Plan Review Details - Permit 16020418
Plan Review Stops For Permit 16020418
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-17 Cont ID  
Sent By jwitmer Date 2016-05-16 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2016-05-14 Time 10:30 Sent To  
Notes
2016-05-14 11:29:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020418 / STADIUM, NATIONALS
 CLUBHOUSE & PRACTICE FIELDS
 W. P. B. PERMIT: 16020419/ ASTROS CLUBHOUSE
 W. P. B. PERMIT: 16020417/ TEAM STORE & BAR
  
 ADD: 5444 N. HAVERHILL RD.
  
 CONT: HUNT CONSTRUCTION
  
 TEL: 561-568-8045 / MICHAEL SANCHEZ
  
 E-MAIL: [email protected]
  
 HCS ARCHITECT/ INTERIOR DESIGNER
 ASSOCIATE ARCHITECT/ INTERIOR DESIGNER
 GLIDDEN SPINA INTERIORS
 STRUCTURAL ENGINEER
 BLISS & NYITRAY, INC
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: SAT. MAY 17/016
 ACTION: BUILDING PROVISO
  
  
 1) BUILDING PROVISO: SHEET 0349_A2-120 & 0350_A2-121.
 ROOF TOP MECHANICAL SCREENS. DETAILS 8 &9/ A6.21 &
 08/A7.21 . FINAL DIMENSIONS & LOCATION OF THE
 MECHANICAL SCREEN TO BE DETERMINED BY THE LOCATION AND
 SIZE OF THE MECHANICAL EQUIPMENT.
  
 2A) BUILDING PROVISO: DELEGATE ENGINEER. ADDITIONAL
 INFORMATION REQUIRED. 2014 FBC-B 410.4./ FBC-B 410.4,
 LOADING REQUIREMENTS FOR THE RAISED DECK( TABLE
 1607.1), HANDRAIL , GUARDRAIL ASSEMBLY (1607.8) AND
 STAIR(TABLE 1607.1).
  
 2B) PROVISO: RESPONSE COMMENT: 1ST ROUND OF COMMENTS.
 FOR BOTH PLATFORMS PLEASE SHOW HOW COMPLIANCE WITH
 VERTICAL ACCESSIBILITY WILL BE MET.2014 201.1.1
 VERTICAL ACCESSIBILITY REQUIREMENTS.
  
 2C ) BUILDING PROVISO: DELEGATE ENGINEER. THE INTERVIEW
 ROOM 50/ 11709 ON THE RIGHT INDICATES A STAGE DETAIL ON
 SHEET 07 / A2.712 . 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. 2014 FBC-B 410.4./ FBC-B 410.4, LOADING
 REQUIREMENTS FOR THE RAISED DECK( TABLE 1607.1),
 HANDRAIL , GUARDRAIL ASSEMBLY (1607.8) AND STAIR(TABLE
 1607.1).
  
 3) REVISION REQUIRED. SHEET 0392_A2-421 NOW DOES SHOW
 THE 6 HANDICAPPED SHEETS ON THE SAME LEVEL AS WELL AS
 THE STRUCTURAL SHEET 0612_S4.31 DETAIL 8. THE 2 SHEETS
 MENTIONED ABOVE DO NOT HAVE ANY ELEVATION TAGS STATING
 AT WHAT ELEVATION THE AISLE TOP OF SLABS FINISH.
 THE DETAIL SHEET 0487_A6.11 DETAIL 07 STILL SHOW THE
 VIP DUG OUT SEATS AT ELEVATION 99.0 FT. NGVD. SHEET
 0389_A2.411 JUST TO THE DETAIL TAG DETAIL 07/A6.11
 STILL SHOWS THE MAIN CONCURS AISLE AT ELEVATION 99 FT.
 AND IN THE SAME DETAIL THE 6 HANDICAPPED WHEEL CHAIRS
 ARE AT A FINISH SLAB OF 100 FT.NGVD.
  
 4) PROVISO: BUILDER AT OWN RISK!!! SHEET 0390_A2-412.
 THE PLANS INDICATE THE USE OF (3) INCLINED STAIRWAY
 CHAIRLIFT. PLEASE PROVIDE DOCUMENTATION THAT THIS
 PRODUCT WILL MEET THE REQUIREMENTS OF ASME A18.1. 2014
 FBC-ACCESSIBILITY CODE 410.1.
  
 5) BUILDING PROVISO: SHEET 0540_A8-31. PLEASE PROVIDE
 THE ELEVATOR MANUFACTURERS PRODUCT AND DATA AND SHOP
 DRAWINGS WILL BE SUBMITTED TO THE DESIGN PROFESSIONAL
 FOR REVIEW AND SHOP DRAWING STAMP OF APPROVAL BEFORE
 BEING SUBMITTED TO THE CITY BUILDING DEPARTMENT FOR
 REVIEW. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET 0601_S2.611 MILB OBSERVATION TOWER PLANS NOT
 IN THIS THIS OF DOCUMENTS, TO BE PERMITTED SEPARATELY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-17 Cont ID  
Sent By jwitmer Date 2016-04-17 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2016-04-16 Time 06:32 Sent To  
Notes
2016-04-17 12:03:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020418 / STADIUM, NATIONALS
 CLUBHOUSE & PRACTICE FIELDS
 W. P. B. PERMIT: 16020419/ ASTROS CLUBHOUSE
 W. P. B. PERMIT: 16020417/ TEAM STORE & BAR
  
 ADD: 5444 N. HAVERHILL RD.
  
 CONT: HUNT CONSTRUCTION
  
 TEL: 561-568-8045 / MICHAEL SANCHEZ
  
 E-MAIL: [email protected]
  
 HCS ARCHITECT/ INTERIOR DESIGNER
 ASSOCIATE ARCHITECT/ INTERIOR DESIGNER
 GLIDDEN SPINA INTERIORS
 STRUCTURAL ENGINEER
 BLISS & NYITRAY, INC
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: SAT.-SUN. APRIL 16-17/2016
 ACTION:
  
 1-3) COMPLIED .
  
 4)BUILDING PROVISO: SHEET 0349_A2-120 & 0350_A2-121.
 ROOF TOP MECHANICAL SCREENS. DETAILS 8 &9/ A6.21 &
 08/A7.21 . FINAL DIMENSIONS & LOCATION OF THE
 MECHANICAL SCREEN TO BE DETERMINED BY THE LOCATION AND
 SIZE OF THE MECHANICAL EQUIPMENT.
  
 5-6) COMPLIED.
  
 7) SHEET 0374_A2.217:
  
 7A) BUILDING PROVISO: DELEGATE ENGINEER. ADDITIONAL
 INFORMATION REQUIRED. 2014 FBC-B 410.4./ FBC-B 410.4,
 LOADING REQUIREMENTS FOR THE RAISED DECK( TABLE
 1607.1), HANDRAIL , GUARDRAIL ASSEMBLY (1607.8) AND
 STAIR(TABLE 1607.1).
  
 7B) PROVISO: RESPONSE COMMENT:
 1ST ROUND OF COMMENTS. FOR BOTH PLATFORMS PLEASE SHOW
 HOW COMPLIANCE WITH VERTICAL ACCESSIBILITY WILL BE
 MET.2014 201.1.1 VERTICAL ACCESSIBILITY REQUIREMENTS.
  
 7C ) BUILDING PROVISO: DELEGATE ENGINEER. THE INTERVIEW
 ROOM 50/ 11709 ON THE RIGHT INDICATES A STAGE DETAIL ON
 SHEET 07 / A2.712 . 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. 2014 FBC-B 410.4./ FBC-B 410.4, LOADING
 REQUIREMENTS FOR THE RAISED DECK( TABLE 1607.1),
 HANDRAIL , GUARDRAIL ASSEMBLY (1607.8) AND STAIR(TABLE
 1607.1).
  
 7D-E) COMPLIED.
  
 8-13) COMPLIED.
  
 14) 0389_A2-411:
 14A) COMPLIED. SHEET A6.11 DETAIL 8 DOES SHOW THE
 PLATFORM LIFT. NEW CONSTRUCTION ALLOWS THE USE OF
 PLATFORM LIFTS UNDER THE 2014 FBC-ACCESSIBILITY
 CODE206.7,2FOR ACCESSIBILITY AND DISPERSION AND LINE OF
 SITE REQUIREMENTS OF 221 AND 802.
  
 14B) SEMI-COMPLIED. THIS WILL BE A GENERAL COMMENT FOR
 THE WHOLE OF THE STADIUM SEATING. PLEASE PROVIDE HOW
 CODE COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE
 SECTIONS IS ACHIEVED:
 14B)(1) 221.2.1.1 SEMI COMPLIED. GENERAL SEATING.
 WHEELCHAIR SPACES COMPLYING WITH 802.1 SHALL BE
 PROVIDED IN ACCORDANCE WITH TABLE 221.2.1.1.
  
 14B)(2) 2ND REQUEST. THERE SEEMS TO BE A DISCREPANCY
 BETWEEN SHEET 0541_A9-01, 0389_A2-411 & 0487_A6-11
 DETAIL 5 & 0612_S4-31. THE (6) ACCESSIBLE SEATS IN BOWL
 SECTION 01 THE VIP DUGOUT SEATS ARE NOT ACCESSIBLE ON
 THE SHEETS LISTED ABOVE WITH EXCEPTION TO THE
 ACCESSIBLE SEATING CHART FOUND ON 0541_A9-01. THE
 DISPERSION OF SEATS WOULD APPEAR TO BE A LITTLE OFF AS
 WELL AS THE COUNT.!!!! MARK UPS ON SHEET 0541_A9-01
 COMMENT FROM THE 1ST SET OF COMMENTS. 221.2.1.2 LUXURY
 BOXES, CLUB BOXES, AND SUITES IN ARENAS, STADIUMS, AND
 GRANDSTANDS. IN EACH LUXURY BOX, CLUB BOX, AND SUITE
 WITHIN ARENAS, STADIUMS, AND GRANDSTANDS, WHEELCHAIR
 SPACES COMPLYING WITH 802.1 SHALL BE PROVIDED IN
 ACCORDANCE WITH TABLE 221.2.1.1.
  
  
 14B)(3) 221.2.1.3 OTHER BOXES. IN BOXES OTHER THAN
 THOSE REQUIRED TO COMPLY WITH 221.2.1.2, THE TOTAL
 NUMBER OF WHEELCHAIR SPACES REQUIRED SHALL BE
 DETERMINED IN ACCORDANCE WITH TABLE 221.2.1.1.
 WHEELCHAIR SPACES SHALL BE LOCATED IN NOT LESS THAN 20
 PERCENT OF ALL BOXES PROVIDED. WHEELCHAIR SPACES SHALL
 COMPLY WITH 802.1.
  
 14C) COMPLIED
  
 14D) 2ND REQUEST. THE SEATING PLAN FOUND ON 0541_A9-01
 IN THE BERM AREA 02 SHOWS 11 ACCESSIBLE SEATS AT WHAT
 APPEARS TO BE GRADE LEVEL. SHEET 0336_A2.02 &
 0385_A2-424 IN THE BOWL SECTION 4 DOES SHOW CONTOUR
 LINES AND IT WOULD APPEAR WHERE THESE SEATS ARE LOCATED
 THE BERM IS IN FRONT OF THEM, THE BALL GAME WOULD NOT
 BE VISIBLE? 2014 FBC-ACCESS. CODE 802.2.LINE OF SIGHT.
 COMMENT 1ST ROUND. ACCESS. CODE 221.5 LAWN SEATING.
 LAWN SEATING AREAS AND EXTERIOR OVERFLOW SEATING AREAS,
 WHERE FIXED SEATS ARE NOT PROVIDED, SHALL CONNECT TO AN
 ACCESSIBLE ROUTE.
  
 14E) SEMI- COMPLIED. ACCESS. CODE 221.6 STADIUMS,
 ARENAS, AND GRANDSTANDS. WHEELCHAIR SPACES AND
 COMPANION SEATS SHALL BE DISPERSED TO ALL LEVELS THAT
 INCLUDE SEATING SERVED BY AN ACCESSIBLE ROUTE.
  
 14F) SEMI-COMPLIED. ACCESS. CODE 221.7 SEATING
 ENCIRCLING A FIELD OF PLAY OR PERFORMANCE. IN ASSEMBLY
 AREAS THAT ARE REQUIRED TO HORIZONTALLY DISPERSE
 WHEELCHAIR SPACES AND COMPANION SEATS BY SECTION
 221.2.3.1 AND THAT HAVE SEATING ENCIRCLING, IN WHOLE OR
 IN PART, A FIELD OF PLAY OR PERFORMANCE, WHEELCHAIR
 SPACES AND COMPANION SEATS SHALL BE DISPERSED AROUND
 THAT FIELD OF PLAY OR PERFORMANCE AREA.
  
 15) PROVISO: BUILDER AT OWN RISK!!! SHEET 0390_A2-412.
 THE PLANS INDICATE THE USE OF (3) INCLINED STAIRWAY
 CHAIRLIFT. PLEASE PROVIDE DOCUMENTATION THAT THIS
 PRODUCT WILL MEET THE REQUIREMENTS OF ASME A18.1. 2014
 FBC-ACCESSIBILITY CODE 410.1.
  
 16) COMPLIED, HYDROTHERAPY POOLS.
  
 17) SHEET 0509_A7-11: PROVISO : HOW RAILINGS ARE TO BE
 READ. SHEET A2.421- A2. 424. THE DRAWING ARE TO BE READ
 FROM THE PLAN TO DETAIL. THEY SHOULD DETERMINE THE
 RAILING REQUIREMENTS BY REVIEWWING THE PLANS, WHICH
 PROVIDE A RAILING DESIGNATION, THEN REVIEIWING THE
 RAILING SCHEDULE TO CONFIRM WHICH RAIL TYPE IS
 REQUIRED. SHOP DRAWING ARE TO BE SUBMITTED TO THE
 DESIGNER OF RECORD FOR APPROVAL WITH SHOP DRAWING STAMP
 OF APPROVAL BEFORE BEING SUBMITTED TO THE CITY BUILDING
 DEPARTMENT.
  
 18) SHEET 0533_A8-01:
  
 18A) COMPLIED.
  
 18B) COMPLIED/ 2 ? INCHES BETWEEN WALL AND HANDRAIL
 NFPA REQUIREMENT.
  
 19-20) COMPLIED.
  
 21) BUILDING PROVISO: SHEET 0540_A8-31. PLEASE PROVIDE
 THE ELEVATOR MANUFACTURER?S PRODUCT AND DATA AND SHOP
 DRAWINGS WILL BE SUBMITTED TO THE DESIGN PROFESSIONAL
 FOR REVIEW AND SHOP DRAWING STAMP OF APPROVAL BEFORE
 BEING SUBMITTED TO THE CITY BUILDING DEPARTMENT FOR
 REVIEW. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 22) SHEET 0601_S2.611 MILB OBSERVATION TOWER PLANS NOT
 IN THIS THIS OF DOCUMENTS, TO BE PERMITTED SEPARATELY.
  
 23) ELECTRONIC SIGNATURES MISSING ON SHEETS:
 0542-1_A9-111
 0542-2_A9-115
 0543_A9-121
 0543_A9-122
 054-2_A9-124
 054-3_A9-125
 0543-4_A9-126
 0543-5_A9-128
 0543-6_A9-129
 0544_A9-132
 0544-1_A9-134
 0544-2_A9-135
 0545_A9-217
 0545-1_A9-218
 0545-2_A9-219
 0545-3_A9-227
 0545-2_A9-228
 0546_A9-312
 0546-1_A9-313
 0546-2_A9-314
 0546-3_A9-324
 0547_A10-110
 0547-1_A10-111
 0547-2_A10-115
 0548_A10-121
 0548-1_A10-122
 0548-2_A10-124
 0548-3_A10-125
 0548-4_A10-126
 0548-5_A10-128
 0548-6_A10-129
 0549_A10-132
 0549-1_A10-134
 0549-2_A10-125
 0550_A10-217
 0550-1_A10-217
 0550-1_A10-218
 0550-2_A10-219
 0550-3_A10-227
 0550-4_A10-228
 0550-5_A10-312
 0550-6_A10-313
 0550-8_A10-324
  
 0598_S2-424 REUSED FROM STRUCTURE ONLY PERMIT CITY
 STAMP APPLIED.
 0600_S2-512 REUSED FROM STRUCTURE ONLY PERMIT CITY
 STAMP APPLIED.
 0614_S4-33 REUSED FROM STRUCTURE ONLY PERMIT CITY STAMP
 APPLIED.
 0618_S6-12 REUSED FROM STRUCTURE ONLY PERMIT CITY STAMP
 APPLIED.
 0622_S7-14 REUSED FROM STRUCTURE ONLY PERMIT CITY STAMP
 APPLIED.
  
  
 24) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-04 Cont ID  
Sent By jwitmer Date 2016-03-04 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2016-02-23 Time 10:50 Sent To  
Notes
2016-03-04 09:51:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020418 / STADIUM, NATIONALS
 CLUBHOUSE & PRACTICE FIELDS
 W. P. B. PERMIT: 16020419/ ASTROS CLUBHOUSE
 W. P. B. PERMIT: 16020417/ TEAM STORE & BAR
  
 ADD: 5444 N. HAVERHILL RD.
 CONT: HUNT CONSTRUCTION
 TEL: 561-568-8045 / MICHAEL SANCHEZ
 E-MAIL: [email protected]
  
 HCS ARCHITECT/ INTERIOR DESIGNER
 ASSOCIATE ARCHITECT/ INTERIOR DESIGNER
 GLIDDEN SPINA INTERIORS
  
 STRUCTURAL ENGINEER
 BLISS & NYITRAY, INC
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) SHEET 0339_A2-110 STADIUM CLUBHOUSE LEVEL SECTOR A.
 THIS COMMENT WILL STAND AS A COMMON COMMENT FOR ALL
 SHEETS. SEE ROOMS 11029A, 11025 & 11032, ALL HAVE A
 SIMILAR WALL DETAIL, WHAT APPEARS TO BE POSSIBLY A WALL
 ACCESS PANEL TO GAIN ACCESS TO A WALL CLEAN OUT, PLEASE
 PROVIDE ADDITIONAL INFORMATION ON THIS DETAIL. IT MAY
 INTERFERE WITH THE CLEAR FLOOR SPACE FOR FIXTURES IF
 NOT AN ACCESS COVER. 2014 FBC- ACCESSIBILITY CODE
 604.3.2 OVERLAP. SEE ROOM 11032.
  
 2) SHEET 0340_A2-111 110 STADIUM CLUBHOUSE LEVEL SECTOR
 B. THE DOOR 11103 PLEASE DIMENSION THE CLEAR FLOOR
 SPACE TO THE RIGHT SIDE OF THE LATCH, IT MAY NOT MEET
 THE MANEUVERING CLEARANCES REQUIRED BY THE 2014
 FBC-ACCESSIBILITY CODE 404.2.4 AND FIGURE 404.2.4.`(A).
 REQUIRED 18 INCHES.
  
 3) SHEETS 0345_A2-115 & 0355_A2-125 BOTH SHOW GATE G1
 THAT CAN BE LOCKED & BLOCKS AN ELEVATOR AND STAIRWAY.
 THIS GATE IS NOT FOUND ON THE 3 SHEETS OF DOOR
 SCHEDULE?S AND WOULD NEED TO COMPLY WITH EITHER
 2014 FBC-B 1008.1.10 PANIC HARDWARE OR 1008.2.1. PANIC
 HARDWARE IS NOT REQUIRED ON GATES SURROUNDING STADIUMS
 WHERE SUCH GATES ARE UNDER CONSTANT IMMEDIATE
 SUPERVISION WHILE THE PUBLIC IS PRESENT, AND WHERE SAFE
 DISPERSAL AREAS BASED ON 3 SQUARE FEET (0.28 M2) PER
 OCCUPANT ARE LOCATED BETWEEN THE FENCE AND ENCLOSED
 SPACE. SUCH REQUIRED SAFE DISPERSAL AREAS SHALL NOT BE
 LOCATED LESS THAN 50 FEET (15 240 MM) FROM THE ENCLOSED
 SPACE. SEE SECTION 1027.5 FOR MEANS OF EGRESS FROM SAFE
 DISPERSAL AREAS.
  
 4) SHEET 0349_A2-120 & 0350_A2-121. PROVISO: ROOF TOP
 MECHANICAL SCREENS. DETAILS 8 &9/ A6.21 & 08/A7.21 .
 FINAL DIMENSIONS & LOCATION OF THE MECHANICAL SCREEN TO
 BE DETERMINED BY THE LOCATION AND SIZE OF THE
 MECHANICAL EQUIPMENT.
  
 5) SHEET 0351_AS-122 DRINKING FOUNTAIN. SHOWS A DETAIL
 06/0527-4_A7.65. THIS DETAIL SHOWS RAILINGS ON EACH
 SIDE OF THE DRINKING FOUNTAIN, IT APPEARS TO TRY
 COMPLYING WITH THE 2014 FBC-ACCESSIBILITY CODE
 PROTRUDING OBJECTS SECTION 307.3. SEE NOTE: RAIL TYPE
 XX, XX INCHES HIGH.
  
 6) SHEET 0428_A3-58 DETAIL # 1 SHOWS A BAR AT A HEIGHT
 OF 3 FT. 6 INCHES. PLEASE SHOW COMPLIANCE WITH THE:
 2014 FBC-ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES
 ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT
 LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING
 SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2014 FBC-ACCESSIBILITY CODE 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 7) SHEET 0374_A2.217:
  
 7A) THE INTERVIEW ROOM 50/ 11709 ON THE LEFT END OF THE
 ROOM SHOWS A RAISED PLATFORM BUT THERE APPEARS TO BE A
 DETAIL TAG THAT WAS BURIED INTO A WALL LINE DOES NOT
 IDENTIFY WHERE TO LOCATE THE DETAIL. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED. 2014 FBC-B 410.4./
 FBC-B 410.4, LOADING REQUIREMENTS FOR THE RAISED DECK(
 TABLE 1607.1), HANDRAIL , GUARDRAIL ASSEMBLY (1607.8)
 AND STAIR(TABLE 1607.1).
  
 7B) FOR BOTH PLATFORMS PLEASE SHOW HOW COMPLIANCE WITH
 VERTICAL ACCESSIBILITY WILL BE MET.2014 201.1.1
 VERTICAL ACCESSIBILITY REQUIREMENTS.
  
 7C ) THE INTERVIEW ROOM 50/ 11709 ON THE RIGHT
 INDICATES A STAGE DETAIL ON SHEET 07 / A2.712 .
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. 2014 FBC-B
 410.4./ FBC-B 410.4, LOADING REQUIREMENTS FOR THE
 RAISED DECK( TABLE 1607.1), HANDRAIL , GUARDRAIL
 ASSEMBLY (1607.8) AND STAIR(TABLE 1607.1).
  
 7D) DOOR JAMB 11713 IT APPEARS TO BE DEEPER ON THE
 INSIDE THAN 8 INCHES WILL NEED TO COMPLY WITH 2014
 FBC-ACCESSIBILITY CODE 404.2.4.3.
  
 7E) ASTROS LOBBY CLUBHOUSE STAIR DETAIL 01/A8.20 PLEASE
 PROVIDE CODE COMPLIANCE WITH 2014 FBC-ACCESS. CODE
 307.4 & FIGURE 307.4.
  
 8) SHEET 0375_A2-218. DOOR 11829B THIS DOOR IS A 3?-6?
 DOOR, IT MAY OR MAY NOT PROVIDE THE 18 INCHES ON THE
 PULL SIDE OF THE LATCH. 2014 FBC-ACCESSIBILITY CODE.
 404.2.4. MANEUVERING CLEARANCES.
  
 9) 0381_A2-237 THE BRIDGE SHOW A CUT SECTION THROUGH,
 SECTION0501_ A7.03. DETAIL 06. SHOWS AIPP BRIDGE
 GUARDRAIL BY OTHERS. THIS PLAN DOES NOT GIVE THE
 GUARDRAIL THE CODE DESIGN CRITERIA AS FOUND IN THE 2014
 FBC-B 1607.8.1. FOR THE OTHER DESIGNERS TO USE AS A
 GUIDELINE.
  
 10) SHEET 0384_A2-312.
 10A) MILB KITCHEN DOOR 11234 MAY NOT HAVE 18 INCHES FOR
 MANEUVERING CLEARANCES PULL LATCH SIDE OF THE DOOR, NOT
 DIMENSIONED AS TO 18 INCHES MINIMUM. 2014 FBC-ACCESS.
 CODE 404.2.4.MANEUVERING CLEARANCES & FIGURE
 404.2.4.1.(A).
  
 10B) DESIGNER OF RECORD SHOWS THE LAUNDRY ROOM 11211 IS
 INDICATED 1 HR. RATED. NEITHER DOOR 11211 NOR 11211B
 SHOW A DOOR RATING DOOR SCHEDULE 0411_A3-32. FBC-B
 TABLE 716.5. NOT A SINGLE DOOR IS SHOWN TO BE FIRE
 RATED.
  
 11) SHEET 0385_A2-313.
 11A) THE DESIGNER OF RECORD INDICATES THE LAUNDRY ROOM
 11313 TO HAVE 1 HOUR FIRE RATING. THE DOOR SCHEDULE ON
 0411_A3-32 IS MISSING THE DOOR RATING. FBC-B TABLE
 716.5.
  
 11B) PLEASE SEE MLB TRAVEL EQUIPMENT MANAGER ROOM 11309
 ENTRY DOOR THE WALL THICKNESS APPEARS TO BE
 APPROXIMATELY 1 FOOT THICK. THE DOOR WILL NEED TO BE IN
 COMPLIANCE WITH FBC-ACCESSIBILITY CODE 404.2.4.3
 RECESSED DOOR AND GATES.
  
 12) SHEET 0386_A2-314:
 12A) EXAM ROOM 11425. ENTRY DOOR 11425 APPEARS TO BE IN
 A WALL THICKER THAN 8 INCHES K1/R8, SHOW COMPLIANCE
 WITH 2014 WITH FBC-ACCESSIBILITY CODE 404.2.4.3
 RECESSED DOOR AND GATES.
  
 12B) DOOR 11237B WILL NEED TO SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY 404.2.4.3 RECESSED DOOR AND GATES.
  
 12C) THE ELECTRIC ROOM DOOR 11412 IS SHOWN TO BE IN A 1
 HOUR RATED WALL, SHOW COMPLIANCE WITH FBC-B TABLE
 716.5.
  
 12D) THE ELECTRIC ROOM DOOR 11412 IS SHOWN TO BE IN A
 WALL DEEPER THAN 8 INCHES K1/R8 WILL NEED TO COMPLY
 WITH 2014 FBC-ACCESSIBILITY 404.2.4.3 RECESSED DOOR AND
 GATES.
  
 13) 0388_A2-324:
 13A) JUST TO THE LEFT OF DOOR 12412B THERE IS A 6INCH
 DIMENSION AND ARROW TO A LINE BUT THERE IS NO REFERENCE
 TO WHAT THE 6 INCHES IS INDICATING CHANGE IN GRADE? IF
 SO PLEASE REVIEW 2014 1003.5 ELEVATION CHANGES.
  
 13B) DOOR 12419 NOT DIMENSIONED IT APPEARS THAT IT MAY
 NEED TO COMPLY WITH 2014 FBC-ACCESS. CODE 404.2.4
 MANEUVERING CLEARANCES, 18 INCHES LATCH SIDE OF THE
 DOOR.
  
 14) 0389_A2-411:
 14A) THERE IS NOMENCLATURE ON THE PLANS WITH A
 DIRECTIONAL ARROW INDICATING A PLATFORM LIFT BUT THE
 DIRECTIONAL ARROW APPEARS TO BE POINTING AT A STAIR OR
 POSSIBLE ROOF? THE PROVIDED SECTION THROUGH THIS AREA
 DETAIL 07/A6.11 SHOWS STAIRS NO ACCESSIBLE LIFT.
 PROVIDE CODE COMPLIANCE. 2014 FBC202.1 & 410.
  
 14B) THIS WILL BE A GENERAL COMMENT FOR THE WHOLE OF
 THE STADIUM SEATING. PLEASE PROVIDE HOW CODE COMPLIANCE
 WITH THE 2014 FBC-ACCESSIBILITY CODE SECTIONS IS
 ACHIEVED:
 14B)(1) 221.2.1.1 GENERAL SEATING. WHEELCHAIR SPACES
 COMPLYING WITH 802.1 SHALL BE PROVIDED IN ACCORDANCE
 WITH TABLE 221.2.1.1.
  
 14B)(2) 221.2.1.2 LUXURY BOXES, CLUB BOXES, AND SUITES
 IN ARENAS, STADIUMS, AND GRANDSTANDS. IN EACH LUXURY
 BOX, CLUB BOX, AND SUITE WITHIN ARENAS, STADIUMS, AND
 GRANDSTANDS, WHEELCHAIR SPACES COMPLYING WITH 802.1
 SHALL BE PROVIDED IN ACCORDANCE WITH TABLE 221.2.1.1.
  
 14B)(3) 221.2.1.3 OTHER BOXES. IN BOXES OTHER THAN
 THOSE REQUIRED TO COMPLY WITH 221.2.1.2, THE TOTAL
 NUMBER OF WHEELCHAIR SPACES REQUIRED SHALL BE
 DETERMINED IN ACCORDANCE WITH TABLE 221.2.1.1.
 WHEELCHAIR SPACES SHALL BE LOCATED IN NOT LESS THAN 20
 PERCENT OF ALL BOXES PROVIDED. WHEELCHAIR SPACES SHALL
 COMPLY WITH 802.1.
  
 14C) JUST TO THE RIGHT OF THE VIP SEATING THERE IS
 ANOTHER SET OF STADIUM STYLE SEATS, THERE IS NO
 ELEVATIONS PROVIDED FOR EACH TIER TO BE ABLE TO JUDGE
 THE SIZE OF THE STEPS.
  
 14D) ACCESS. CODE 221.5 LAWN SEATING. LAWN SEATING
 AREAS AND EXTERIOR OVERFLOW SEATING AREAS, WHERE FIXED
 SEATS ARE NOT PROVIDED, SHALL CONNECT TO AN ACCESSIBLE
 ROUTE.
  
 14E) ACCESS. CODE 221.6 STADIUMS, ARENAS, AND
 GRANDSTANDS. WHEELCHAIR SPACES AND COMPANION SEATS
 SHALL BE DISPERSED TO ALL LEVELS THAT INCLUDE SEATING
 SERVED BY AN ACCESSIBLE ROUTE.
  
 14F) ACCESS. CODE 221.7 SEATING ENCIRCLING A FIELD OF
 PLAY OR PERFORMANCE. IN ASSEMBLY AREAS THAT ARE
 REQUIRED TO HORIZONTALLY DISPERSE WHEELCHAIR SPACES AND
 COMPANION SEATS BY SECTION 221.2.3.1 AND THAT HAVE
 SEATING ENCIRCLING, IN WHOLE OR IN PART, A FIELD OF
 PLAY OR PERFORMANCE, WHEELCHAIR SPACES AND COMPANION
 SEATS SHALL BE DISPERSED AROUND THAT FIELD OF PLAY OR
 PERFORMANCE AREA.
  
 15) SHEET 0390_A2-412. THE PLANS INDICATE THE USE OF
 (3) INCLINED STAIRWAY CHAIRLIFT. PLEASE PROVIDE
 DOCUMENTATION THAT THIS PRODUCT WILL MEET THE
 REQUIREMENTS OF ASME A18.1. 2014 FBC-ACCESSIBILITY CODE
 410.1.
  
 16) SHEETS 0399_A2-613 & 0400_A2-614:
 16A) DETAIL 02/NATIONS. THE HYDROTHERAPY POOLS DO NOT
 SHOW HANDRAILS/ GUARDRAILS REQUIRED BY THE 2014 FBC-B
 454.1.2.5.5.
  
 16B) DETAIL 02 / NATIONALS. THE TREADMILL HYDROTHERAPY
 POOL DOES NOT INDICATE ANY ACCESS POINTS INTO THE POOL
 REQUIRED BY THE FBC-B 454.1.2.5.
  
 16C) THERE IS NOT ENOUGH INFORMATION TO BE ABLE TO DO A
 COMPLETE AND THOROUGH REVIEW OF THE HYDROTHERAPY POOL
 TO BE ABLE TO COMPLY WITH THE SECTION 454.1 OF THE
 FLORIDA BUILDING CODE.
 THE EXCEPTIONS FOUND UNDER F.S. 514.0115 (5) DOES ALLOW
 FOR A VARIANCE FROM THE FBC-B. THE DEPARTMENT MAY GRANT
 VARIANCES FROM ANY RULE ADOPTED UNDER THIS CHAPTER
 PURSUANT TO PROCEDURES ADOPTED BY DEPARTMENT RULE. THE
 DEPARTMENT MAY ALSO GRANT, PURSUANT TO PROCEDURES
 ADOPTED BY DEPARTMENT RULE, VARIANCES FROM THE
 PROVISIONS OF THE FLORIDA BUILDING CODE SPECIFICALLY
 PERTAINING TO PUBLIC SWIMMING POOLS AND BATHING PLACES
 WHEN REQUESTED BY THE POOL OWNER OR THE POOL OWNER?S
 REPRESENTATIVE TO RELIEVE HARDSHIP IN CASES INVOLVING
 DEVIATIONS FROM THE FLORIDA BUILDING CODE PROVISIONS,
 WHEN IT IS SHOWN THAT THE HARDSHIP WAS NOT CAUSED
 INTENTIONALLY BY THE ACTION OF THE APPLICANT, WHERE NO
 REASONABLE ALTERNATIVE EXISTS, AND THE HEALTH AND
 SAFETY OF THE POOL PATRONS IS NOT AT RISK.
  
 17) SHEET 0509_A7-11: RAIL TYPE SCHEDULE INDICATES
 VARIOUS RAIL TYPES AND HEIGHTS. IT WOULD HELP IS THERE
 WAS A COLUMN THAT WOULD GIVE THE SHEET NUMBER WE COULD
 LOCATE THE USE OF EACH RAIL TYPE SINCE THEY ALL ARE NOT
 42 INCHES IN HEIGHT. 2014 FBC-B 1013.3 HEIGHT. REQUIRED
 GUARDS SHALL NOT BE LESS THAN 42 INCHES (1067 MM) HIGH,
 MEASURED VERTICALLY.
  
 18) SHEET 0533_A8-01:
 18A) DETAILS 2 , 3 & 4 ALL INDICATE STEEL STRINGER
 STAIRS WITH WHAT APPEARS TO BE OPEN STAIRS. PLEASE SHOW
 COMPLIANCE WITH:
 2014 FBC-B 1009.7.5.3 SOLID RISERS.
 2014 FBC-ACCESS. CODE 504.3. OPEN RISERS ARE NOT
 PERMITTED.
  
 18B) DETAILS 06 & 12 BOTH SHOW THE HANDRAILS 2 ? INCHES
 FROM THE WALL. THE 2014 FBC-B SECTION 1012.7 CLEARANCE
 INDICATES A MINIMUM OF 1 ? INCHES FROM A WALL OR OTHER
 SURFACES. THE 2014 FBC-ACCESSIBILITY CODE SECTION 505.5
 CLEARANCE INDICATES THE 1 ? INCH MEASUREMENT AS AN
 ABSOLUTE, NOTE THIS IS NOT A FLORIDA SPECIFIC GRAY BOX
 BUT FEDERAL ADA REQUIREMENT. THE REASONING BEHIND THIS
 REQUIREMENT IS A PERSON WITH ACCESSIBILITY ISSUES MAY
 SLIP AND FALL AND GET THEIR ARM IS PINCHED HIGHER UP
 THE ARM AND CAN BREAK THEIR ARM, AT 1 ? INCHES IT IS
 MORE LIKELY THEY WILL GET THEIR WRIST PINCHED WHICH HAS
 A MOVABLE JOINT.
 THIS OCCURRENCE WOULD BE WHERE THERE IS NO VERTICAL
 ACCESSIBILITY BY ELEVATOR OR BY A PLATFORM LIFT.
 OTHERWISE SIGNAGE SHOULD BE PLACED WHERE THE ACCESSIBLE
 STAIRS ARE LOCATED.
  
 19) SHEET 035_A8-10 STADIUM STAIR PLAN AND DETAILS DOES
 NOT PROVIDE WHAT THE MINIMUM DESIGN CRITERIA UNIFORM
 LIVE LOADS 2014 FBC-B TABLE 1607.1.
  
 20) SHEET 0538_A8-21 SECTIONS 01 & 04. PROVIDE CODE
 COMPLIANCE WITH THE 2014 FBC-B:
 3011.1 ELECTROLYSIS PROTECTION FOR UNDERGROUND
 HYDRAULIC ELEVATOR CYLINDERS.
 ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE
 CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT
 TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL
 CYLINDER AND GROUND CATHODE.
 3011.1.1 THE PLASTIC CASING SHALL BE CAPPED AT THE
 BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED
 TO ENSURE WATER TIGHTNESS.
  
 21) SHEET 0540_A8-31. PLEASE PROVIDE MANUFACTURES
 SPECIFICATIONS ON THE TYPE OF ELEVATOR WILL BE IN THIS
 INSTALLATION. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 22) SHEET 0601_S2.611 MILB OBSERVATION TOWER PLANS NOT
 IN THIS THIS OF DOCUMENTS, TO BE PERMITTED SEPARATELY.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2016-06-16 Cont ID  
Sent By vperez Date 2016-06-16 Time 09:42 Rev Time 0.00
Received By vperez Date 2016-06-16 Time 09:42 Sent To  
Notes
2016-06-16 09:42:46INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE NOTE THAT ALL L/V SYSTEMS ARE TO BE PERMITTED
 SEPARATELY. FBC 107.3.5
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-05-19 Cont ID  
Sent By vperez Date 2016-05-19 Time 15:47 Rev Time 0.00
Received By vperez Date 2016-05-19 Time 15:47 Sent To  
Notes
2016-05-19 15:47:47ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO- EMERGENCY LIGHTING AS ADDRESSED BY EOR
 SUBJECT TO FIELD INSPECTOR APPROVAL
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-04-22 Cont ID  
Sent By albarran Date 2016-04-22 Time 10:59 Rev Time 0.00
Received By albarran Date 2016-04-15 Time 08:25 Sent To  
Notes
2016-04-22 11:00:262ND ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 WITH THE EXCEPTION OF THE MISSING ILLUMINATION ISSUES,
 THE BELOW MENTIONED ITEMS CAN BE EASILY ADDRESSED WITH
 THE PROPER NOTES. THEREFORE A NARRATIVE ADDRESSING THE
 ISSUES CAN BE ACCEPTED AND PLANS ISSUED WITH A PROVISO
 RELATING THERETO.
  
 AS USUAL, IF DURING THE PLAN REVIEW I MISUNDERSTOOD A
 SHEET?S INTENTION AND THE COMMENTS ISSUED ARE
 NON-APPLICABLE PLEASE CORRECT ME AND EXPLAIN.
  
 CORRECTIONS REQUIRED:
 SHEET E1.00-2, E2.111, E3.127, UPLOAD CORRUPTED,
 SHEET E2.110
 1. PER NEC 680.62 HYDRO TUB OUTLETS SHALL BE GFI
 PROTECTED.
 2. NEC 210.8(B)(7) LOCKER ROOM OUTLETS WITH AN
 ASSOCIATED SHOWER FACILITY SHALL BE GFCI PROTECTED.
 SHEET E2.119, E2.112, E2.113, E2.114, E2.117,
 1. NEC 210.8(B)(7) LOCKER ROOM OUTLETS WITH AN
 ASSOCIATED SHOWER FACILITY SHALL BE GFCI PROTECTED.
 SHEET E2.127
 1. NEC 210.63 REQUIRES A GFCI PROTECTED OUTLET WITH 25?
 OF EQUIPMENT. AD.0-AE.0/A04.5-A05
 SHEET E2.129
 1. EXPLAIN 208/1PH
 2. NEC 210.63 REQUIRES A GFCI PROTECTED OUTLET WITH 25?
 OF EQUIPMENT. OUTLET SHOWN ON PLANS IS OUTSIDE THE
 ROOM. A08.3-A08.9/AD
 3. SAME APPLIES FOR ADJACENT AREA. AD-AB.5/A07.5-A08
 SHEET E2.134, E2.132,
 1. TYPICAL PADDLE FAN NOTE ADDED TO PLANS.
 SHEET E2.411, E2.128, E2.126, E2.125, E2.122,
 1. EXPLAIN 208/1 PH
 2. PANEL SCHEDULE ON SHEET E5.01 DOES NOT INDICATE ANY
 LOADS ON CKTS 76,9 OF LP-NB-1
 SHEET E2.413, E2.412,
 1. MISSING THE WEATHER-RESISTANT NOTE ADDED TO ALL
 OTHER SHEETS.
 SHEET E3.112, E3.113, E3.114, E3.115, E3.117, E3.118,
 E3.119, E3.124, E30125, E3.126, E3.128, E3.134,
 1. ADDITIONAL EMERGENCY LIGHTING REQUIRED IN ROOMS,
 1240, 1235, (SHOWER AND TOILET AREAS OF 1204, 1207),
 1211, 1214, 1301, 1310, 1313, 1406, 1413, 1414, 1417,
 1419, 1506, 1508, 1512, 1713, 1706, 1708, 1707, 1801,
 1831, 1832, 1820, 1901, 1916, 1909, 2428, 2517, 2603,
 2607, 2608, 2605, 2616, AREA OF SO5-SO6/SC.5-SB.6,
 2811, 2509,
 2. LIGHTING CONTROL MISSING IN ROOMS 1205, 1206, 1208,
 1321, 1322, 1429, 1417, 1419, 1710, AREA OF
 SO5-SO6/SC.5-SB.6, 2811, JAN CLOSET BETWEEN 3410 &
 3413, 3407, NO3-NO3.5/NC-ND,
 3. ILLUMINATION AND CONTROL MISSING IN ROOM 1806, 1907,
 1908, 2504, 2508, 2509, CORRIDOR SH-SF/S13.25-S13.5,
 3421,
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-10 Cont ID  
Sent By albarran Date 2016-03-10 Time 18:56 Rev Time 0.00
Received By albarran Date 2016-03-07 Time 13:17 Sent To  
Notes
2016-03-10 18:57:591ST ELECTRICAL REVIEW NOTES FOR REVISION #:
 16020418, 16020417, 16020419
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET E0.01
 0. INCLUDE ON THE SHEET DRAWINGS THE DRAWING SCALE
 BEING USED. CITY OF WEST PALM BEACH AMENDMENTS LIMITS
 DRAWINGS TO NO LESS THAN 1/8? SCALE.
 1. THIS SYMBOL MAY INTERFERE OR BE CONFUSED WITH THAT
 OF THE EXIT LIGHTS.
 2. NEC 406.9(B), WEATHER-PROOF RECEPTACLES IN ?WET
 LOCATIONS? SHALL BE LISTED ?WEATHER-RESISTANT?.
 3. INDICATE ON THE LIGHTING LEGEND WHICH OF THE
 FIXTURES WILL HAVE A BATTERY PACK OR BE TIED INTO AN
 EMERGENCY LIGHTING CIRCUIT.
 SHEET E0.02
 1. INDICATE ON THE FIXTURE SCHEDULE WHICH OF THE
 FIXTURES WILL HAVE BATTERY BALLAST.
 SHEET E2.110, E2.111, E2.112, E2.113, E2.114, E2.115,
 E2.117, E2.118, E2.119, E2.121, E2.122, E2.123, E2.124,
 E2.125, E2.126, E2.127, E2.128, E2.129, E2.132, E2.134,
 E2.135, E2.136, E2.137, E2.145, E2.411, E2.412, E2.413,
 1. NEC 210.8(B)(7) RECEPTACLES IN LOCKER ROOMS WITH
 ASSOCIATED SHOWERS SHALL BE GFCI PROTECTED.
 2. NEC 408.9(B) .....AND BE LISTED "WEATHER-RESISTANT"
 "WR".
 SHEET E2.113
 1. IDENTIFY OR CORRECT THE ?NG? FOLLOWING THE NUMERIC
 RATING IN THE NUMBERED NOTES.
 SHEETS E2.116, E2.130, E2131, E2.140, E2.141, E2.142,
 E2.143, E2.144, E3.116,
 1. THESE SHEETS ARE MISSING. IS THIS PAGE INTENTIONALLY
 SKIPPED OR IS IT AN ERROR.
 SHEET E2.126 STORE AREA
 1. NEC 210.62 SHOW WINDOW REQUIREMENT, THERE SHALL BE A
 120 VAC OUTLET WITH 18? OF THE TOP OF EVERY SHOW WINDOW
 FOR EVERY 12? OF SHOW WINDOW OR MAJOR PORTION THEREOF.
 2. NEC 600.5 SIGN OUTLET REQUIREMENT. THERE SHALL BE A
 DEDICATED SIGN OUTLET AT EVERY PEDESTRIAN ENTRY DOOR.
 SHEET E3.110, E3.111,
 1. IN ADDITION TO THE MISSING EMERGENCY LIGHTING, YOU
 SHALL SHOW COMPLIANCE WITH FBC-EC405 FOR LIGHT
 REDUCTION.
 2. ACCORDING TO THE FIXTURE SCHEDULE THE EXIT LIGHTS DO
 NOT HAVE BATTERY BACK UP. (TYPICAL)
 SHEET E3.513
 1. EXHAUST FANS REQUIRED FOR THE TOILET ROOMS.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By albarran Date 2016-03-03 Time 14:09 Rev Time 0.00
Received By albarran Date 2016-03-03 Time 12:00 Sent To  
Notes
2016-03-03 14:10:17THERE IS A PROBLEM WITH THE PLANS AND/OR PROJECTDOX
 MAKING THE PLANS ILLEGIBLE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-04-20 Cont ID  
Sent By Mgonzale Date 2016-04-20 Time   Rev Time 0.50
Received By mgonzale Date 2016-04-20 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-04-19 Cont ID  
Sent By wjolin Date 2016-04-19 Time 10:23 Rev Time 0.00
Received By wjolin Date 2016-04-19 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-03-09 Cont ID  
Sent By wjolin Date 2016-03-09 Time 17:05 Rev Time 0.00
Received By wjolin Date 2016-03-09 Time 10:51 Sent To  
Notes
2016-03-09 11:01:155444 NORTH HAVERHILL ROAD
 PERMIT #16020418
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 SHEET LS1.02: A FIRE IN CORRIDOR #11237 HAS THE
 POTENTIAL TO BLOCK BOTH EXITS FROM COACH'S LOCKER
 #11415. PER SECTION 7.5.1.3.1 WHERE MORE THAN ONE EXIT,
 EXIT ACCESS, OR EXIT DISCHARGE IS REQUIRED FROM A
 BUILDING OR PORTION THEREOF, SUCH EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT
 MORE THAN
 ONE HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 SHEET A2.227: 1ST FLOOR LOBBY #11711 IS OPEN TO THE
 SECOND FLOOR RECEPTION #12704. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 SHEET A2.324 1ST FLOOR LOBBY #11408 IS OPEN TO THE
 SECOND FLOOR CORRIDOR #12412B. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 SHEET E1.00: PROVIDE AMBULANCE/RESCUE VEHICLE120V SHORE
 POWER RECHARGING STATION ALONG FIRE LANE NEAR SITE PLAN
 MARKER #8.
  
 SHEET E2.411: PROVIDE AMBULANCE/RESCUE VEHICLE120V
 SHORE POWER RECHARGING STATION IN VEHICLE ENTRANCE
 TUNNEL ADJACENT TO THE BULLPEN.
  
 IN GENERAL THE EMERGENCY LIGHTING AND EXIT SIGN
 PLACEMENT IS INCONSISTENT. FOR EXAMPLE:
 SHEET E3.110: COULD ONLY LOCATE 1 EMERGENCY LIGHT
 FIXTURE.
 SHEET E3.111: CORRIDOR #11130 INDICATES A LIGHT FIXTURE
 F7 WITH AN "EM" DESIGNATION. THIS APPEARS TO BE
 POSSIBLY EMERGENCY LIGHTING BUT THE EM ABBREVIATION IS
 NOT FOUND OR DESCRIBED ON SHEET E0.01. ALSO CORRIDOR
 #11130 HAS AN EXIT SIGN LEADING OCCUPANTS THROUGH A
 HIGHER HAZARD (MAINT. SHOP) WHICH IS NOT PERMITTED.
 SHEET E3.111: NO EMERGENCY LIGHTING ON MEZZANINE AND
 ONLY 1 EXIT SIGN PROVIDED IN MAINTENANCE SHOP #11125.
 SHEET E3.118: NO EXIT SIGNS IN LOCKER ROOM #11718.
 SHEET E3.119: NO EXIT SIGNS OR EMERGENCY LIGHTS IN MLB
 EQUIP. #11917; OTHER LARGE ROOMS SIMILAR TO THIS ROOM
 HAVE BOTH.
  
 FIRE ALARM PLANS DO NOT INDICATE A SCALE.
  
 FA2.110: DOES NOT APPEAR TO BE SUFFICIENT VISUAL
 COVERAGE IN UMPIRE SHOWER #11031.
  
 FA2.113: NO NOTIFICATION PROVIDED IN SAUNAS. INADEQUATE
 COVERAGE PROVIDED FOR EAST PORTION OF WEIGHTS #11318.
 NO NOTIFICATION CONFERENCE #11301.
  
 FA2.118: NO NOTIFICATION PROVIDED IN EAST PORTION OF
 KITCHEN. NO PULL STATION PROVIDED AT GYM STAIR EXIT
 DOOR.
  
 FA2.122: NO NOTIFICATION PROVIDED IN EAST PORTION OF
 KITCHEN.
  
 FA2.124: NO NOTIFICATION IN NORTH ROOM OF COMMISSARY
 #12405 AND WEST ROOM OF CONCESSION #12404.
  
 FA2.127: NO PULL STATION AT EXIT DOOR.
  
 FA2.128: NO PULL STATION AT EXIT DOOR.
  
 FA2.134: NO NOTIFICATION IN WOMENS' RESTROOM #13414.
  
 SIGNAGE: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SIGNAGE: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By wjolin Date 2016-03-03 Time 17:15 Rev Time 0.00
Received By wjolin Date 2016-02-23 Time 12:08 Sent To  
Notes
2016-02-24 16:00:495444 NORTH HAVERHILL ROAD
 PERMIT #16020418
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 SHEET LS1.02: A FIRE IN CORRIDOR #11237 HAS THE
 POTENTIAL TO BLOCK BOTH EXITS FROM COACH'S LOCKER
 #11415. PER SECTION 7.5.1.3.1 WHERE MORE THAN ONE EXIT,
 EXIT ACCESS, OR EXIT DISCHARGE IS REQUIRED FROM A
 BUILDING OR PORTION THEREOF, SUCH EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT
 MORE THAN
 ONE HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 SHEET A2.227: 1ST FLOOR LOBBY #11711 IS OPEN TO THE
 SECOND FLOOR RECEPTION #12704. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 SHEET A2.324 1ST FLOOR LOBBY #11408 IS OPEN TO THE
 SECOND FLOOR CORRIDOR #12412B. PER SECTION 8.6.9.2
 UNENCLOSED VERTICAL OPENINGS CREATED BY CONVENIENCE
 STAIRWAYS SHALL BE PERMITTED AS FOLLOWS: 1) THE
 CONVENIENCE STAIR OPENING SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS 2) THE CONVENIENCE STAIR OPENING SHALL
 BE PROTECTED IN ACCORDANCE WITH THE METHOD DETAILED FOR
 THE PROTECTION OF VERTICAL OPENINGS IN NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 ALL OF THE E2 AND E3 SERIES ELECTRICAL DRAWINGS ARE
 CORRUPT FILES OR THE PLANS HAVE NOT BEEN COMPLETED.
  
 SHEET E5-04 FIRE ALARM RISER: FILE IS CORRUPT OR PLAN
 HAS NOT BEEN COMPLETED.
  
 ALL OF THE FA2 SERIES FIRE ALARM DRAWINGS ARE CORRUPT
 FILES OR THE PLANS HAVE NOT BEEN COMPLETED.
  
 SIGNAGE: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SIGNAGE: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2016-05-12 Cont ID  
Sent By tklarge Date 2016-05-12 Time 10:44 Rev Time 0.00
Received By tklarge Date 2016-05-12 Time 10:32 Sent To  
Notes
2016-05-12 10:45:39THE GAS SHALL BE DONE UNDER A SEPARATE PERMIT. PLANS
 AND SPECIFICATIONS SHALL BE SUBMITTED FOR REVIEW. TKL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By tklarge Date 2016-04-28 Time 13:22 Rev Time 0.00
Received By tklarge Date 2016-04-27 Time 10:24 Sent To  
Notes
2016-04-27 15:02:261) THE RESPONSE FROM WSP FOR COMMENT #32 DOES NOT
 SATISFY THE COMMENT. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION SIZE AND TERMINATION OF ALL GAS VENTS FROM
 EQUIPMENT AND APPLIANCES THAT ARE REQUIRED TO BE VENTED
 TO THE EXTERIOR.2014 FGC SECS.502 THRU 505. THE REVIEW
 COMMENT WAS NOT SPECIFIC AS TO THE TYPE OF VENT
 INFORMATION THAT WAS BEING REQUESTED.
 2) SUBMIT A GAS EQUIPMENT SCHEDULE LISTING EACH GAS
 APPLIANCE/ PIECE OF EQUIPMENT, THE BTU VALUE, THE TAG /
 ITEM NUMBER AND THE PIPE SIZE FOR THE APPLIANCE
 /EQUIPMENT. I HAVE ALREADY REVIEWED THE K DRAWINGS.
 3) SHT. P5.401 & P5.401.3 - THE RISER SHOWS THE TOTAL
 BTU LOAD ON THE MAIN AND AT THE METER AS 9258 MBH.
 AFTER THE TWO GWH-2 WATER HEATERS THE LOAD IS REDUCED
 TO 5358 MBH. PLEASE CLARIFY AS TO HOW 9258 MBH MINUS
 1980 MBH EQUALS 5358 MBH. MY CALCULATION COMES TO 7278
 MBH .THIS LINE IS UNDERSIZED AND NEEDS TO BE 4 INCHES
 IN SIZE. THE ENTIRE LINE SHALL BE CHECKED FOR PROPER
 SIZING IN ACCORDANCE WITH 2014 FGC TABLE 402.4 (5).
 CLARIFY.
 4) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MEDIUM PRESSURE REGULATOR.
 2014 FGC SEC.409.4.
 5) SHT. P5.401 & P5.401.1 - THE 1 1/4 INCH LINE TO
 APPLIANCES #1047 & #1048 IS UNDERSIZED. THE MAXIMUM BTU
 LOAD ON A 1 INCH PIPE AT 30 FT. DEVELOPED LENGTH IS 583
 MBH PER FGC TABLE 402.4 (1).
 6) SHT. P5.401.1 - SIZE THE GAS LINE TO GWH-3 AND SHOW
 THE BTU LOAD ON THE RISER.
 7) SHT. P5.401.2 - SIZE THE PIPE TO GWH-3 DOWNSTREAM OF
 THE MP REGULATOR. THE LINE SHALL BE A MINIMUM OF 1 INCH
 PER FGC TABLE 402.4 (1).THE MEDIUM PRESSURE SIDE SHALL
 ALSO BE 1 INCH PER TABLE 403.4 (5).
 8) SHT. P5.402.1 - THE 3/4 INCH LINE TO ITEM #243 IS
 UNDERSIZED.THE MAXIMUM MBH ON A 3/4 INCH LINE AT 20 FT.
 IS 188 MBH. THE 1 INCH LINE CARRYING 440 MBH IS
 UNDERSIZED. THE MAXIMUM BTU LOAD ON A 1 INCH LINE AT 20
 FT. IS 353 MBH PER TABLE 402.4 (1) OF FGC.
 9) SHT. P5.402.1 - SIZE THE LINES TO UNITS MUA-A-2-2
 AND ERU-A-3-1 DOWNSTREAM OF THE MP REGULATOR. THE SIZE
 OF THE LINE TO ERU-A-3-1 SHALL BE A MINIMUM OF 1 INCH.
 FGC TABLE 402.4 (1).
 10) SIZE ALL SECTIONS OF PIPING DOWNSTREAM OF ALL MP
 REGULATORS.
 11) SHT. P5.402.1- THE LOW PRESSURE LINE SUPPLYING 440
 MBH TO ITEMS # 243, 246 & 247 IS UNDERSIZED. THE
 MINIMUM SIZE PIPE SHALL BE 1 1/4 INCHES. FGC TABLE
 402.4 (1).
 12) SHT. P5.402.1 - THE 3/4 INCH LOW PRESSURE LINE TO
 ITEM # 243 IS UNDERSIZED. THE MINIMUM SIZE SHALL BE 1
 INCH PER FGC TABLE 402.4.(1).
 13) SHT. P5.402.2 - SIZE THE LOW PRESSURE LINE
 DOWNSTREAM OF THE MP REGULATOR TO UNIT MUA-A-2-1.
 14) SHT. P5.402.2 - THE RISER SHOWS A 3/4 INCH LOW
 PRESSURE LINE TO ITEM #L2 CARRYING 350 MBH. THE MAXIMUM
 MBH ON A 3/4 INCH LINE AT 20 FT. IS 188 MBH. THE
 MINIMUM SIZE OF THIS LINE SHALL BE 1 INCH PER FGC TABLE
 402.4 (1).
 15) SHT. P5.402.2 - THE RISER SHOWS A 3/4 INCH LINE TO
 ITEM # L2 WITH A BTU LOAD OF 350 MBH AND ALSO A 1 INCH
 LINE SUPPLYING TWO ITEMS WITH THE SAME MBH LOAD OF 350.
 CLARIFY AND SHOW THE CORRECT PIPE SIZE.
 16) SHT. P5.402.2 - SIZE THE LOW PRESSURE LINE
 DOWNSTREAM OF THE PRESSURE REGULATOR AT GWH-1 AND TO
 EACH HEATER AND SHOW THE MBH LOAD FOR BOTH HEATERS.
 COMPLY WITH FGC TABLE 402.4 (1).
 17) SHT. P-5.402.2 - SIZE THE LOW PRESSURE LINES
 DOWNSTREAM OF THE MP REGULATOR TO EQUIPMENT ITEMS
 ERU-A-2-5 AND ERU-A-2-6.
 18) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO THE
 FUTURE POOL HEATER DOWNSTREAM OF THE MP REGULATOR. THE
 LINE SHALL BE A MINIMUM OF 1 1/4 INCHES PER 2014 FGC
 TABLE 402.4 (1).
 19) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO UNIT
 ERU-N-2-5 DOWNSTREAM OF THE MP REGULATOR. THE MINIMUM
 SIZE SHALL BE 1 INCH. SHOW THE BTU LOAD AND SIZE THE
 LINE UPSTREAM OF THE MP REGULATOR.
 20.) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO
 ITEMS # 146 & #148. THE MINIMUM SIZE SHALL BE 1 INCH.
 TABLE 402.4 (1) FGC.
 21) SHT. P5403.1 - THE 3/4 INCH MEDIUM PRESSURE LINE TO
 ITEMS #146 AND 148 IS UNDERSIZED. THE MINIMUM SIZE
 SHALL BE 1 INCH. TABLE 402.4 (5) FGC.
 22) SHT.P5.403.1 - THERE IS 1 INCH LOW PRESSURE LINE
 SERVING OUTLETS ADJACENT TO ITEMS # 146 AND # 148 WITH
 350 MBH. THIS LINE IS UNDERSIZED AND SHALL BE 1 1/4
 INCHES. ALSO, IDENTIFY THE APPLIANCES ON THESE OUTLETS.
 FGC TABLE 402.4 (1). THERE IS ALSO A 3/4 INCH LOW
 PRESSURE LINE CARRYING 175 MBH. THIS LINE IS
 UNDERSIZED. THE MINIMUM SIZE SHALL BE 1 INCH.
 23) SHT. P5.403.1 - SIZE THE LOW PRESSURE LINE TO
 DHU-N-2-1. THE MINIMUM SIZE OF THIS LINE SHALL BE 1
 INCH. FGC TABLE 402.4 (1).
 24) SHT. P5.403.2 - THE 1 1/4 INCH LOW PRESSURE LINE TO
 THE FOUR L2 ITEMS IS UNDERSIZED. THE MINIMUM SIZE SHALL
 BE 1 1/2 INCHES. A MAXIMUM OF 583 MBH IS ALLOWED ON A 1
 1/4 INCH LINE, 284 MBH ON A 1 INCH LINE, AND 151MBH ON
 A 3/4 INCH LINE. THESE LINES ARE ALSO UNDERSIZED. THE
 RISER SHOWS 700 MBH ON THIS LINE. ALSO, SHOW THE SIZE
 OF THE DROPS TO THE EQUIPMENT AND THE BTU LOAD OF AT
 EACH OUTLET. SIZE ALL SECTIONS OF THE SYSTEM AT THIS
 AREA. FGC TABLE 402.4 (1).
 25) SHT. P5.403.2 - THE 1 INCH AND 3/4 INCH LOW
 PRESSURE LINES TO ITEMS #37 AND #38 ARE UNDERSIZED. THE
 MAXIMUM MBH LOAD ON A 3/4 INCH LINE AT 30 FT. IS 151
 MBH AND 284 MBH ON A 1 INCH LINE. THESE LINES SHALL BE
 INCREASED TO 1 INCH AND 1 1/4 INCHES. FGC TABLE 402.4
 (1).
 26) SHT.P5.403.2 - THE 2 1/2 INCH LOW PRESSURE LINE TO
 THE TWO GWH-1 WATER HEATERS IS UNDERSIZED. THE MAXIMUM
 MBH ON A 2 1/2 INCH LINE AT 30 FT. IS 2680 MBH. THE
 LINE NEEDS TO BE 3 INCH. TABLE 402.4 (1).
 27) SHT. K2.111.1 - ITEM #38 IS SHOWN WITH A 3/4 INCH
 GAS SIZE BUT THE SCHEDULE ON SHT. P5.403 SHOWS THE GAS
 SIZE AS 1 1/4 INCH. CLARIFY.
 28) SHT. K2.112.1 - THE UTILITY SCHEDULE SHOWS ITEM
 3146 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.403 SHOWS AN
 1 1/4 GAS SIZE. CLARIFY.
 29) SHT. K2.113.1 - THE UTILITY SCHEDULE SHOWS ITEM #
 246 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.402 SCHEDULE
 SHOWS 1 1/4 INCHES.CLARIFY.
 30) SHT.K2.114.1 - THE UTILITY SCHEDULE SHOWS ITEM #
 354 WITH A 3/4 INCH GAS SIZE BUT SHT. P5.402 SCHEDULE
 SHOWS 1 1/4 INCHES. CLARIFY.
 31) IDENTIFY THE L 2 APPLIANCE. I COULD NOT FIND THIS
 ON THE UTILITY SCHEDULE.
 32) ENSURE THE GAS PIPE SIZES ON THE UTILITY SCHEDULES
 CORRELATE WITH THE SCHEDULES ON THE GAS PLANS.2014 FBC
 107.2.1.
 33) THERE ARE STILL NUMEROUS AREAS ON THE GAS RISERS
 WHERE PIPE SIZES ARE NOT SHOWN AND EQUIPMENT NOT
 LABELED.ENSURE ALL SECTIONS ARE CLEARLY SIZED AND
 OUTLETS LABELED AS TO THE EQUIPMENT BEING SERVED. 2014
 FBC 107.2.1.
 34) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 LOUVERS BEING USED TO PROVIDE THE COMBUSTION AIR FOR
 THE DRYERS AND SHOW THE LOCATIONS OF THE LOUVERS ON THE
 ARCHITECTURAL AND PLUMBING PLANS. LOUVERS SHALL COMPLY
 WITH THE 2014 FBC SEC.1609.1.2.1. SUBMIT PRODUCT
 APPROVALS FOR THE LOUVERS SHOWING COMPLIANCE FOR WIND
 LOAD REQUIREMENTS.
 35) WHERE ARE COMBUSTION AIR CALCULATIONS FOR THE REST
 OF THE APPLIANCES SUCH AS THE COOKING EQUIPMENT IN THE
 CONCESSION AREAS AND OTHER AREAS WHERE GAS FUELED
 EQUIPMENT IS LOCATED IN ROOMS, AREAS OR OTHER TYPE OF
 ENCLOSURES? 2014 FGC SEC.304.1, 304.5.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-24 Cont ID  
Sent By skennedy Date 2016-05-24 Time 08:58 Rev Time 0.00
Received By skennedy Date 2016-05-11 Time 12:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-28 Cont ID  
Sent By lmarchan Date 2016-04-28 Time 15:22 Rev Time 0.00
Received By lmarchan Date 2016-04-15 Time 09:06 Sent To  
Notes
2016-04-15 09:09:12PLANS UNDER 16020418

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-11 Cont ID  
Sent By cpuell Date 2016-03-11 Time 07:50 Rev Time 0.00
Received By cpuell Date 2016-02-16 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-19 Cont ID  
Sent By ccole Date 2016-05-19 Time 09:30 Rev Time 0.00
Received By ccole Date 2016-05-17 Time 13:44 Sent To  
Notes
2016-05-19 09:41:07MECHANICAL PROVISOS
 5/19/16
  
 SEPARATE PERMITS ARE REQUIRED FOR ALL KITCHEN EXHAUST
 HOODS AND FIRE SUPPRESSION SYSTEMS.
 REVISIONS TO THE APPROVED PLANS SHALL BE PROVIDED TO
 SHOW COMPLIANCE WITH THE FOLLOWING PROVISIONS.
  
 1) DUCT SMOKE DETECTORS SHALL BE PROVIDED IN THE RETURN
 AIR SYSTEMS OF THE ERUS. PROVIDE A NOTE IN THE
 EQUIPMENT SCHEDULE.
  
 2) THE DRYER EXHAUST DUCTS SHALL NOT EXTEND THROUGH THE
 RETURN AIR PLENUMS. THE DUCTS SHALL BE RE-ROUTED OR
 INSTALLED IN AN ENCLOSURE.
  
 3) THE CONTRACTOR SHALL SUBMIT APPROVED SHOP DRAWINGS
 FOR EQUIPMENT ACCESS PANELS.
  
 4) CHEMICAL AND PAINT STORAGE ROOMS: PROVIDE ON THE
 ARCHITECTURAL PLANS A COMPLETE LIST OF CHEMICALS AND
 PAINTS TO BE STORED IN THE ROOMS, THE HAZARD
 CLASSIFICATIONS FOR EACH PRODUCT, THE MAXIMUM ALLOWABLE
 QUANTITIES FOR EACH, AND THE ACTUAL AMOUNTS TO BE
 STORED.
  
 5) FIRE DAMPER LOCATIONS, SCHEDULES, AND INSTALLATION
 DETAILS.
  
 6) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR ALL EXTERIOR MECHANICAL EQUIPMENT INCLUDING RTU AND
 FAN CURBS, ROOF AND WAL-MOUNTED FANS, AC STANDS, AND
 LOUVERS ETC. SHALL BE REVIEWED AND APPROVED BY THE EOR,
 AND SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW AND
 APPROVAL PRIOR TO 1ST INSPECTION.
  
 7) PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION,
 THE REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEM COMMISSIONING AND
 COMPLETION IN ACCORDANCE WITH SECTION C408.2.4 AND
 C408.2.5 FBC-14 ENERGY CONSERVATION.
  
 8) REVISE SHEETS M2.114 & M2.117 TO INDICATE ADEQUATE
 EXHAUST CAPACITIES IN THE LOCKER AND BATH ROOMS PER THE
 CALCULATIONS ON SHEET M0.07.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-21 Cont ID  
Sent By ccole Date 2016-04-21 Time 11:42 Rev Time 0.00
Received By ccole Date 2016-04-19 Time 08:15 Sent To  
Notes
2016-04-21 11:45:572ND REVIEW: FBC 2014 MECHANICAL
 PERMIT 16020418
 4/19/16
  
 THE SECOND REVIEW OF THE PROJECT IS BASED ON THE
 REVISED PLANS AND NARRATIVE RESPONSES FROM WSP, AND
 SOME OF THE1ST REVIEW ISSUES THAT STILL EXIST.
  
 1) 1ST REVIEW COMMENT #2: REFER TO SHEET M0.07 & THE
 FOLLOWING SHEETS WHERE LOCKER ROOM EXHAUST AT A RATE OF
 .5 CFM PER SF. IS MISSING. A) M2.111- MEN'S AND WOMEN'S
 LOCKER ROOMS 11102 &11103. B) M2.113- MLB COACHES
 LOCKER 11302. C) M2.114- STAFF/COACHES LOCKER 11415
 (SEE SHEET M2.113 AND LABEL THE 16X14 EXHAUST RISER AND
 ROOF FAN). M2.117- MLB COACHES LOCKER 11702.
 2) 1ST REVIEW COMMENT #4: M0.07, ERU CALCULATIONS-
 REFER TO SECTION 403.2.1 ITEM #4. IT APPEARS BY THE
 CALCULATION THAT MORE THAN 10% OF THE EXHAUST AIR FROM
 THE LOCKER ROOM AND BATH AREAS IS BEING RECIRCULATED.
 PLEASE SUBMIT MANUFACTURER'S PRODUCT DATA SHEETS FOR
 THE ERU'S.
 3) 1ST REVIEW COMMENT #2: M0.07: VENTILATION
 CALCULATIONS FOR THE DHU'S NOT PROVIDED. PLEASE PROVIDE
 THE CALCULATIONS AND MANUFACTURER'S PRODUCT DATA
 SHEETS.
 4) 1ST REVIEW COMMENT #5: A) SHEET M0.02: PLACE A NOTE
 FOR REQUIRED DUCT SMOKE DETECTORS IN THE ERU SCHEDULE.
 B) M0.05: PLACE A NOTE REQUIRING A DUCT SMOKE DETECTOR
 FOR AHU-S-4-1. C) M701, NOTE M: PLEASE PROVIDE
 ADDITIONAL INFORMATION PERTAINING TO FAN SHUT DOWN.
 CLARIFY WHICH FANS WILL SHUT DOWN WHEN A DETECTOR
 ACTIVATES- THE UNIT FAN, FANS IN THE FIRE AREA, BOTH
 SUPPLY AND EXHAUST FANS IN THE FIRE AREA? D) IT MAY BE
 HELPFUL TO PLACE DS SYMBOLS AT THE REQUIRED LOCATIONS
 ON THE LAYOUT PLANS.
 5) M2.111, CHEMICAL AND PAINT STORAGE, 1ST REVIEW
 COMMENT #6: A) THE LETTER TITLED "LTAS BALLPARK OF THE
 PALM BEACHES-HAZMAT STORAGE.." AS NOTED IN THE
 NARRATIVE RESPONSE, WAS NOT UPLOADED FOR REVIEW,
 THEREFORE A COMPLETE REVIEW CANNOT BE COMPLETED AT THIS
 TIME. B) COMMENTS #6C- EXHAUST VENTILATION
 CALCULATIONS, AND #6D- MAKE UP AIR SOURCE LOCATION FOR
 THE EXHAUST STILL EXIST.
 6) M0.06, COMMENT #16: PLEASE INDICATE WHICH MUA'S
 LISTED IN THE SCHEDULE ON M0.05 CORRESPOND WITH THE AIR
 BALANCE CALCULATIONS. AS PREVIOUSLY NOTED, THE KITCHEN
 HOODS AND ALL ASSOCIATED MAKE-UP AIR AND EXHAUST
 SYSTEMS AND FIRE SUPPRESSION WILL BE DONE UNDER
 SEPARATE PERMIT. A) PLEASE REVIEW THE MUA SCHEDULE ON
 M0.05: THE SECTOR LOCATIONS OF THE MUA'S ON THE
 CONCOURSE LEVELS DO NOT APPEAR TO MATCH THE LOCATIONS
 SHOWN ON THE PLANS.
 7) M2.112, M2.117, M2.118, M2.119 COMMENT #17: PLEASE
 CLARIFY IF THE C, E & G TRANSFERS ARE TRANSFERRING THE
 AIR ABOVE OR BELOW THE CORRIDOR CEILINGS ON THESE PLANS
 AND OTHER PLANS WITH CORRIDORS.
 8) M2.113, COMMENT #21: COMBUSTION AIR AND LOCATION OF
 GIH-N-2-1 NOT SHOWN.
 9) M2.114, COMMENT #22 STILL EXISTS. REFER TO COMMENT
 #2 OF THIS REVIEW.
 10) M2.117, COMMENT #25 COMBUSTION AIR CALCULATION AND
 SOURCE OF THE AIR.
 11) M2.120, COMMENT #26: FOR CLARIFICATION PLEASE
 INDICATE THE TYPE OF EXHAUST DUCTWORK FOR THE TYPE 1
 HOODS.
 12) 1ST REVIEW COMMENT #27: THE REQUESTED WIND LOAD
 ENGINEERED INSTALLATION DETAILS FOR THE ROOFTOP
 MECHANICAL EQUIPMENT HAS NOT BEEN PROVIDED. REFERENCE
 IS MADE TO THE STRUCTURAL DRAWINGS IN THE NARRATIVE,
 HOWEVER NO EXACT SHEET IS REFERENCED AND THE REFERENCE
 TO ARCHITECTURAL SHEET A7.21 DOES NOT PROVIDE ANY INFO.
 PLEASE NOTE THAT THE REQUIRED ENGINEERING CAN BE DONE
 AS A DEFERRED SUBMITTAL, HOWEVER REQUIRED MECHANICAL
 INSPECTIONS WILL BE ON HOLD UNTIL ENGINEERING HAS BEEN
 REVIEWED AND APPROVED. GIVEN THE AMOUNT OF EQUIPMENT TO
 BE INSTALLED, IT IS HIGHLY RECOMMENDED THAT ENGINEERING
 IS EXPEDITED BY THE DESIGN PROFESSIONALS IN ORDER TO
 AVOID ANY DELAYS.
 13) M2.125, COMMENT #28: ENVIRONMENTAL AIR AS DEFINED
 IN SECTION 202 DOES NOT INCLUDE AIR EXHAUSTED FROM
 STORAGE ROOMS. PLEASE RELOCATE ALL EXHAUST OUTLETS TO
 MINIMUM 10' ABOVE ADJOINING GRADE AND REFER TO SECTIONS
 501.3, 501.3.1 (2), AND 501.3.1.1 FOR ADDITIONAL
 COMPLIANCES.
 14) 1ST REVIEW COMMENT #31A: IN RESPONSE TO THIS
 COMMENT ABOUT REQUIRED EQUIPMENT ACCESS PANELS, THE
 NARRATIVE STATES THE CONTRACTOR MAY PROVIDE A CEILING
 COORDINATION DRAWING DURING CONSTRUCTION. RESPECTFULLY,
 THE BUILDING DIVISION WILL REQUIRE THE DESIGN
 PROFESSIONALS TO PROVIDE THOSE DRAWINGS INDICATING
 PANEL LOCATIONS, PANEL SIZES, AND CONSTRUCTION DETAILS.
 PLEASE NOTE THAT PANELS SHALL BE SIZED LARGE ENOUGH TO
 REMOVE AND REPLACE THE EQUIPMENT LOCATED ABOVE THE
 CEILINGS- SECTION 306.1.
 15) 1ST REVIEW COMMENT #33A: UL APPROVED FIRE STOPPING
 ASSEMBLIES ARE REQUIRED FOR REFRIGERANT PIPING
 PENETRATING FIRE-RATED WALLS AND FLOORS. PLEASE REVISE
 DETAIL 2/M6.-01.
 16) 1ST REVIEW COMMENT #34: THE REQUESTED DETAILS WERE
 NOT PROVIDED, AND REFERENCE TO THE PROJECT
 SPECIFICATION BOOK WAS MADE IN THE NARRATIVE, HOWEVER
 WE DO NOT REVIEW SPEC BOOKS. PLEASE PROVIDE DETAILS ON
 THE PLANS.
 17) 1ST REVIEW COMMENT #35, SHEET M7.02: PLEASE PROVIDE
 THE CONTROLS OPERATION FOR THE DHU'S AND A SYMBOL
 LEGEND.
 18) SHEET M0.04: THE GAGE OF ALUMINUM DUCTWORK IS
 INDICATED TO BE 14 INCHES- PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-09 Cont ID  
Sent By ccole Date 2016-03-09 Time 17:37 Rev Time 0.00
Received By ccole Date 2016-03-08 Time 12:16 Sent To  
Notes
2016-03-09 17:41:061ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020418
 BALLPARK OF THE PALM BEACHES
 3/8/16
  
 1) THE DESIGN PROFESSIONALS OF RECORD MUST SIGN AND
 PROVIDE THEIR PROFESSIONAL REGISTRATION NUMBERS ON PAGE
 3 OF THE ENERGY CONSERVATION FORM SUBMITTAL- SEE
 SECTION C103.1.1.1.2 FBC-14 ENERGY CONSERVATION.
 2) DISCREPANCIES BETWEEN THE ENERGY FORM AND THE
 MECHANICAL PLANS:
 A) THE FORM LISTS ERU-A-2-5 CAPACITY AT 75300 BTUH ,
 THE AC SCHEDULE ON SHEET M0.02 LISTS THE CAPACITY AT
 92000 BTUH
 B) ENERGY FORM LISTS ERU-A-2-6 AT 75300, SCHEDULE-
 92,000.
 C) ENERGY FORM LISTS COMPLIANCE DATA FOR AHU-S-2-4 ,
 HOWEVER THIS SYSTEM IS NOT INCLUDED IN THE EQUIPMENT
 SCHEDULES ON THE PLANS.
 D) THE SPLIT SYSTEMS, THE 100% O/A SYSTEMS, THE DHU'S,
 THE COMPUTER ROOM AC, AND MANY OF THE VRF SYSTEMS ARE
 NOT LISTED IN THE ENERGY CONSERVATION FORM.
 3) THE AC COOLING AND HEATING CALCULATIONS MUST BE
 SIGNED AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD:
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 4) DISCREPANCIES BETWEEN THE AC CALCULATIONS AND THE
 MECHANICAL PLANS:
 A) CALCULATED COOLING LOAD FOR ACC-S-4 IS 391 MBH,
 HOWEVER THE SCHEDULE ON SHEET M0.04 INDICATES THE
 CAPACITY AT 528 MBH.
 B) AHU-A-2-1 COOLING LOAD- 925 MBH / SCHEDULE ON SHEET
 M0.02 INDICATES CAPACITY AT 836 MBH
 C) AHU-N-2-1 LOAD- 695 MBH/ SCHEDULE- 835 MBH.
 D) AHU-N-2-2 LOAD- 786 MBH/ SCHEDULE- 732 MBH.
 E) AHU- S-3-1 LOAD- 121.9 MBH/SCHEDULE- 197 MBH.
 F) AHU-S-3-2 LOAD- 52.8 MBH/ SCHEDULE- 87 MBH.
 G) AHU-S-3-4 LOAD- 58 MBH/ SCHEDULE-83.
 H) AHU-S-2-4 IS SHOWN IN THE CALCS BUT NOT IN THE
 SCHEDULES.
 I) AHU-S-3-5 IS SHOWN IN THE SCHEDULE BUT NOT IN THE
 CALCS.
 J) DHU-N-2-1 LOAD- 81.3 MBH/SCHEDULE- 133 MBH.
 K) ERU-A-2-5 LOAD- 245.7 MBH/ SCHEDULE- 92 MBH
 L) ERU-A-3-1 LOAD- 131.8 MBH/ SCHEDULE- 92 MBH.
 M) ERU-N-2-5 LOAD- 180 MBH/ SCHEDULE- 112.5 MBH.
 N) ERU-N-2-6 LOAD- 286.6 MBH/ SCHEDULE- 92 MBH.
 O) CLARIFY WHICH SYSTEMS WERE SIZED UNDER THE LOAD
 CALCULATIONS PAGES TITLED "MISC" AND "SYSTEM 023": I
 CANNOT CONNECT THESE UP WITH THE AC SCHEDULES.
 IN REFERENCE TO THE DISCREPANCIES ABOVE PLEASE REFER TO
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 2) SHEETS M0.03: INDICATE HOW EACH EXHAUST FAN IN THE
 SCHEDULE WAS SIZED: PROVIDE EXHAUST VENTILATION
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC-14
 MECHANICAL, AND TABLE 6-4 ASHRAE 62.1-2010.
 3) M0.04: REFER TO TABLE C403.2.3(10) FBC ENERGY
 CONSERVATION AND PROVIDE THE SCOP RATING FOR THE
 COMPUTER ROOM AC UNITS.
 4) M2.03 & M2.04: THE PLANS APPEAR TO INDICATE
 MECHANICAL SYSTEMS ON THE SUITE AND ROOF LEVELS OF
 SECTOR A, HOWEVER THERE ARE NO ENLARGED PLANS FOR THOSE
 AREAS IN THE SETS AND THERE ARE ROOF TOP UNITS ON THE
 CONCOURSE LEVEL OF SECTOR A- PLEASE CLARIFY.
 5) DUCT SMOKE DETECTORS ARE REQUIRED IN RETURN AIR
 SYSTEMS WITH DESIGN CAPACITIES GREATER THAN 2000 CFM
 PER SECTION 606.2.1 FBC-14 MECHANICAL. MANY OF THE
 PROPOSED AC SYSTEMS FOR THE PROJECT HAVE RETURN AIR
 SYSTEMS EXCEEDING THAT THRESHOLD. PLEASE PROVIDE DS
 DETECTOR SYMBOLS ON THE PLANS WHERE APPLICABLE, AND
 PROVIDE NOTES AND DETAILS CLARIFYING THE SEQUENCE OF
 OPERATION FOR THE DETECTORS AND HOW THEY WILL BE
 SUPERVISED- SECTION 606.4.1. PLEASE INCLUDE AN
 INSTALLATION DETAIL FOR THE DEVICES AND A PRODUCT
 SUBMITTAL APPROVED BY THE ENGINEER OF RECORD.
 6) M2.110 AND ALL MECH. PLAN SHEETS: NUMEROUS SYMBOLS
 FOR ACCESS PANELS ARE SHOWN FOR THE ABOVE CEILING CAV'S
 AND VAV'S. REFER TO SECTION 306.1 AND PROVIDE THE
 DIMENSION AND CONSTRUCTION DETAILS FOR THE PANELS.
 PLEASE NOTE THE PANELS SHALL BE LARGE ENOUGH TO REMOVE
 AND REPLACE THE EQUIPMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION.
 7) M2.111: PROVIDE A KEY NOTE IDENTIFYING WHICH AC
 SYSTEM IS PROVIDING THE 20X16 SUPPLY AND RETURN DUCT
 DROPS.
 8) M2.111: PROVIDE KEY NOTES IDENTIFYING WHICH EXHAUST
 FANS ARE SERVICING THE EXHAUST DUCT RISERS SHOWN IN THE
 AREA OF THE CHEMICAL AND PAINT STORAGE ROOMS.
 9) M2.111: CHEMICAL AND PAINT STORAGE ROOMS: A) REFER
 TO SECTION 414.1.3 FBC-14 BUILDING: [F] 414.1.3
 INFORMATION REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
 B) PROVIDE ON THE PLAN AN ITEMIZED LIST OF THE
 HAZARDOUS MATERIALS TO BE STORED AND THEIR EXPECTED
 QUANTITIES, AND SUBMIT MSDS SHEETS FOR EACH ITEM. C)
 PROVIDE EXHAUST VENTILATION CALCULATIONS FOR EACH
 EXHAUST SYSTEM, INDICATE THE TYPE OF EXHAUST DUCTWORK
 TO BE INSTALLED, AND SEQUENCE OF OPERATION FOR THE
 FANS- SEE SECTIONS 502.8.1.1 & 510.1- 510.9. PLEASE
 NOTE THAT FIRE SUPPRESSION MAY BE REQUIRED FOR THE
 EXHAUST DUCTS. D) REFER TO SECTION 510.5.5 AND INDICATE
 HOW MAKE-UP AIR IS BEING PROVIDED FOR THE SYSTEMS AND
 THE RATE. PLEASE NOTE THAT THE SOURCE OF THE MAKE-UP
 AIR MUST BE DIRECTLY FROM THE OUTDOORS AND TRANSFER
 DUCTS FROM ADJOINING ROOMS CANNOT BE USED.
 10) M2.111: FIRE DAMPERS ARE REQUIRED FOR THE 12X12
 LOCKER AND RESTROOM EXHAUST DUCT PENETRATING THE
 FIRE-RATED PAINT STORAGE WALLS IN ACCORDANCE WITH
 SECTION 607.5.2 FBC-14 MECHANICAL.
 11) M2.111: PROVIDE THROUGH-PENETRATION FIRESTOPPING
 SYSTEM DETAILS FOR DUCTS PENETRATING FIRE-RATED WALLS-
 SEE SECTION 714.1.1 FBC-14 BUILDING.
 12) M2.111: INDICATE THE REQUIRED CLEARANCES FOR THE
 EXHAUST OUTLETS FROM EF S-1-1 AND EF S-1-2: REFER TO
 SECTION 501.3.1 FBC-14 MECHANICAL. IDENTIFY THE ROOMS
 IN THE MAINTENANCE MEZZANINE AND INDICATE A SOURCE OF
 MAKE-UP AIR FOR THE EXHAUST SYSTEMS.
 13) M2.111: PLEASE NOTE THAT ALL EXTERIOR EXHAUST
 OUTLET AND AIR INTAKE OPENINGS SHOWN ON THIS PLAN SHEET
 AND ALL OTHERS MUST BE PROTECTED IN ACCORDANCE WITH
 SECTIONS 1609.1.2 AND 1609.6.4.4.1 FBC-14 BUILDING.
 MIAMI-DADE NOA'S AND/OR FLORIDA PRODUCT APPROVALS SHALL
 BE SUBMITTED FOR ALL COMPONENTS AND CLADDINGS WITH
 REVIEW AND APPROVAL SIGNATURES FROM THE DESIGN
 PROFESSIONALS OF RECORD.
  
 14) M2.112, LAUNDRY: A) PROVIDE AN EQUIPMENT SCHEDULE
 ON THE PLAN FOR THE DRYERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD. B) A COMBUSTION AIR INTAKE DUCT
 IS INDICATED- PROVIDE COMBUSTION AIR CALCULATIONS FOR
 SIZING THE DUCT. C) EXPAND NUMBERED NOTE #5 TO INDICATE
 THE TYPE AND GAGE OF DUCT MATERIAL, THE INTAKE HOOD THE
 DUCT IS CONNECTED TO, AND HOW THE DUCT WILL BE
 SUPPORTED. D) EXPAND NUMBERED NOTE #1 TO INDICATE
 COMPLIANCE WITH SECTION 504.7: COMMERCIAL CLOTHES
 DRYERS.
 THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING
 COMMERCIAL CLOTHES DRYERS SHALL COMPLY WITH THE
 APPLIANCE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 EXHAUST FAN MOTORS INSTALLED IN EXHAUST SYSTEMS SHALL
 BE LOCATED OUTSIDE OF THE AIRSTREAM. IN MULTIPLE
 INSTALLATIONS, THE FAN SHALL OPERATE CONTINUOUSLY OR BE
 INTERLOCKED TO OPERATE WHEN ANY INDIVIDUAL UNIT IS
 OPERATING. DUCTS SHALL HAVE A MINIMUM CLEARANCE OF 6
 INCHES (152 MM) TO COMBUSTIBLE MATERIALS. CLOTHES DRYER
 TRANSITION DUCTS USED TO CONNECT THE APPLIANCE TO THE
 EXHAUST DUCT SYSTEM SHALL BE LIMITED TO SINGLE LENGTHS
 NOT TO EXCEED 8 FEET (2438 MM) IN LENGTH AND SHALL BE
 LISTED AND LABELED FOR THE APPLICATION. TRANSITION
 DUCTS SHALL NOT BE CONCEALED WITHIN CONSTRUCTION. E)
 SEE TABLE 403.3 AND PROVIDE OUTSIDE AIR CALCULATIONS
 FOR THE LAUNDRY AREA. F) SUBMIT SPECS FOR THE ENERVEX
 MEC 18 EXHAUST CONTROL SYSTEM REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
 15) M2.112: PROVIDE NUMBERED KEY NOTES AT THE MAIN
 SUPPLY AND RETURN DUCT DROPS TO IDENTIFY WHICH AC AND
 ERU SYSTEMS ARE SERVICING THE AREAS.
 16) M2.112: THE KITCHEN HOOD EXHAUST AND FIRE
 SUPPRESSION SYSTEMS SHALL BE DONE UNDER A SEPARATE
 PERMIT- PLEASE PLACE A NOTE ON THE PLAN ACCORDINGLY AND
 PROVIDE AN AIR BALANCE CALCULATION FOR THE AREA. PLEASE
 NOTE ALL OTHER KITCHEN HOOD EXHAUST AND FIRE
 SUPPRESSION SYSTEMS THROUGHOUT THE FACILITY WILL ALSO
 BE DONE UNDER SEPARATE PERMIT WITH AIR BALANCE CALCS
 REQUIRED FOR EACH.
 17) M2.112: I AM NOT SEEING ANY OUTSIDE AIR
 CALCULATIONS IN THE SCHEDULES FOR THE CORRIDOR
 SERVICING THIS SECTOR OR CALCULATIONS FOR ANY OF THE
 OTHER SECTOR CORRIDORS- REFER TO TABLE 403.3 AND
 PROVIDE THE CALCULATIONS. IT ALSO NEEDS TO BE VERIFIED
 THAT THE CORRIDORS IN ALL SECTORS ARE NOT SERVING AS
 SUPPLY, RETURN, EXHAUST, RELIEF, OR VENTILATION AIR
 DUCTS PER SECTION 601.2. AS NOTED IN SECTION 601.2.1,
 THE CEILINGS ABOVE THE CORRIDORS MAY SERVE AS RETURN
 AIR PLENUMS.
 18) M2.113: EXPAND NUMBERED NOTE #11 TO INDICATE WHICH
 AC SYSTEM
 19) M2.113: PLACE A NUMBERED NOTE ON THE PLAN TO
 INDICATE WHERE THE HVAC SYSTEMS FOR THE HYDRO ROOM CAN
 BE FOUND.
 20) INDICATE THE REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS FOR THE EXHAUST OUTLET FOR EF N-1-3. REFER
 TO COMMENT #12 ABOVE FOR MORE INFO.
 21) M2.113: REFER TO COMMENTS # 13 AND 15 FOR THE
 LAUNDRY AND KITCHEN AREAS ON THIS PLAN SHEET.
 22) M2.114: PROVIDE AN EXHAUST SYSTEM AND CALCULATIONS
 FOR THE STAFF/COACHES LOCKER ROOM- SEE TABLE 403.3.
 23) M2.115 & M2.412: THE 8" ROUND UNDERGROUND EXHAUST
 DUCT FROM THE DUGOUT SHALL BE CONSTRUCTED OF PVC HAVING
 A MINIMUM PIPE STIFFNESS OF 8 PSI AT 5-PERCENT
 DEFLECTION WHEN TESTED IN ACCORDANCE WITH ASTM D2412.
 PROVIDE A SUBMITTAL FOR THE DUCT REVIEWED AND APPROVED
 BY THE DESIGN PROFESSIONAL OF RECORD.
 24) M2.115: PROVIDE A NUMBERED KEY NOTE IDENTIFYING
 WHICH AC SYSTEM THE 24X14 SUPPLY AND 26X20 RETURN DUCT
 DROPS ARE CONNECTED TO.
  
 25) SHEETS M2.117, 118, & 119- CLUBHOUSE SECTORS H, J,
 & K: MANY OF THE COMMENTS PRINTED ABOVE FOR SHEETS
 M2.111, 112, 113, 114, & 115 (NATIONAL'S CLUBHOUSE) CAN
 APPLIED TO THESE PLAN SHEETS AND SECTORS FOR THE ASTROS
 CLUBHOUSE INCLUDING: A) REQUIRED EXHAUST SYSTEM AND
 CALCULATIONS FOR THE MLB COACHES LOCKER ROOM (M2.117).
 B) LAUNDRY AND KITCHEN AREAS. C) AC SYSTEM
 IDENTIFICATIONS AT DUCT DROPS. D) EXHAUST OUTLET AND
 AIR INLET CLEARANCE DISTANCES. E) NOA?S AND PRODUCT
 APPROVALS. F) OUTSIDE AIR FOR CORRIDORS.
 26) M2.120: EXPAND GENERAL NOTE A TO INDICATE THE GAGE
 OF ALUMINUM DUCTWORK.
 27) M2.120, 121, 122, 123, 127, 128, 129, 132, 134,
 135, 136, 137, 138, 139, 145: WIND LOAD ENGINEERING IS
 REQUIRED FOR THE ROOF-MOUNTED ERU'S, AHU'S, ACC'S CU'S,
 EF'S, MUA'S, DUH'S, GIH'S, AND ALL OTHER ROOF MOUNTED
 EQUIPMENT, COMPONENTS, AND DUCTWORK- SECTION 301.15
 PROVIDE STRUCTURAL DETAILS ACCORDINGLY INCLUDING
 SECTION CUTS INDICATING CURB HEIGHTS ABOVE THE ROOF
 SURFACES, CURB TO STRUCTURE AND UNIT TO CURB
 ATTACHMENTS, STAND TO STRUCTURE AND UNIT TO STAND
 ATTACHMENTS ETC. IF THE DETAILS ARE FOUND ON
 ARCHITECTURAL OR STRUCTURAL SHEETS PLEASE PLACE NOTES
 ON THE PLAN INDICATING THE SHEET AND DETAIL NUMBERS.
 28) M2.125: A) PROVIDE EXHAUST OUTLET CLEARANCE
 DISTANCES FOR EF-S-2-5 AND PROTECTION FOR THE OPENING.
 B) IDENTIFY WITH A NUMBERED NOTE WHICH AC SYSTEM IS
 PROVIDING THE O/A DROP. C) SEPARATE PERMITS REQUIRED
 FOR THE KITCHEN HOOD GREASE EXHAUST AND FIRE
 SUPPRESSION SYSTEMS D) IDENTIFY WITH A NOTE WHICH AC
 SYSTEM IS PROVIDING THE 28X20 SA AND RA DROPS. E)
 NUMBERED NOTE #5 INDICATES CONDENSATE FROM AC S-2-1 &
 S-2-4 DISCHARGING INTO A PLUMBING DRAIN- PLEASE NOTE
 THAT THIS CONDENSATE AND ALL OTHER CONDENSATE FROM AC
 COOLING COILS IS PROHIBITED TO DRAIN INTO THE WPB
 SANITY SEWER SYSTEM PER SEC. 90-126 WPB CODE OF
 ORDINANCES.
 29) M2.126: IDENTIFY WITH A NOTE WHICH AC SYSTEM IS
 PROVIDING THE 20X12 AND 18X12 SA AND RA DROPS.
 30) M2.129: I AM NOT SEEING MAU S-3-6 IN THE EQUIPMENT
 SCHEDULES- PLEASE INDICATE WHERE IT IS LOCATED. PLEASE
 NOTE THAT THE VENTILATION CALCULATION AND EQUIPMENT
 SCHEDULES DO NOT LIST THIS UNIT. MAU-N-2-6 & MAU-N-2-7
 ARE LISTED IN THE VENTILATION SCHEDULES HOWEVER I CAN?T
 FIND THEM ON THE PLANS ON IN THE EQUIPMENT SCHEDULES-
 PLEASE CLARIFY AND INDICATE HOW THESE SYSTEMS WERE
 SIZED.
 31) M2.132, 134, 135 & M0.07: THE VENTILATION
 CALCULATIONS ARE INCORRECT FOR THE SUITES AND OTHER
 SPECTATOR AREAS ON THE SUITE LEVEL. REFER TO TABLE
 403.3 FBC-14 MECHANICAL: SPECTATOR AREAS ARE CALCULATED
 AT 150 PEOPLE PER 1000 SQ.FT. AND REQUIRE 7.5 CFM PER
 PERSON- PLEASE CORRECT. A) PROVIDE ACCESS PANEL SYMBOLS
 FOR THE FCU?S AND DIMENSIONED DETAILS FOR INSTALLATION
 OF THE PANELS.
 32) M4.01, 402: EXPAND NOTE #3 TO INDICATE WHICH AC
 SYSTEM IS PROVIDING THE SA AND RA DROPS TO THE AREAS.
 33) M4.02: PROVIDE AN EQUIPMENT SCHEDULE FOR THE SF
 N-1-4, AND DETAILS FOR WIND LOAD ENGINEERING FOR
 ANCHORING THE FAN AND DUCTWORK- SECTION 301.15.
 34) M4.02 & 403.: THE REFRIGERANT PIPING DIAGRAMS ARE
 INCOMPLETE: PROVIDE DIAGRAMS FOR ALL SYSTEMS AND
 INCLUDE PIPE AND PIPE INSULATION SPECIFICATIONS, AND
 FIRESTOPPING DETAILS FOR ALL PIPES PENETRATING
 FIRE-RATED WALLS OR FLOOR/CEILING ASSEMBLIES
 34) M.602 & 603: PROVIDE SUPPORT AND HANGING DETAILS
 FOR INSTALLATION OF THE FCU?S, THE VAV AND CAV BOXES,
 THE INLINE FANS, THE G90 AND ALUMINUM DUCTWORK, AND THE
 FLEX DUCTS. INCLUDE CONNECTION AND REINFORCEMENT
 DETAILS FOR ALL DUCTWORK, AND TYPES AND SIZES OF
 HANGERS AND FASTENERS- REFER TO TABLE C403.2.7.2 FBC-14
 ENERGY CONSERVATION AND SMACNA HVAC DUCT CONSTRUCTION
 STANDARDS-2005.
  
 35) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION: PROVIDE SHUTOFF DAMPER CONTROLS FOR
 OUTDOOR AIR SUPPLY AND EXHAUST DUCTS WHERE REQUIRED.
 36) REFER TO SECTION C408: COMMISSIONING OF THE
 MECHANICAL AND ELECTRICAL POWER AND LIGHTING SYSTEMS IS
 REQUIRED. PLEASE REVIEW ALL SUB-SECTIONS UNDER C408 AND
 SUBMIT A COMMISSIONING PLAN FOR REVIEW.
 37) PROVIDE A SUBMITTAL PACKAGE FOR ALL MECHANICAL
 EQUIPMENT AND COMPONENTS INCLUDING BUT NOT LIMITED TO
 THE AC SYSTEMS, EXHAUST AND SUPPLY FANS, ROOF TOP CURBS
 AND STANDS, EXHAUST OUTLET AND AIR INLET LOUVERS, DUCT
 SMOKE DETECTORS, FIRE DAMPERS, THE DRYERS, ETC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-06-16 Cont ID  
Sent By tklarge Date 2016-06-16 Time 08:44 Rev Time 0.00
Received By tklarge Date 2016-06-16 Time 08:43 Sent To  
Notes
2016-06-16 08:44:52PROVISO
  
 PLANS SHALL BE SUBMITTED FOR THE OZONE GENERATING
 EQUIPMENT PRIOR TO THE INSTALLATION OF THE EQUIPMENT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-05-12 Cont ID  
Sent By tklarge Date 2016-05-12 Time 09:54 Rev Time 0.00
Received By tklarge Date 2016-05-12 Time 03:45 Sent To  
Notes
2016-05-12 09:55:17THESE PROVISO NOTES ARE ALSO ON THE PLANS.
 **** NOTE**** THE FOLLOWING COMMENTS ARE PROVISOS FOR
 THE PLUMBING PLAN REVIEW ONLY.
 1) THE GAS PERMIT AND PLAN REVIEW WILL BE DONE AS A
 SEPARATE PERMIT AND IS NOT PART OF THIS SUBMITTAL
 PACKAGE.
 2) SHT.IR1.07 - THE ACID INJECTION SYSTEM FOR THE
 IRRIGATION SYSTEM SHALL BE UNDER A SEPARATE PERMIT.
 COMPLETE PLANS AND SPECIFICATIONS SHALL BE SUBMITTED
 FOR REVIEW.
 3) THE LAUNDRY AREAS IN THE CLUBHOUSES SHALL COMPLY
 WITH THE 2014 FBC- ACCESSIBILITY SECS. 611 & 309. ALL
 WASHERS AND DRYERS SHALL COMPLY WITH THE REQUIREMENTS
 FOR CLEAR FLOOR SPACE, OPERABLE PARTS, AND HEIGHT.
 4) SHT.P4.003 - APPROVAL IS REQUIRED FROM THE PALM
 BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL RESOURCE
 MANAGEMENT FOR THE ABOVE GROUND FUEL STORAGE TANKS AND
 DISPENSING SYSTEM PER PALM BEACH COUNTY ORDINANCE
 #2015-008. THE FUEL TANKS AND FUEL DISPENSING SYSTEM
 SHALL BE DONE AS A SEPARATE PERMIT.
 5) THE SANITARY AND WATER RISERS ARE INCOMPLETE AND
 DEFICIENT AND A THOROUGH AND COMPREHENSIVE REVIEW COULD
 NOT BE DONE AT THIS TIME. AS-BUILT SANITARY AND WATER
 RISERS SHALL BE SUBMITTED DURING THE INSPECTION PROCESS
 FOR THESE SYSTEMS.
 6) SHT. A3.23 - ACCESSIBLE ROLL-IN SHOWER WITH GRAB BAR
 AND SEAT DETAIL SH - 3. ALTERNATE ROLL-IN SHOWER
 COMPARTMENTS SHALL COMPLY WITH 2014 FBC-ACCESSIBILITY
 SEC. 608.2.3 FOR ENTRY OPENING AND LAYOUT, SEC.608.3
 FOR THE LOCATION OF GRAB BARS, SEC. 608.5.3 FOR THE
 LOCATION OF CONTROLS, FAUCETS AND SHOWER SPRAY UNITS,
 AND SEC.610.3 FOR SEATS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-28 Cont ID  
Sent By tklarge Date 2016-04-28 Time 15:09 Rev Time 0.00
Received By tklarge Date 2016-04-18 Time 09:35 Sent To  
Notes
2016-04-27 06:02:241) ) SHT. A3.23 - ACCESSIBLE ROLL-IN SHOWER WITH GRAB
 BAR AND SEAT DETAIL SH 3 - THIS IS CONSIDERED AS AN
 ALTERNATE ROLL-IN SHOWER DUE TO THE SIZE (36 X 60
 INCHES). THE LOCATION OF THE SHOWER SEAT SHALL COMPLY
 WITH THE 2014 FBC-ACCESSIBILITY SEC.610.3 AND THE
 LOCATION OF THE SHOWER CONTROLS SHALL COMPLY
 FBC-ACCESSIBILITY SEC.608.5.3.PROVIDE DETAILS THAT SHOW
 COMPLIANCE.
 2) DEFINE THE OCCUPANCY FOR THIS STRUCTURE. THE AMOUNT
 OF COMBUSTIBLE/FLAMMABLE LIQUID STORAGE APPEARS TO
 DEFINE THIS STRUCTURE AS AN "H" OCCUPANCY PER CHAPT.
 307.4, 307.5 & CHAPT. 4 OF THE 2014 FBC. PLEASE SUBMIT
 A COPY OF THE LETTER FROM HOWE ENGINEERS DATED MARCH23,
 2016 PROVIDED IN A RESPONSE COMMENT TO WESLEY JOLIN
 WHICH INDICATES THAT THE QUANTITIES OF THE VARIOUS
 MATERIALS STORED DO NOT REQUIRE THE BUILDING TO BE
 CONSIDERED AN "H" OCCUPANCY. I COULD NOT FIND THIS
 LETTER IN THE SUPPRTING DOCUMENT FOLDER. SEE RESPONSE
 TO PLUMBING PLAN REVIEW COMMENTS FROM HKS DATED APRIL
 14, 2016.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
 **** NOTE**** THE FOLLOWING COMMENTS ARE PROVISOS FOR
 THE PLUMBING PLAN REVIEW ONLY. THE GAS PLAN REVIEW WILL
 BE LISTED AS A SEPARATE REVIEW. THE PROVISOS SHALL BE
 SATISFIED BY THE SUBMITTAL OF THE REQUIRED INFORMATION
 PRIOR TO ANY PLUMBING INSPECTIONS BEING PERFORMED AT
 THESE AREAS. TIM LARGE, CHIEF PLUMBING INSPECTOR.
 3) SHT.IR 1.07 - SUBMIT COMPLETE DETAILS FOR THE ACID
 INJECTION SYSTEM FOR THE IRRIGATION SYSTEM, CONTAINMENT
 SYSTEM, PUMPS,VALVES,PIPING, ETC. SHOW HOW THIS AREA
 WILL BE PROTECTED AGAINST UNAUTHORIZED ENTRY. 2014 FBC
 SEC.107.2.1.
 4) SUBMIT MSDS DATA FOR THE CHEMICALS TO BE USED FOR
 THE ACID INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.
 2014 FBC SEC.107.2.1.
 5) THE LAUNDRY AREAS IN THE CLUBHOUSES SHALL COMPLY
 WITH THE 2014 FBC- ACCESSIBILITY SECS .611 & 309. ALL
 WASHERS AND DRYERS SHALL COMPLY WITH THE REQUIREMENTS
 FOR CLEAR FLOOR SPACE, OPERABLE PARTS, AND HEIGHT.
 6) SHT.P4.003 - APPROVAL IS REQUIRED FROM THE PALM
 BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL RESOURCE
 PROTECTION FOR THE ABOVE GROUND FUEL STORAGE TANKS PER
 PALM BEACH COUNTY ORDINANCE #2015-008.
 7) THE SANITARY AND WATER RISERS ARE INCOMPLETE AND
 DEFICIENT AND A THOROUGH AND COMPREHENSIVE REVIEW COULD
 NOT BE DONE AT THIS TIME. AS-BUILT SANITARY AND WATER
 RISERS SHALL BE SUBMITTED DURING THE INSPECTION PROCESS
 FOR THESE SYSTEMS.
 8) MANUFACTURER'S SPECIFICATIONS FOR THE FUEL
 DISPENSERS, TANKS, VALVES, ETC. SHALL BE SUBMITTED FOR
 REVIEW. 2014 FBC SEC.107.2.1.
 9) THE FUEL TANKS, DISPENSERS AND ALL ASSOCIATED PIPING
 SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 30, 2012
 EDITION AS ADOPTED BY THE 2014 FBC.
 10) SUBMIT A CONDENSATE RISER FOR REVIEW. THE
 CONDENSATE SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM
 OR THE GREASY WASTE SYSTEM PER THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES AND 2014 FBC SEC.1003.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By tklarge Date 2016-03-10 Time 10:51 Rev Time 0.00
Received By tklarge Date 2016-02-27 Time 10:20 Sent To  
Notes
2016-03-08 08:59:021) SHT.C9.21 - GREASE/WATER SEPARATOR DETAIL - THE CITY
 DETAIL ON THE PLAN IS AN OUTDATED DETAIL. REFER TO
 DETAIL GS 7 ISSUED IN 2015.
 2) SHT. IR1.07 - SUBMIT COMPLETE DETAILS FOR THE ACID
 INJECTION SYSTEM FOR THE IRRIGATION SYSTEM, CONTAINMENT
 SYSTEM, PUMPS, VALVES, PIPING, ETC. FBC 107.2.1. SHOW
 HOW THIS AREA WILL BE PROTECTED AGAINST UNAUTHORIZED
 ENTRY.
 3) SUBMIT MSDS DATA FOR THE CHEMICALS USED FOR THE ACID
 INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.FBC 107.2.1.
 4) SHT. A1.22 - DETAIL #2 - THE GUTTERS FOR THE BATTING
 TUNNEL ROOF SHALL BE SIZED IN ACCORDANCE WITH TABLE
 1106.6 OF THE 2014 FL. PLUMBING CODE. CLEARLY THE
 LOCATION OF ALL GUTTERS ON THE PLAN.
 5) THE ROOM FINISH PLAN ON SHT. A3.40 SHOWS THE WALLS
 IN SOME OF THE RESTROOMS AND TOILET ROOMS AS PAINT.
 2014 FBC SEC. 1210.2.2 REQUIRES WALLS AND PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER
 CLOSETS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO
 A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR.EXCEPTION:TOILET ROOMS THAT ARE NOT ACCESSIBLE TO
 THE PUBLIC AND WHICH HAVE NOT MORE THAN ONE WATER
 CLOSET.
 6) SINKS LOCATED IN BREAK ROOM AREAS SHALL COMPLY WITH
 THE 2014 FAC SEC.212 & 606.
 7) THE LAUNDRY AREAS SHALL COMPLY WITH THE 2014 FAC
 SEC.611.
 8) SHT. A2.913 - DETAIL # 01 - THE WATER CLOSET SHALL
 BE LOCATED DIAGONALLY OF THE COMPARTMENT DOOR PER 2014
 FAC SEC.604.8.1.2.
 9) SHT. A2.914 - DETAILS # 3 & #4 - THE DOOR SHALL BE
 LOCATED PER FAC SEC.604.8.1.2.
 10) SHT.A3.23 - DETAIL EWC 3 - THE SPOUT ON THE HIGH
 SIDE DRINKING FOUNTAIN SHALL BE LOCATED 38-43 INCHES
 ABOVE THE FINISH FLOOR OR GROUND PER THE FAC SEC.602.7.
 11) SHT.A#.23 - ACCESSIBLE ROLL IN SHOWER WITH GRAB BAR
 AND SEAT - THIS IS CONSIDERED AN ALTERNATE ROLL- IN
 TYPE SHOWER DUE TO THE SIZE (36" X 60") AND THE
 LOCATION OF THE SHOWER SEAT SHALL COMPLY WITH THE 2014
 FAC SEC.610.3 AND THE LOCATION OF THE CONTROLS SHALL
 COMPLY WITH SEC.608.5.3.
 12) SHT. A3.23 - ACCESSIBLE SHOWER TRANSFER - THE
 CONTROLS SHALL BE A MINIMUM OF 38 INCHES AND A MAXIMUM
 OF 48 INCHES ABOVE THE SHOWER FLOOR AND SHALL BE
 LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. FAC
 SEC.608.5.1.
 13) TOILET PAPER DISPENSERS IN THE ACCESSIBLE TOILET
 ROOMS/COMPARTMENTS SHALL BE LOCATED A MINIMUM OF 7
 INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. FAC
 SEC.604.7.
 14) SHT. A8.21 - ALL NEWLY INSTALLED UNDERGROUND
 HYDRAULIC PRESSURE CYLINDERS SHALL BE ENCASED IN OUTER
 PLASTIC CONTAINMENT TO MINIMIZE ELECTROLYTIC CORROSION
 BETWEEN THE METAL CYLINDER AND GROUND CATHODE. 2014 FBC
 SEC.3011.1.
 15) SHT. P0.03 - THE PLUMBING FIXTURE SCHEDULE SHOWS
 LAVATORY FAUCETS 2B & 2C WITH COLD WATER ONLY. HOT OR
 TEMPERED SHALL BE SUPPLIED TO THE LAVATORIES PER FPC
 SEC.607.1.THE WATER RISERS SHALL CLEARLY SHOW
 HOT/TEMPERED WATER TO THE REQUIRED FIXTURES.
 16) SHT. P2.001, 002 & 003 - THE OVERALL PLANS ARE
 PEPPERED WITH DARK MARKS AND ARE IMPOSSIBLE TO SEE WHAT
 THEY REPRESENT. CLARIFY.
 17) SHT. P2.114 - THERE IS A GREASY WASTE LINE THAT
 APPEARS TO BE ALSO LABELED AS A SANITARY LINE.SEE AREA
 BETWEEN GRID LINES S17 & S18 AND SG & SH. PLEASE CHECK
 ALL SHEETS TO ENSURE THE DRAINAGE LINES ARE PROPERLY
 LABELED.
 18) SHT.P4.003 - APPROVAL IS REQUIRED FROM THE PALM
 BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCE PROTECTION
 FOR THE ABOVE GROUND FUEL STORAGE TANKS. PBC ORD. #
 2015 - 008.
 19) SHT. P4.003 - THE FUELING SCHEMATIC REFERS TO
 SEVERAL DETAILS ( A,B,C, ETC.) WHERE ARE THESE DETAILS?
 CLARIFY.
 20) SHT.P4.003 - NUMBERED NOTE #1 REFERS TO A ONE
 THOUSAND GALLON DIVIDED FUEL TANK BUT THE FUELING
 SYSTEM SCHEMATIC SHOWS A DIVIDED 2500 GALLON TANK.
 CLARIFY.
 21) THE SANITARY AND WATER RISERS ARE INCOMPLETE AND
 DEFICIENT AND A THOROUGH AND COMPREHENSIVE REVIEW COULD
 NOT BE DONE AT THIS TIME. AS-BUILT SANITARY AND WATER
 RISERS WILL BE SUBMITTED DURING THE INSPECTION PROCESS.
 22) PLACE THE ROOM NUMBERS ON THE ENLARGED PLANS. IT IS
 DIFFICULT TO LOCATE THESE AREAS ON THE PLAN VIEW
 LAYOUT. FBC 107.2.1.
 23) SAMPLING PORTS ARE REQUIRED ON THE DISCHARGE SIDE
 OF EACH GREASE INTERCEPTOR PER THE CWPB STANDARD
 DRAWING GS-7.1.
 24) SUBMIT MANUF. SPECIFICATIONS FOR THE RETROCEPTOR
 SHOWN IN THE STADIUM SUITE LEVEL PARTY DECK.
 25) SHT. S5.101.5 - THERE ARE NUMBERED NOTE TAGS ON THE
 RISER DIAGRAM BUT THERE ARE NO NUMBERED NOTES ON THE
 DRAWING. CLARIFY.
 26) SHT.P5.401 - THE SHEET DRAWING NUMBERS THAT SHOW
 THE CONTINUATION OF THE FUEL GAS SYSTEM ARE ILLEGIBLE .
 SUBMIT A PLAN THAT CLEARLY SHOWS THE SHEET DRAWING
 NUMBERS. FBC 107.2.1.
 27) CLEARLY SHOW THE LOCATION OF ALL MEDIUM PRESSURE
 GAS REGULATORS ON THE GAS RISERS. FBC 107.2.1.
 28) CLEARLY SHOW THE PIPE SIZES OF THE PIPING
 DOWNSTREAM OF THE MP REGULATOR.FBC 107.2.1.
 29) SIZE ALL SECTIONS OF THE PIPING ON ALL GAS
 RISERS.FBC 107.2.1.
 30) IDENTIFY THE GAS METER ON THE GAS RISER ON
 SHT.P5.401.
 31) IDENTIFY EACH PIECE OF GAS EQUIPMENT ON THE GAS
 RISER AND THE BTU LOAD FOR EACH PICE OF
 EQUIPMENT/APPLIANCE.FBC 107.2.1.
 31) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1.
 32) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505.
 33) ALL EQUIPMENT SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH 2014 FGC SEC.301.3.
 34) SHT. P5.401 - MEP EQUIPMENT SCHEDULE SHOWS THE
 GWH-2 AS 1950 MBH BUT SHEET P5.401.1 APPEARS TO SHOW
 GWH-2 WITH LESS BTU'S. CLARIFY.
 35) SHT. P5.401.3 - SUBMIT AN EXPANDED GAS RISER
 DIAGRAM FOR THE WATER HEATERS AND SHOW THE REGULATOR.
 IT IS IMPOSSIBLE TO SEE WHERE THE MEDIUM PRESSURE AND
 LOW PRESSURE PIPING BEGINS AND ENDS.
 36) THE FOLLOWING COMMENTS ARE ALL FOR SHT. P5.402 -
 THE 2" MEP LINE IS UNDERSIZED.TABLE 402.4 (5) LIMITS A
 2' LINE TO 2010MBH.THE DRAWING SHOWS A BTU LOAD FROM
 2010 MBH UP TO 3030 MBH.
 37) THE 1 1/4 " LINE WITH 700MBH IS UNDERSIZED.MAXIMUM
 ALLOWED BY TABLE 402.4 (5) IS 695 MBH. THE LINE SHALL
 BE 1 1/2" MINIMUM.
 38) THE 1" MEDIUM PRESSURE LINE WITH 440 MBH IS
 UNDERSIZED. MAXIMUM IS 339MBH.THE LINE SHALL BE 1 1/4".
 39) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1640MBH
 NEEDS TO BE 2" PER TABLE 402.4 (5).
 40) THE 1 1/2" MEDIUM PRESSURE LINE CARRYING 1440 MBH
 NEEDS TO BE 2".
 41) THE 1"MP LINE CARRYING 440 MBH NEEDS TO BE 1 1/4".
 42) SHT. P5.402.1 - THE FOLLOWING COMMENTS ARE ALL
 APPLICABLE TO SHT.P5.402.1.
 43) THE 1 1/4" MP LINE CARRYING 700 MBH IS UNDERSIZED.
 IT NEEDS TO BE 1 1/2".
 44) THE 1" MP & LOW PRESSURE LINE CARRYING 440 MBH IS
 UNDERSIZED. BOTH LINES NEED TO BE 1 1/4".
 45) THE 3/4" MP LINE CARRYING 300 MBH IS UNDERSIZED. IT
 NEEDS TO BE 1". THE LOW PRESSURE SAID NEEDS TO BE 1
 1/4".
 46) THE 1 1/2" MP LINE CARRYING 1440 MBH IS UNDERSIZED.
 IT NEEDS TO BE 2". TABLE 402.4 (5).
 47) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED.
 IT NEEDS TO BE 2". TABLE 402.4 (5).
 48)SHT. P5.402.2. - THE FOLLOWING COMMENTS ARE ALL
 APPLICABLE TO SHT. P5.402.2. -
 49) THE 1 1/2" MP LINE CARRYING 1640MBH IS UNDERSIZED.
 IT NEEDS TO BE 2".
 50) THE 2" MP LINE CARRYING 2080MBH IS UNDERSIZED. IT
 NEEDS TO BE 2 1/2". TABLE 402.4 (5).
 51) THE 1" MP LINE CARRYING 440MBH IS UNDERSIZED. IT
 NEEDS TO BE 1 1/4".
 52) THE 2" MP LINE CARRYING 2130 IS UNDERSIZED. IT
 NEEDS TO BE 2 1/2".
 53) THE 1 1/4" LOW PRESSURE LINE CARRYING 700MBH IS
 UNDERSIZED. IT NEEDS TO BE 1 1/2".
 54) THE 2" MP LINE CARRYING 3030MBH IS UNDERSIZED.IT
 NEEDS TO BE 2 1/2".
 55) THE 3" MP LINE CARRYING 6930MBH IS UNDERSIZED. IT
 NEEDS TO BE 4".
 56) THE 2 1/2" MP LINE CARRYING 3900 IS UNDERSIZED. IT
 NEEDS TO BE 3".
 57) THE 2" LOW PRESSURE LINE CARRYING 1950MBH IS
 UNDERSIZED. IT NEEDS TO BE 2 1/2'.
 58) THE FOLLOWING COMMENTS ARE ALL APPLICABLE TO
 SHT.P5.403.
 59) PROVIDE THE TEXT FOR NUMBERED NOTE #1.
 60) THE 1" MP LINE CARRYING 500MBH IS UNDERSIZED. IT
 NEEDS TO BE 1 1/4".
 61) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED.
 IT NEEDS TO BE 2".
 62) THE 1 1/4"MP LINE CARRYING 700MBH IS UNDERSIZED. IT
 NEEDS TO BE 1 1/2".
 63) THE 2" MP LINE CARRYING 2020MBH, 2220MBH, AND 2320
 MBH IS UNDERSIZED. IT NEEDS TO BE 2 1/2".
 64) THE 3/4" MP LINE CARRYING 200MBH IS UNDERSIZED. IT
 NEEDS TO BE 1".
 65) THE 1 1/2" MP LINE CARRYING 1320MBH IS UNDERSIZED.
 IT NEEDS TO BE 2".
 66) THE 3" MP LINE CARRYING 6970 MBH IS UNDERSIZED. IT
 NEEDS TO BE 4".
 67) THE 2 1/2" MP LINE CARRYING 3900MBH IS UNDERSIZED.
 IT NEEDS TO BE 3".
 68) SHT.P5.403.1 - CHECK THE ENTIRE RISER FOR CORRECT
 SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND
 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD.
 69) SHT. P5.403.2 - CHECK THE ENTIRE RISER FOR CORRECT
 SIZING AND COMPLY WITH 2014 FGC TABLES 402.4 (1) AND
 402.4 (5). THE RISER IS UNDERSIZED FOR THE BTU LOAD.
 70) SHT.P4.003 - SUBMIT A LEGEND FOR ALL THE COMPONENT
 TAGS THAT ARE SHOWN ON THE PLAN. FBC 107.2.1.
 71) INDICATE THE LIQUID CLASS FOR THE GASOLINE ON THE
 PLANS IN ACCORDANCE WITH CHAPT.2 OF 2014 FBC.
 72) MANUFACTURER'S SPECIFICATIONS FOR DISPENSERS,
 TANKS, VALVES, ETC. SHALL BE SUBMITTED FOR REVIEW. THE
 DOCUMENTS CAN BE SUBMITTED NOW OR BE A DEFERRED
 SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.2.
 73) DEFINE THE OCCUPANCY FOR THIS STRUCTURE. THE AMOUNT
 OF COMBUSTIBLE/FLAMMABLE LIQUID STORAGE APPEARS TO
 DEFINE THIS STRUCTURE AS AN "H" OCCUPANCY PER CHAPT.
 307.4, 307.5 & CHAPT. 4 OF THE 2014 FBC.
 74) THE TANKS,DISPENSERS AND ALL ASSOCIATED PIPING AND
 CONSTRUCTION OF THE ENCLOSURE SHALL COMPLY WITH NFPA 30
 AND 2014 FBC.
 75) SUBMIT A CONDENSATE RISER FOR REVIEW. THE
 CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY PER CITY
 ORDINANCE OR TO THE GREASY WASTE SYSTEM. 2014 FBC SEC.
 1003.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-05-24 Cont ID  
Sent By skennedy Date 2016-05-24 Time 08:58 Rev Time 0.00
Received By skennedy Date 2016-05-24 Time 08:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-05-23 Cont ID  
Sent By ajones Date 2016-05-23 Time 17:07 Rev Time 0.00
Received By ajones Date 2016-05-23 Time 17:07 Sent To  
Notes
2016-05-23 17:09:435/23/16- PASSED WITH THE PROVISO THAT SEPARATE PERMITS
 ARE REQUIRED FOR FENCING, LIGHT POLES, SIGTGNAGE,
 LANDSCAPING, HARDSCAPE (PUBLIC PATHS) AND IRRIGATION.
  
 ANGELLA VANN
 561-822-1441
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-04-21 Cont ID  
Sent By dkittred Date 2016-04-21 Time 18:03 Rev Time 0.00
Received By dkittred Date 2016-04-21 Time 15:29 Sent To  
Notes
2016-04-21 18:01:42PLANNING AND ZONING COMMENTS: ***FAILED***
  
 4/21/16
  
 1. [PREVIOUS COMMENT #1] THERE APPEARS TO BE MORE THAN
 ONE SITE PLAN SUBMITTED - SP0.01, C2.01 AND A1-00
 DEPICTING DIFFERENT AMOUNTS OF INFORMATION. THE
 SUBMITTED SITE PLANS ARE EITHER NOT COMPLETE OR DO NOT
 REPRESENT CHANGES MADE TO THE SINCE CITY COMMISSION
 APPROVAL. PLEASE INCLUDE A COPY OF THE MINOR PD
 AMENDMENT SITE PLAN WHICH WILL ADDRESS THIS COMMENT AND
 THE FOLLOWING PREVIOUS COMMENTS:
 A. INCLUDE ALL SITE DATA AND CALCULATIONS. THIS
 INFORMATION WILL NEED TO BE UPDATED TO REFLECT ANY
 CHANGES TO THE SITE PLAN.
 B. BUBBLE ALL CHANGES ON THE SITE PLAN.
 C. PROVIDE LABELS FOR ITEMS ON THE PLAN (I.E. COVERED
 BATTING TUNNELS, POOL, DUGOUT, ETC.).
 D. INCLUDE DIMENSIONS, SETBACKS, ETC. TO DEMONSTRATION
 COMPLIANCE OR DEVIATIONS FROM THE APPROVED SITE PLAN.
  
 2. SHEET C9.01 - CORRECT STRIPING DETAIL FOR ADA SPACE
 TO SHOWN DOUBLE STRIPED LINES CONNECTED AT THE BOTTOM.
 WHERE ON THE PLANS ARE THE REGULAR PARKING SPACE WIDTHS
 INDICATED. STRIPING DETAIL INDICATES 'STALL WIDTH', BUT
 NO DIMENSION INDICATED.
  
 GENERAL COMMENTS:
  
 3. SHEET L3.08 - DETAIL 2 FOR PLAZA BIKE RACK - BASED
 ON MINIMUM SPACING (2.5 FEET BETWEEN RACKS, 2 FEET
 BETWEEN END RACK AND EDGE OF PAD), PROPOSED 12 RACKS,
 AND WIDTH OF EACH RACK BEING 3 INCHES, THE PAD DEPTH ON
 THE DETAIL NEEDS TO BE A MINIMUM OF 34.5 FEET. A NOTE
 HAS BEEN ADDED TO THE PLAN BUT SHOULD BE CORRECTED WITH
 A RESUBMITTAL.
  
 4. SHEET A7.06 - ENTRY LOGO SCULPTURES WILL NEED TO BE
 PERMITTED UNDER A SEPARATE PERMIT. PLEASE NOTE THAT
 ADDITIONAL REVIEW WILL BE REQUIRED BASED ON THE SIGNAGE
 REGULATIONS AND PLACEMENT. THE PROPOSED LOCATION OF
 NATIONAL ENTRY LOGO SPANS OVER A SIDEWALK AND 3 OF THE
 6 PROPOSED UPLIGHTS ARE ALSO LOCATED ON THE SIDEWALK.
 NOTE HAS BEEN ADDED TO THE PLANS.
  
 5. SEPARATE PERMITS REQUIRED FOR FENCING, LIGHT POLES,
 SIGNAGE, LANDSCAPING, AND IRRIGATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By dkittred Date 2016-03-08 Time 17:34 Rev Time 0.00
Received By dkittred Date 2016-02-26 Time 12:50 Sent To  
Notes
2016-03-10 13:17:16PLANNING AND ZONING COMMENTS **UPDATE**
  
 3/10/16
  
 IN FOLLOW-UP TO COMMENT #7, THE PROPOSED CAPITOL BIKE
 RACK WILL NOT BE AN ACCEPTED MODEL FOR USE AS IT LACKS
 TWO POINTS OF SUPPORT AND HAS LIMITED ABILITY TO HANDLE
 A MIX OF BICYCLE LOCKING MECHANISMS. IF OBLIGATED TO
 USE A BICYCLE RACK MODEL PROVIDED BY FORMS + SURFACES,
 THE FOLLOWING MODELS WILL BE ACCEPTED - TRIO BIKE RACK,
 CORDIA BIKE RACK, SUMMIT BIKE RACK, AND TWIST BIKE
 RACK. OTHERWISE, YOU CAN ALSO WORK WITH ANOTHER VENDOR
 TO PROVIDE AN ACCEPTABLE MODEL.
  
  
2016-03-08 17:37:27PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/8/16
  
 1. THERE APPEARS TO BE MORE THAN ONE SITE PLAN
 SUBMITTED ? C2.01 AND A1-00 DEPICTING DIFFERENT AMOUNTS
 OF INFORMATION. THE SUBMITTED SITE PLAN IS NOT COMPLETE
 AND THE FOLLOWING MUST BE ADDRESSED:
 A. INCLUDE ALL SITE DATA AND CALCULATIONS. THIS
 INFORMATION WILL NEED TO BE UPDATED TO REFLECT ANY
 CHANGES TO THE SITE PLAN.
 B. BUBBLE ALL CHANGES ON THE SITE PLAN.
 C. PROVIDE LABELS FOR ITEMS ON THE PLAN (I.E. COVERED
 BATTING TUNNELS, POOL, DUGOUT, ETC.).
 D. INCLUDE DIMENSIONS, SETBACKS, ETC. TO DEMONSTRATION
 COMPLIANCE OR DEVIATIONS FROM THE APPROVED SITE PLAN.
 E. THE HARDSCAPE PLAN SHOWS CHANGES TO FENCE HEIGHTS
 AND LOCATIONS WHICH WILL ALSO NEED TO BE UPDATED ON THE
 MASTER SITE PLAN. ADDITIONALLY IT IS DIFFICULT TO
 LOCATE 4 FOOT FENCE TYPE ON HARDSCAPE PLAN L3.00 THRU
 L3.06.
  
 2. A MINOR PD AMENDMENT IS REQUIRED FOR ALL CHANGES
 FROM THE APPROVED SITE PLAN. THE MINOR PD AMENDMENT
 SUBMITTAL NEEDS TO HAVE CALCULATIONS DEMONSTRATING THAT
 NONE OF THE MAJOR PD AMENDMENT THRESHOLDS IN RES.
 205-15 ARE EXCEEDED.
  
 3. SHEET 7.04 SHOWS THERE IS NO LONGER A 5 FOOT
 LANDSCAPE ISLAND NEXT TO THE SOUTHEASTERN MOST PARKING
 SPACE BECAUSE THE LIFT STATION APPEARS TO HAVE BEEN
 ENLARGED. PLEASE CONFIRM CONFLICTS WITH THE SITE PLAN.
 A MINIMUM 5 FOOT LANDSCAPE ISLAND WILL BE REQUIRED.
  
 4. SHEET 9.01 - CORRECT STRIPING DETAIL TO PROVIDE 4"
 DOUBLE STRIPES, SEPARATED BY 12", AND CONNECTED AT THE
 BOTTOM [ZLDR SEC. 94-485, STALL PAINING DETAIL]. SINGLE
 STRIPED PARKING SPACES IS NOT PERMITTED.
  
 5. SHEET L3.00 - PLEASE NOTE THAT THE COLOR CHOSEN ON
 THE HARDSCAPE PLAN TO REPRESENT THE CRUSHED GRAVEL
 PATHWAY IS A VERY SIMILAR IN COLOR TO THE PAVED PARKING
 AREAS. PLEASE PROVIDE ANOTHER COLOR OR SYMBOL TO
 DISTINGUISH THE DIFFERENCE BETWEEN THE CRUSHED GRAVEL
 PATHWAY AND PAVED PARKING AREAS.
  
 6. SHEET L3.08 - DETAIL 1 FOR STANDARD BIKE RACK DETAIL
 - THE BICYCLE RACK SPACING DIMENSIONS ARE FROM THE RACK
 ITSELF AND NOT THE CENTER OF THE RACK. PLEASE ACCOUNT
 FOR WIDTH OF RACKS IN OVERALL WIDTH OF THE BICYCLE
 PARKING PADS TO ENSURE 2.5 FEET CAN BE PROVIDED BETWEEN
 RACKS AND 2 FEET FROM THE END RACK TO EDGE OF PAD.
 ADJUST SIZES ON SITE PLAN AS NECESSARY.
  
 7. SHEET L3.08 - DETAIL 2 FOR CAPITOL BIKE RACK - THIS
 MODEL IS UNDER REVIEW AS AN ACCEPTABLE BICYCLE RACK
 STYLE FOR USE IN THE CITY. IF APPROVED, PROVIDE A
 SPACING DETAIL FOR THE BICYCLE RACKS TO DEMONSTRATE A
 MINIMUM 2.5 FEET BETWEEN RACKS, 2 FEET BETWEEN END RACK
 AND EDGE OF PAD, AND 6 FEET MINIMUM LENGTH FOR THE
 PARKING PAD.
  
 8. PLEASE REVIEW ALL PLANS FOR CONSISTENCY WITH BICYCLE
 PARKING LOCATIONS. FOR EXAMPLE, PLAZA PARKING IS
 DEPICTED DIFFERENTLY IN SHEETS L3.03 AND L4.04.
  
 9. ALL EQUIPMENT CORRALS MUST BE SCREENED IN ACCORDANCE
 WITH ZLDR SEC. 94-444(B) AND (C). WINDSCREENS ON A
 CHAIN-LINK FENCE IS NOT SUFFICIENT.
  
 10. SHEET A7.06 - ENTRY LOGO SCULPTURES WILL NEED TO BE
 PERMITTED UNDER A SEPARATE PERMIT. PLEASE NOTE THAT
 ADDITIONAL REVIEW WILL BE REQUIRED BASED ON THE SIGNAGE
 REGULATIONS AND PLACEMENT. THE PROPOSED LOCATION OF
 NATIONAL ENTRY LOGO SPANS OVER A SIDEWALK AND 3 OF THE
 6 PROPOSED UPLIGHTS ARE ALSO LOCATED ON THE SIDEWALK.
  
 11. SHEET E1-00-3, SHEET E1-00-4 - THERE ARE WALL
 MOUNTED JUNCTION BOXES WITHIN THE SETBACK. HOW HIGH ARE
 THESE JUNCTION BOXES MOUNTED?
  
 12. SEPARATE PERMITS REQUIRED FOR FENCING, LIGHT POLES,
 SIGNAGE, LANDSCAPING, AND IRRIGATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  