Plan Review Details - Permit 16020495
Plan Review Stops For Permit 16020495
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-16 Cont ID  
Sent By ccole Date 2016-02-16 Time 13:34 Rev Time 0.00
Received By ccole Date 2016-02-12 Time 16:17 Sent To  
Notes
2016-02-12 16:17:45MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-18 Cont ID  
Sent By ccole Date 2016-03-18 Time 10:11 Rev Time 0.00
Received By ccole Date 2016-03-18 Time 10:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-16 Cont ID  
Sent By ccole Date 2016-02-16 Time 13:34 Rev Time 0.00
Received By ccole Date 2016-02-16 Time 13:34 Sent To  
Notes
2016-02-16 13:41:191ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020495
 2/16/16
  
 1) THIS APPEARS TO BE A NEW WALK-IN COOLER INSTALLATION
 IN AN EXISTING RESTAURANT- PLEASE PROVIDE A DIMENSIONED
 FLOOR PLAN LAYOUT THAT CLEARLY SHOWS THE LOCATION OF
 THE NEW COOLER.
 2) INDICATE ON THE PLAN THE LOCATIONS OF THE EVAPORATOR
 AND CONDENSER UNITS, AND PROVIDE WIND LOAD ENGINEERING
 FOR INSTALLATION OF THE EXTERIOR CONDENSER.
 3) PLEASE CLARIFY IF ELECTRIC IS TO BE PROVIDED UNDER
 THIS PERMIT APPLICATION OR IF TO BE UNDER SEPARATE
 PERMIT.
 4) PROVIDE A CONDENSATE DISPOSAL PLAN INCLUDING THE
 TYPE AND SIZE OF PIPING, PIPING RUN AND DISCHARGE
 LOCATION
 5) I AM CHALLENGING THE $2,858.00 VALUE ON THE PERMIT
 APPLICATION IN ACCORDANCE WITH SECTION 109.3, WPB
 AMENDMENTS OT THE FBC-14 BUILDING CODE. TOTAL VALUE
 SHALL INCLUDE THE LABOR, MATERIALS, AND EQUIPMENT.
 PLEASE PROVIDE AN ACCURATE VALUE OR A VALUE WILL BE
 PLACED ON THE PROJECT BASED ON CURRENT VALUATION DATA
 TABLES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  