | | FIXTURE PER THE 2014 FAC SEC, PER THE FAC SEC.603.2.3.. | | | REFERE TO EXCEPTION #2. | | | 4) THE WATER CLOSETS SHALL BE LOCATED A MINIMUM OF 16 | | | INCHES AND A MAXIMUM OF 18 INCHES TO THE CENTERLINE OF | | | THE WATER CLOSET TO AN ADJACENT WALL. 2014 FAC | | | SEC.604.2. SHOW THIS ON THE ENLARGED PLANS ON SHT.P.2. | | | 5) THE LOCATION OF THE GRAB BARS FOR THE WATER CLOSETS | | | SHALL COMPLY WITH FAC SEC.604.5 THROUGH 604.5.2 & | | | FIGURES 604.5.1 & 604.5.2. | | | 6) SHOW THE INSIDE CLEAR DIMENSIONS ( LENGTH X WIDTH) | | | OF BOTH TOILET ROOMS. THE DIMENSIONS SHOWN ON SHTS. P.1 | | | & P.2 ARE NOT INSIDE DIMENSIONS. | | | 7) SHT. P.2 - 608.2.1 TRANSFER TYPE SHOWER | | | COMPARTMENTS. | | | TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES | | | (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS | | | MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND | | | SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE | | | FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES | | | (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG | | | MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE | | | PROVIDED. THE PLANS SHOW THE CLEAR FLOOR SPACE MEASURED | | | FROM THE WALL OPPOSITE THE CONTROLS. | | | 8) GRAB BARS ARE REQUIRED IN THE SHOWERS PER FAC | | | SECS.608.3, 608.3.1. | | | 9) THE SHOWER CONTROLS SHALL COMPLY WITH FAC | | | SEC.608.5.1, 309.4, 608.6.SUBMIT DETAIL FOR REVIEW. | | | 10) THE SHOWER THRESHOLD SHALL COMPLY WITH FAC | | | SEC.608.7. | | | 11 ) SHT. PL.2 - THE MINIMUM SIZE OF THE WATER HEATER | | | PAN DRAIN SHALL BE 3/4 INCH PER THE 2014 FPC | | | SEC.504.7.1.THE PLAN SHOWS 1/2". | | | 12) THE HEATE PAN SHALL BE A MINIMUM OF 1 1/2 INCHES | | | DEEP PER THE 2014 FPC SEC.504.7.1. | | | 13) THE WATER RISER APPEARS TO HAVE THE HOT AND COLD | | | WATER LINES REVERSED. CLARIFY. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-02-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-02-23 |
Time |
06:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-02-19 |
Time |
18:13 |
Sent To |
|
|
| Notes |
| 2016-02-23 06:57:21 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. P-1 THE FLOOR PLAN DOES NOT MATCH THE REST OF | | | THE PLAN AND IS ADDRESSED DIFFERENTLY PLEASE CLARIFY. | | | PER WPB AMEND. TO FBC 107.2.1 | | | | | | 2. SHT. HC.1 THE TEXT IS PRINTED VERY BLURRY AND IS | | | UNCLEAR PLEASE PROVIDE A SHEET THAT IS PRINTED CLEARLY | | | PER WPB AMEND. TO FBC SEC. 107.2.1.4 | | | | | | 3. SHT. PL.1 WATER FOUNTAIN CAN NOT TIE INTO THE WET | | | VENT OF BATHROOM GROUP | | | PER. FBC PL SEC. 912.1 | | | | | | 4. SHT. PL.1 REFERENCES A 40 GAL. WATER HEATER FIXTURE | | | SCHEDULE ON PL.2 REFERENCES A 50 GAL. PLEASE CLARIFY. | | | PER WPB AMEND. TO FBC 107.2.1 | | | | | | 5. SHOWER SEAT SHALL COMPLY WITH FBC ACC. SEC 610 | | | PLEASE SHOW ON PLAN. | | | PER WPB AMEND. TO FBC 107.2.1 | | | | | | 6. SHT. SHOW WATER HAMMER ARRESTORS ON WATER RISER | | | DIAGRAM. | | | PER WPB AMEND. TO FBC 107.2.1 |
|
|