Plan Review Details - Permit 16020468
Plan Review Stops For Permit 16020468
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By albarran Date 2016-03-14 Time 15:09 Rev Time 0.00
Received By albarran Date 2016-03-14 Time 14:44 Sent To I
Notes
2016-03-14 15:10:52ALL PREVIOUSLY MENTIONED DEFICIENCKIES HAVE BEEN
 SATISFACTORILY CORRECTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-19 Cont ID  
Sent By albarran Date 2016-02-19 Time 13:15 Rev Time 0.00
Received By albarran Date 2016-02-19 Time 12:23 Sent To I
Notes
2016-02-19 13:15:141ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 2. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 3. THE LIGHTING PLAN IS MISSING A FIXTURE LEGEND
 4. HOW WILL THE LIGHTING IN THE OPERATIONS AREA BE
 DIMMED/CONTROLLED? W/O A FIXTURE LEGEND DIMMING
 CAPABILITIES OF THE FIXTURES IS NOT KNOWN AND ALL
 LIGHTING IS ON A SINGLE CIRCUIT IN THAT AREA.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By albarran Date 2016-03-14 Time 15:12 Rev Time 0.00
Received By albarran Date 2016-03-11 Time 15:33 Sent To  
Notes
2016-03-14 15:13:413/14/16 PASSED EXPEDITED ELECTRICAL REVIEW. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL READY BIN "W".
 MA
2016-03-11 15:33:31MALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-19 Cont ID  
Sent By albarran Date 2016-02-19 Time 13:16 Rev Time 0.00
Received By albarran Date 2016-02-12 Time 14:00 Sent To  
Notes
2016-02-19 13:17:402/19/16 FAILED 1ST ELECTRICAL REVIEW. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN "W".
 MA
2016-02-12 14:00:18REVISION ROUTED TO MALBARRAN