Plan Review Details - Permit 16020513
Plan Review Stops For Permit 16020513
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-25 Cont ID  
Sent By rmcdouga Date 2016-02-25 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2016-02-25 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-22 Cont ID  
Sent By rmcdouga Date 2016-02-22 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2016-02-16 Time 10:15 Sent To  
Notes
2016-02-16 10:16:08REVISION ROUTED TO RMCDOUGAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-25 Cont ID  
Sent By rmcdouga Date 2016-02-25 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2016-02-25 Time 15:30 Sent To  
Notes
2016-02-25 15:36:04THE REVISION IS TO REPLACE THE DUCT WORK ON TWO
 EXISTING A/H UNITS AND REVISIONS TO OTHER DUCT WORK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-22 Cont ID  
Sent By rmcdouga Date 2016-02-22 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2016-02-22 Time 07:30 Sent To  
Notes
2016-02-22 08:02:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE REVISED PLANS SHOW THE ADDITION OF TWO (2) NEW
 HVAC SYSTEMS (#S 4 & 5) ON THE SECOND FLOOR. NO
 INCREASE TO THE VALUE OF WORK WAS LISTED ON THE
 REVISION FORM. FBC 109.3
  
 2) PROVIDE THE EQUIPMENT SCHEDULES FOR THE TWO (2) NEW
 AHUS AND CONDESERS ON THE MECHANICAL PLANS. 107.2.1
  
 3) PROVIDE LOAD CALCULATIONS FOR THE NEW SYSTEMS.
 FBCR-M1401.3
  
  
  