Plan Review Details - Permit 16020455
Plan Review Stops For Permit 16020455
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-01 Cont ID  
Sent By ccole Date 2016-03-01 Time 17:28 Rev Time 0.00
Received By ccole Date 2016-03-01 Time 11:02 Sent To  
Notes
2016-03-01 11:02:15RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-16 Cont ID  
Sent By ccole Date 2016-02-16 Time 07:54 Rev Time 0.00
Received By ccole Date 2016-02-12 Time 11:45 Sent To  
Notes
2016-02-12 11:46:03ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-01 Cont ID  
Sent By ccole Date 2016-03-01 Time 17:28 Rev Time 0.00
Received By ccole Date 2016-03-01 Time 17:28 Sent To  
Notes
2016-03-01 17:30:32MECHANICAL PROVISOS:
 PERMIT #16020455
 3/1/16
  
 1) VALUE INCREASE FROM $29, 426.00 TO $53,326.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-16 Cont ID  
Sent By ccole Date 2016-02-16 Time 07:55 Rev Time 0.00
Received By ccole Date 2016-02-16 Time 07:55 Sent To  
Notes
2016-02-16 08:08:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020455
 2/16/16
  
 1) PROVIDE THE SCOP RATING ON THE EQUIPMENT SCHEDULE
 FOR THE NEW LIEBERT SYSTEM- SEE TABLE C403.2.3(10)
 FBC-14 ENERGY CONSERVATION.
 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE NEW CU-2 ON THE EXISTING EXTERIOR PAD.- SECTION
 301.15 FBC-14 MECHANICAL.
 3) PLEASE NOTE THAT THE PERMIT VALUE SHALL BE BASED ON
 LABOR, MATERIALS, AND EQUIPMENT, THEREFORE THE COST OF
 THE NEW 20-TON SYSTEM MUST BE INCLUDED IN THE TOTAL
 PROJECT COST- SECTION 109.3 WPB AMENDMENTS TO THE
 FBC-14 BUILDING CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  