Plan Review Details - Permit 16020406
Plan Review Stops For Permit 16020406
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By jgomez Date 2016-03-10 Time 11:28 Rev Time 0.00
Received By jgomez Date 2016-03-10 Time 07:50 Sent To  
Notes
2016-03-10 11:46:21RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES AS SPECIFIED ON PLANS.
  
 B) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 C) HURRICANE SHUTTERS IF DOORS WITH GLAZING DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER RECORD TO LIST FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- PLANS SUBMITTED ARE NOT LEGIBLE. LETTERING ON PLANS
 AND ELEVATIONS IS TOO BLURRY. PROVIDE CLEAR COPIES.
 SEC. 107.2.1.4
  
 4- CHANGING THE USE OF THE DETACHED GARAGE. PLEASE
 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-02 Cont ID  
Sent By vperez Date 2016-03-02 Time 12:48 Rev Time 0.00
Received By vperez Date 2016-03-02 Time 12:48 Sent To  
Notes
2016-03-02 13:24:35INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES-
 E3603.1
 2.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES-
 E3609.3
 3.PROVIDE GFCI PROTECTION FOR RECEPTACLES WITHIN 6FT OF
 SINK IN LAUNDRY AREA. FBC RES- E3902.7
 4.PROVIDE GFCI PROTECTION FOR RECEPTACLES IN BATHROOM
 AREA. FBC RES- E3902.1
 5.SHOW AN EQUIPMENT GROUNDING CONDUCTOR WITH THE FEEDER
 CONDUCTORS SERVING THE SUBPANEL LOADS. FBC RES-
 E3607.3.1
 6.PROVIDE GENERAL NOTES INDICATING AFCI FOR BRANCH
 CIRCUITS. FBC RES- E3902.12
 7.PROVIDE GENERAL NOTES INDICATING TAMPER RESISTANT
 RECEPTACLES REQUIRED PER FBC RES- E4002.14
 8.SUMP PUMP SHOWN TO HAVE GFCI PROTECTION. FBC RES
 E3902.3
 9.SHOW LAUNDRY OUTLET ON PANEL SCHEDULE AT 20AMP
 MINIMUM PER E3703.3
 10.SHOW BATHROOM OUTLET ON PANEL SCHEDULE AT 20AMP
 MINIMUM PER E3703.4
 11.PANEL SCHEDULES BRANCH CIRCUIT MUST ID EXACTLY WHAT
 AREA IS BEING PROTECTED, GEN LIGHTING ID NOT
 SUFFICIENT. SEE FBC RES E3706.2
 12.CORRECT TYPO ON SUB-PANEL SCHEDULE TO INDICATE 15AMP
 OVERCURRENT BREAKER NOT 14AMP AS SHOWN. FBC 107.3.5
 13.ZONING COMMENTS PENDING REGARDING USE OF STUCTURE AS
 SHOWN.
 14.FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-03-15 Cont ID  
Sent By fmitter Date 2016-03-15 Time 15:29 Rev Time 0.00
Received By fmittner Date 2016-03-15 Time 15:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-16 Cont ID  
Sent By lmarchan Date 2016-03-16 Time 09:28 Rev Time 0.00
Received By lmarchan Date 2016-02-11 Time 09:38 Sent To  
Notes
2016-03-02 13:26:313/02 TO LAURA
2016-02-12 09:38:45R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-03-10 Cont ID  
Sent By jgomez Date 2016-03-10 Time 16:08 Rev Time 0.00
Received By jgomez Date 2016-03-10 Time 16:08 Sent To  
Notes
2016-03-10 16:11:191- CHANGING THE USE OF THE DETACHED GARAGE. PLEASE
 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-20 Cont ID  
Sent By tklarge Date 2016-02-20 Time 06:24 Rev Time 0.00
Received By tklarge Date 2016-02-20 Time 06:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-03-15 Cont ID  
Sent By fmittner Date 2016-03-15 Time 15:29 Rev Time 0.00
Received By fmittner Date 2016-03-15 Time 15:29 Sent To  
Notes
***NONE***