Plan Review Details - Permit 16020377
Plan Review Stops For Permit 16020377
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2016-12-14 Cont ID  
Sent By jwitmer Date 2016-12-14 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-12-14 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2016-09-20 Cont ID  
Sent By jwitmer Date 2016-09-20 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2016-09-20 Time 13:23 Sent To  
Notes
2016-09-20 14:18:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 5TH REVIEW
 DATE: TUES. SEPT. 20/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1) THE BUILDING OFFICIAL HAS APPROVED THE COST ANALYSIS
 AND REVIEWING THE DOCUMENTS. THE 4 SUB-PERMITS THAT ARE
 A NO COST IF THEY CAME IN AT THE TIME OF THE PRIME
 PERMIT ARE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING.
 IF THEY COME IN AFTER THE PRIME PERMIT WAS CREATED THEY
 ARE A $80.00 SUB-PERMIT, THE $80.00 IS AN
 ADMINISTRATIVE FEE.
 THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE
 PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE
 DEDUCTED FROM THE $900,000.00 STATED. THESE PERMIT
 INCLUDE, FIRE SPRINKLERS, FIRE ALARMS, ALL LOW VOLTAGE
 PERMITS. THIS VALUE WILL NEED TO BE DECLARED SO WE CAN
 REDUCE THE OVERALL BUILDING VALUE SO WE DO NOT CHARGE
 YOU TWICE FOR ASSOCIATED PERMIT FEES.
  
 PLEASE NOTE ALL OTHER PERMITS NOT ASSOCIATED WITH THE
 BUILDING ARE CONSIDERED PROJECT COST AND WILL BE
 PERMITTED SEPARATELY. SITE CLEARING, DEMOLITION OF
 STRUCTURES, UNDERGROUND UNITIES, PAVING, SEAL COATING &
 STRIPING, SIDEWALKS, IRRIGATION, LANDSCAPE, POOLS, POOL
 DECK IF NOT INCLUDED IN THE POOL CONTRACT, FENCING, OUT
 BUILDINGS, SIGNAGE ETC.
  
 2) COMPLIED. A PAPER SIGNED AND SEALED ORIGINAL SOILS
 REPORT ON FILE WITH CITY.
  
  
 3) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM.
 THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE
 PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES
 AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND
 FLORIDA ACCESSIBILITY CODE.
 REACH RANGES UNDER 308.
 OPERABLE PARTS 309.
  
 4) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR
 ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED
 BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF
 APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 5A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 6A) PROVISO: BAHAMA SHUTTERS TO PROVIDE SHOP DRAWINGS,
 PLEASE NOTE I UNDERSTAND THE INTENT IS TO LEAVE THESE
 AWNINGS IN THE OPEN POSITION IN A HIGH WIND EVENT.
 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID
 AWNINGS AND CANOPY SHUTTERS.
  
 6B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED
 FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE
 FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR
 HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-06-07 Cont ID  
Sent By jwitmer Date 2016-06-07 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2016-06-07 Time   Sent To  
Notes
2016-06-07 08:37:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4TH REVIEW
 DATE: TUES. JUNE 07/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1)THE BUILDING OFFICIAL IS IN RECEIPT OF COST ANALYSIS
 AND REVIEWING THE DOCUMENTS.
 CONTRACTOR TO BRING IN A EVALUATION BY A CPA. THE
 PERMIT APPLICATION VALUE OF $900,000,00 DOLLARS IS
 ACTUALLY HIGH IN RELATION TO THE AUGUST 2015 ICC
 VALUATION TABLES. THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED
 PERMITS. PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS
 FOR THE BUILDING, SUBMIT A LIST OF PERMITS AND
 BREAK-OUT THE VALUE FROM THE TOTAL COST TO DETERMINE
 THE FINAL VALUATION OF THE BUILDING PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) COMPLIED.
  
 2F) NOTICE ONLY, FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G) NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACHES AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) COMPLIED/ ADDRESSING
  
 4) 4TH REQUEST.
 SUBMITTED IS A 195 PAGE DOCUMENT FOR PHASE I
 ENVIRONMENTAL SITE ASSESSMENT, NOT FOR MINIMUM BEARING
 VALUE, IT WOULD APPEAR A LAKE ONSITE WILL BE FILED IN
 AND THERE IS NO INFORMATION AS TO HOW THE FILE WILL BE
 COMPACTED, NO INFORMATION ON SOILS BORING TEST NOR THE
 DEVELOPMENT OF THE PADS FOR THE FOUNDATION. MISSING
 FROM THE SUPPORTING DOCUMENT FOLDER IS COMPLIANCE WITH:
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) COMPLIED.
  
 6) SEMI-COMPLIED. SEE MECHANICAL COMMENTS.
  
 7A-C) COMPLIED.
  
 7D) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM.
 THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE
 PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES
 AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND
 FLORIDA ACCESSIBILITY CODE.
 REACH RANGES UNDER 308.
 OPERABLE PARTS 309.
  
 8A) PROVISO: THE DESIGNER INDICATES 45 MIN. WINDOW,
 DOORS AND FRAMES. THE CONTRACTOR IN RESPONSE INDICATES
 THESE OPENINGS WILL HAVE PRODUCT TESTING FOR BOTH FIRE
 RESISTANCE RATING AND LARGE MISSILE IMPACT RESISTANCE
 TESTING. IF THE UNIT COST ARE TOO HIGH FOR THESE TYPE
 OF UNITS THEN FIRE RATED WINDOWS AND STORM SHUTTERS AND
 OR PANELS WILL BE REQUIRED. IF STORM PANELS ARE TO BE
 INSTALLED, THEN STORAGE WITHIN THE RECREATION CENTER
 WILL BE A REQUIREMENT.
  
 SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE
 WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE
 RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE
 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE
 RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45
 MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW
 THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED
 GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE
 ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING
 AS WELL AS LARGE MISSILE IMPACT TESTING.
  
 8B) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR
 ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED
 BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF
 APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 9) COMPLIED.
 .
 10A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10C) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10D) PROVISO: FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIXE.
  
 10E) PROVISO: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
  
 10F) COMPLIED. SHEET A8.03 DETAIL # 1 AC/ COMPRESSORS
 BEING TIED DOWN TO CONCRETE PADS
  
 11A) PROVISO: BAHAMA SHUTTERS TO PROVIDE SHOP DRAWINGS,
 PLEASE NOTE I UNDERSTAND THE INTENT IS TO LEAVE THESE
 AWNINGS IN THE OPEN POSITION IN A HIGH WIND EVENT.
 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID
 AWNINGS AND CANOPY SHUTTERS.
  
 11B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED
 FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE
 FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR
 HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 12) COMPLIED.
  
 13) 4TH REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) BEFORE PERMIT ISSUANCE CAN OCCUR ONE SET OF SIGNED
 AND SEALED DOCUMENTS (PLANS, SOILS REPORTS, & ENERGY
 CALCULATIONS) WILL BE SUBMITTED TO THE BUILDING
 DEPARTMENT FOR THE RECORD RETENTION PROGRAM AND
 REVIEWED WITH THE ELECTRONIC PLANS FOR ACCURACY AND
 CODE COMPLIANCE.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 13:53 Rev Time 0.00
Received By jwitmer Date 2016-05-12 Time 16:55 Sent To  
Notes
2016-05-13 13:53:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: FRI. MAY 13 19/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1) CONTRACTOR TO BRING IN A EVALUATION BY A CPA. THE
 PERMIT APPLICATION VALUE OF $9,000,000.00 DOLLARS IS
 ACTUALLY HIGH IN RELATION TO THE AUGUST 2015 ICC
 VALUATION TABLES. THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED
 PERMITS. PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS
 FOR THE BUILDING, SUBMIT A LIST OF PERMITS AND
 BREAK-OUT THE VALUE FROM THE TOTAL COST TO DETERMINE
 THE FINAL VALUATION OF THE BUILDING PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) COMPLIED.
  
 2F) NOTICE ONLY, FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G) NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACHES AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) COMPLIED/ ADDRESSING
  
 4) 3RD REQUEST. MISSING FROM THE SUPPORTING DOCUMENT
 FOLDER IS COMPLIANCE WITH: 2014 FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 5) COMPLIED.
  
 6) SEMI-COMPLIED. SEE MECHANICAL COMMENTS.
  
 7A-C) COMPLIED.
  
 7D) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM.
 THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE
 PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES
 AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND
 FLORIDA ACCESSIBILITY CODE.
 REACH RANGES UNDER 308.
 OPERABLE PARTS 309.
  
 8A) PROVISO: THE DESIGNER INDICATES 45 MIN. WINDOW,
 DOORS AND FRAMES. THE CONTRACTOR IN RESPONSE INDICATES
 THESE OPENINGS WILL HAVE PRODUCT TESTING FOR BOTH FIRE
 RESISTANCE RATING AND LARGE MISSILE IMPACT RESISTANCE
 TESTING. IF THE UNIT COST ARE TOO HIGH FOR THESE TYPE
 OF UNITS THEN FIRE RATED WINDOWS AND STORM SHUTTERS AND
 OR PANELS WILL BE REQUIRED. IF STORM PANELS ARE TO BE
 INSTALLED, THEN STORAGE WITHIN THE RECREATION CENTER
 WILL BE A REQUIREMENT.
  
 SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE
 WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE
 RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE
 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE
 RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45
 MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW
 THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED
 GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE
 ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING
 AS WELL AS LARGE MISSILE IMPACT TESTING.
  
 8B) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR
 ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED
 BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF
 APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 9) COMPLIED.
 .
 10A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10C) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10D) PROVISO: FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIXE.
  
 10E) PROVISO: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
  
 10F) COMPLIED. SHEET A8.03 DETAIL # 1 AC/ COMPRESSORS
 BEING TIED DOWN TO CONCRETE PADS
  
 11A) PROVISO: BAHAMA SHUTTERS TO PROVIDE SHOP DRAWINGS,
 PLEASE NOTE I UNDERSTAND THE INTENT IS TO LEAVE THESE
 AWNINGS IN THE OPEN POSITION IN A HIGH WIND EVENT.
 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID
 AWNINGS AND CANOPY SHUTTERS.
  
 11B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED
 FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE
 FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR
 HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 12) COMPLIED.
  
 13)3RD REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) BEFORE PERMIT ISSUANCE CAN OCCUR ONE SET OF SIGNED
 AND SEALED DOCUMENTS (PLANS, SOILS REPORTS, & ENERGY
 CALCULATIONS) WILL BE SUBMITTED TO THE BUILDING
 DEPARTMENT FOR THE RECORD RETENTION PROGRAM AND
 REVIEWED WITH THE ELECTRONIC PLANS FOR ACCURACY AND
 CODE COMPLIANCE.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-19 Cont ID  
Sent By jwitmer Date 2016-04-19 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2016-04-19 Time 10:01 Sent To  
Notes
2016-04-19 12:34:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7000 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. APRIL 19/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1) 2ND REQUEST. THE PERMIT APPLICATION VALUE OF
 $9,000,000.00 DOLLARS IS ACTUALLY HIGH IN RELATION TO
 THE AUGUST 2015 ICC VALUATION TABLES. THE MEP AND
 ROOFING PERMITS, ARE SUB-PERMITS AND IF NOT SUBMITTED
 AT THE TIME OF PERMIT ARE A $80.00 SUB-PERMIT AND ARE
 INCLUDED IN THE VALUE OF THE BUILDING COST. ALL OTHER
 SUB-PERMITS ARE FEED PERMITS. PLEASE PROVIDE A LIST OF
 ALL OTHER SUB-PERMITS FOR THE BUILDING, SUBMIT A LIST
 OF PERMITS AND BREAK-OUT THE VALUE FROM THE TOTAL COST
 TO DETERMINE THE FINAL VALUATION OF THE BUILDING
 PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) PLEASE NOTE THIS BUILDING DOES NOT REQUIRE A
 THRESHOLD OR A RESIDENT INSPECTOR. PLEASE CONFIRM THAT
 THE CONTRACTOR IS GOING TO CALL IN INSPECTIONS FOR THE
 CITY INSPECTORS WILL BE DOING THE STRUCTURAL
 INSPECTIONS FOR THIS BUILDING OR WILL THE THRESHOLD
 INSPECTOR ALSO COMPLETE THE STRUCTURAL INSPECTIONS FOR
 THIS BUILDING AS WELL.
  
 THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) COMPLIED/ MAY 02/16.2ND REQUEST. THRESHOLD
 INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 2C)COMPLIED W.P.B. AMENDMENT 110.3.7.4./ 633 FLORIDA
 STATUTE.
  
 2D) COMPLIED/ MAY 02/16. 2ND REQUEST. FOR THE SPECIAL
 INSPECTOR PLEASE PROVIDE A RESUME' OF INSPECTION
 EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' MUST BE
 ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME'. AFTER THE RESUME' IS REVIEWED, A INTERVIEW
 MAYBE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA.
  
 2E) COMPLIED/ MAY 02/16. 2ND REQUEST. THE CONTRACTOR
 WILL PRODUCE A JOB SUMMARY OR HISTORY FOR THIS TYPE OF
 CONSTRUCTION.
  
  
 2F) NOTICE ONLY, FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACHES AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) COMPLIED/ ADDRESSING
  
 4) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT
 FOLDER IS COMPLIANCE WITH: 2014 FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 5A) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT
 FOLDER IS A SURVEY. 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE
  
 5B) COMPLIED. ASSUMED PROPERTY LINE BETWEEN THE VARIOUS
 BUILDINGS WITH THE PERCENTAGE OF ALLOWABLE OPENINGS
  
 6) 2ND REQUEST. UNDER THE 2014 ENERGY CODE THIS
 BUILDING IS USING ASHRAE 90 FORMS FOR CODE COMPLIANCE.
 THE INPUT DATA REPORT ON PAGES 2 & 3 INDICATES THE USE
 OF ? INCH ISO BETWEEN ? INCH FURRING. PAGE 7 UNDER THE
 MATERIALS USED ALSO INDICATES THE USE OF 4.8/ 0.75 INCH
 ISO BETWEEN FURRING 24 INCHES ON CENTER. WHEREAS SHEET
 A.302R INDICATES R4.1 AL-FOIL INSULATION BETWEEN 1 X2
 PT FURRING STRIPS. NOTE THERE IS A DISCREPANCY BETWEEN
 THE ENERGY CALCULATIONS AND THE WALL INSULATION
 INDICATED ON THE PLANS.
  
 7A) COMPLIED. SHEET A2.00 R IS THE LIFE SAFETY PLAN FOR
 THE LEASING AND RECREATION CENTER. THE SHEET INDICATES
 UNDER THE OCCUPANCY TYPE AN A3 FOR THE RECREATION
 CENTER. THE LEASING AREA OF THE BUILDING IS
 APPROXIMATELY 936 SQ. FT. OR 0.18 % OF THE FLOOR PLATE
 MAKING THIS A MIXED USE OCCUPANCY BETWEEN AN A3
 OCCUPANCY AND A BUSINESS OCCUPANCY. IN THE 2014 FBC-B
 TABLE 508.4 BETWEEN AN A3 AND BUSINESS OCCUPANCY
 REQUIRES 2 HOUR SEPARATION FOR NON-SPRINKLERED
 BUILDINGS. THE DESIGNER OF RECORD HAS NOT DECLARED IF
 THE PLANS WERE DEVELOPED AS SEPARATION OF
 OCCUPANCIES(508.2.4) OR NON-SEPARATED OCCUPANCIES
 (508.3).
  
 7B) COMPLIED. THE RECREATION AND LEASING BUILDING WILL
 NOT ONLY NEED TO MEET THE REQUIREMENTS OF FAIR HOUSING
 BUT THE FBC-ACCESSIBILITY CODE AS WELL. THE FITNESS
 ROOM THE EXERCISE MACHINE AND EQUIPMENT WILL NEED TO
 MEET THE REQUIREMENTS OF FBC-ACCESSIBILITY CODE 1004.1.
  
 7C) COMPLIED. KITCHEN/ BREAK ROOM SINK
  
 7D) PROVISO: THERE ARE NO ELEVATIONS OF THE BREAK ROOM.
 THERE ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE
 PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES
 AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND
 FLORIDA ACCESSIBILITY CODE.
 REACH RANGES UNDER 308.
 OPERABLE PARTS 309.
  
 8A) SEMI-COMPLIED. DESIGNER WILL PROVIDE 45 MIN. WINDOW
 AND FRAMES. WILL NEED TO SUPPLY STORM SHUTTERS AS WELL.
 WILL THE BAHAMA STYLE SUN SHADE BE TESTED FOR HURRICANE
 IMPACT TESTING THAT CAN BE DROPPED INCASE OF A
 HURRICANE AS THE LARGE MISSILE RESISTANT COVERING? IS
 SO SUPPLY THE PRODUCT APPROVAL.
  
 SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE
 WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE
 RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE
 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE
 RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45
 MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW
 THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED
 GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE
 ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING
 AS WELL AS LARGE MISSILE IMPACT TESTING.
  
 8B) PROVISO: CONTRACTOR TO SUBMIT PRODUCT APPROVAL FOR
 ADHERED MASONRY VENEER PER FBC-B 1405.10 TO BE REVIEWED
 BY THE DESIGNER OF RECORD, SHOP DRAWING STAMP OF
 APPROVAL APPLIED BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 9) SHEET S-3 REC BUILDING NOTES.
 9A)2ND REQUEST, THERE IS A BLOCKED OUT SQUARE WHERE THE
 CONSTRUCTION TYPE IS LOCATED.
 THE DESIGN PARAMETERS LIST THIS CONSTRUCTION AS
 BUILDING TYPE VB. WHEREAS THE LIFE SAFETY SHEET A2.00
 INDICATES THE BUILDING TYPE IIIB. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9B) COMPLIED.
 9C) COMPLIED. WIND DESIGN.
 10A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10B) PROVISO: COMPONENTS & CLADDING. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10C) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10D) PROVISO: FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIXE.
  
 10E) PROVISO: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
  
 10F) SHEET A8.03 DETAIL # 1 INDICATES AC/ COMPRESSORS
 BEING TIED DOWN TO CONCRETE PADS WITH 1 ? INCH HILTI
 POWER ACTUATED DRIVE PINS @ EACH CORNER THRU THE
 COMPRESSOR PAN. SHEET M4 SHOW A DIFFERENT TYPE OF TIE
 DOWN DISCREPANCY IN PLANS.
  
 11A) 2ND REQUEST. SHEET A3.02 INDICATES AN AWNING
 DETAIL FOUND ON SHEET A8.01, THIS SHEET IS LOADED FOR
 THIS REVIEW BUT THERE IS NO DETAIL 06.PLEASE PROVIDE
 DOCUMENTATION AS TO IS THIS A FABRIC AWNING OR A RIGID
 FIXED AWNING? PLEASE PROVIDE TO WHICH DESIGN CRITERIA
 THE AWNING IS TO BE DESIGNED TOO? THE SHUTTER
 FABRICATOR NEEDS TO KNOW TO WHAT WIND SPEED THE SHUTTER
 DESIGN NEEDS TO MEET. IS THE DESIGN INTENT TO LEAVE THE
 SHUTTER OPEN IN THE FIXED POSITION IN THE EVENT OF A
 HIGH WIND EVENT
 2014 FBC-B 3105.4 DESIGN. 2014 FBC-B 3105.5 RIGID
 AWNINGS AND CANOPY SHUTTERS.
  
 11B) COMPLIED, N/A. 2014 FBC-B 3105.3.3.1 FABRIC USED
 FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE
 FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR
 HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 12) COMPLIED.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) BLUE LINE RAMP AND DECK MODULAR STRUCTURE PLAN IS
 NOT SIGNED NOR SEALED. PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 15) NEITHER THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL
 SHEETS HAVE ELECTRONIC SIGNATURES. THE CITY NO LONGER
 ACCEPTS THE PEDDS SIGNATURE, 61G15-23.005 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO SEAL ENGINEERING WORK SHALL HAVE THEIR
 IDENTITY AUTHENTICATED BY A CERTIFICATION AUTHORITY AND
 SHALL ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT;
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By jwitmer Date 2016-02-17 Time 15:49 Rev Time  
Received By jwitmer Date 2016-02-17 Time   Sent To  
Notes
2016-02-17 15:49:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7000 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. FEB. 17/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1) THE PERMIT APPLICATION VALUE OF $9,000,000.00
 DOLLARS IS ACTUALLY HIGH IN RELATION TO THE AUGUST 2015
 ICC VALUATION TABLES. THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED
 PERMITS. PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS
 FOR THE BUILDING, SUBMIT A LIST OF PERMITS AND
 BREAK-OUT THE VALUE FROM THE TOTAL COST TO DETERMINE
 THE FINAL VALUATION OF THE BUILDING PERMIT.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) PLEASE NOTE THIS BUILDING DOES NOT REQUIRE A
 THRESHOLD OR A RESIDENT INSPECTOR. PLEASE CONFIRM THAT
 THE CONTRACTOR IS GOING TO CALL IN INSPECTIONS FOR THE
 CITY INSPECTORS WILL BE DOING THE STRUCTURAL
 INSPECTIONS FOR THIS BUILDING OR WILL THE THRESHOLD
 INSPECTOR ALSO COMPLETE THE STRUCTURAL INSPECTIONS FOR
 THIS BUILDING AS WELL.
  
 THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 A INTERVIEW MAYBE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) PLEASE NOTE THE SITE ADDRESS HAS BEEN PROVIDED AS
 7000 OKEECHOBEE BLVD. PLEASE CONTACT THE CITY?S
 ADDRESSING SPECIALIST FOR ADDRESSING CONCERNS, EITHER
 STREET NAMES OR NUMERICAL ADDRESSES TO IDENTIFY EACH
 BUILDING. CITY MUNI CODE SEC.78-6 (1-7).
 (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE
 ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR
 TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE
 ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE
 BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE
 HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE
 NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF
 NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE,
 SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE
 CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS
 WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A
 SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS
 SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL
 ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL
 ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE
 POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH
 A COMMON EXTERIOR ENTRANCE.
 (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE
 RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE
 DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
  
 4) MISSING FROM THE SUPPORTING DOCUMENT FOLDER IS
 COMPLIANCE WITH: 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5A) MISSING FROM THE SUPPORTING DOCUMENT FOLDER IS A
 SURVEY. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE
  
 5B) MISSING FROM THE PLANS IS A SITE PLAN THAT SHOWS
 THE ASSUMED PROPERTY LINE BETWEEN THE VARIOUS BUILDINGS
 WITH THE PERCENTAGE OF ALLOWABLE OPENINGS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE
  
 6) UNDER THE 2014 ENERGY CODE THIS BUILDING IS USING
 ASHRAE 90 FORMS FOR CODE COMPLIANCE. THE INPUT DATA
 REPORT ON PAGES 2 & 3 INDICATES THE USE OF ? INCH ISO
 BETWEEN ? INCH FURRING. PAGE 7 UNDER THE MATERIALS USED
 ALSO INDICATES THE USE OF 0.75 INCH ISO BETWEEN FURRING
 24 INCHES ON CENTER. WHERE AS SHEET A.302R INDICATES
 R4.1 AL-FOIL INSULATION BETWEEN 1 X3 PT FURRING STRIPS.
 NOTE THERE IS A DISCREPANCY BETWEEN THE ENERGY
 CALCULATIONS AND THE WALL INSULATION INDICATED ON THE
 PLANS.
  
 7A) SHEET A2.00 R IS THE LIFE SAFETY PLAN FOR THE
 LEASING AND RECREATION CENTER. THE SHEET INDICATES
 UNDER THE OCCUPANCY TYPE AN A3 FOR THE RECREATION
 CENTER. THE LEASING AREA OF THE BUILDING IS
 APPROXIMATELY 936 SQ. FT. OR 0.18 % OF THE FLOOR PLATE
 MAKING THIS A MIXED USE OCCUPANCY BETWEEN AN A3
 OCCUPANCY AND A BUSINESS OCCUPANCY. IN THE 2014 FBC-B
 TABLE 508.4 BETWEEN AN A3 AND BUSINESS OCCUPANCY
 REQUIRES 2 HOUR SEPARATION FOR NON-SPRINKLERED
 BUILDINGS. THE DESIGNER OF RECORD HAS NOT DECLARED IF
 THE PLANS WERE DEVELOPED AS SEPARATION OF
 OCCUPANCIES(508.2.4) OR NON-SEPARATED OCCUPANCIES
 (508.3).
  
 7B) THE RECREATION AND LEASING BUILDING WILL NOT ONLY
 NEED TO MEET THE REQUIREMENTS OF FAIR HOUSING BUT THE
 FBC-ACCESSIBILITY CODE AS WELL. THE FITNESS ROOM THE
 EXERCISE MACHINE AND EQUIPMENT WILL NEED TO MEET THE
 REQUIREMENTS OF FBC-ACCESSIBILITY CODE 1004.1.
  
 7C) THIS SHEET SHOWS A KITCHEN/ BREAK ROOM. THE PLANS
 DO NOTE THAT THE SINK WILL BE LOCATED IN THE COUNTER
 TOP AT 34 INCHES ABOVE FLOOR LEVEL. THERE ARE NO OTHER
 DETAILS TO SHOW COMPLIANCE WITH FAIR HOUSING NOR THE
 FLORIDA ACCESSIBILITY CODE.
  
 7D) THERE ARE NO ELEVATIONS OF THE BREAK ROOM. THERE
 ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE
 PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES
 AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND
 FLORIDA ACCESSIBILITY CODE.
 REACH RANGES UNDER 308.
 OPERABLE PARTS 309.
  
 8A) SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE
 WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE
 RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE
 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE
 RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45
 MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW
 THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED
 GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE
 ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING
 AS WELL AS LARGE MISSILE IMPACT TESTING.
  
 8B) SHEET A3.01R & A3.02R BOTH INDICATE THE USE OF
 CULTURED STONE. THERE IS A NOTE ON THE PLANS STONE
 VENEER BY CULTURED STONE LEDGE STONE VENEER TYPE. THIS
 PRODUCT HAS CODE COMPLIANCE EVALUATION AND LISTING,
 TEST ICC-ESESR-1364. PLEASE SUBMIT REPORT TO VERIFY
 COMPLIANCE WITH EITHER 1405.7 STONE VENEERS/ ANCHORED
 OR 1405.10 ADHERED MASONRY VENEERS. TO BE REVIEWED BY
 THE DESIGNER OF RECORD BEFORE BEING SUBMITTED TO THE
 BUILDING DEPARTMENT.
  
 9) SHEET S-2 REC BUILDING NOTES.
 9A) THE DESIGN PARAMETERS LIST THIS CONSTRUCTION AS
 BUILDING TYPE VB. WHEREAS THE LIFE SAFETY SHEET A2.00
 INDICATES THE BUILDING TYPE IIIB. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9B) THE DESIGN PARAMETERS AND ASSUMPTIONS LIST THE
 OCCUPANCY CLASSIFICATION AS R-3. NOTE THIS IS A MIXED
 USE OCCUPANCY A3/B.
  
 9C) NO WIND LOAD CHART HAS BEEN PROVIDED FOR ZONES
 1,2,3, 4 & 5. PLEASE PROVIDE THE POSITIVE AND NEGATIVE
 PRESSURES IN VASD SINCE THE PRODUCT APPROVALS ARE GIVEN
 IN VASD. PLEASE PROVIDE CALCULATIONS (STATING VASD) FOR
 10 SQ. FT., 20 SQ. FT., 50 SQ. FT. & 100 SQ. FT. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA, WIND DESIGN PRESSURES.
  
 10A) MISSING FROM THE SUBMITTED DOCUMENT FILE WERE
 PRODUCT APPROVAL DOCUMENTS. EITHER THE DESIGNER OF
 RECORD OR CONTRACTOR CAN SUBMIT THE PRODUCT APPROVAL
 DOCUMENTS OR ELECT TO HAVE THESE DOCUMENTS BE
 CONSIDERED AS A DEFERRED SUBMITTAL. IF THEY PREFER THE
 PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS THEY MUST
 STATE SO IN THE RESPONSE NARRATIVE.
  
 10B) COMPONENTS & CLADDING. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 10D) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIXE.
  
 10E) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED. IF SO RAS 117
 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT
 OR ENGINEER.
  
 10F) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 11A) SHEET A3.02 INDICATES A AWNING DETAIL FOUND ON
 SHEET A8.01, THERE IS NO SUCH SHEET IN THIS SET OF
 DRAWINGS. PLEASE PROVIDE DOCUMENTATION AS TO IS THIS A
 FABRIC AWNING OR A RIGID FIXED AWNING? PLEASE PROVIDE
 TO WHICH DESIGN CRITERIA THE AWNING IS TO BE DESIGNED
 TOO?
 2014 FBC-B 3105.4 DESIGN.
 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS.
  
 11B) 2014 FBC-B 3105.3.3.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD
 INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84 OR UL 723.
  
 12) SHEET S-4 DETAIL C SHOWS A DOUBLE LEDGER TO BE
 ATTACHED TO THE BLOCK WALL WITH FILED CELLS.
 12A) THE PLANS DO NOT PROVIDE WHAT SIZE OF LUMBER THE
 LEDGER SHOULD BE NOR THE TYPE OF WOOD, SPECIES, & GRADE
 ? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 12B) THIS SAME DETAIL INDICATES THE LEDGER BE FASTENED
 TO THE FILED CELL BLOCK WALL, BUT MISSING THE TYPE OF
 ANCHOR, DIAMETER & LENGTH, AND AT WHAT CENTER TO CENTER
 ARE THEY TO BE PLACED. THE PLANS ALSO FAIL TO INDICATE
 THE LOCATION OF THE ANCHOR IN REGARDS TO THE FRAMING
 MEMBER, UPPER 1/3RD, CENTERED OR IN THE LOWER 1/3RD OR
 STAGGERED? ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.3.
  
 12C) THE TYPICAL CUT SECTION THROUGH A 1 STORY
 STRUCTURE LOWER RIGHT CORNER OF THE SHEET INDICATES
 19/32 EXPOSURE1, EXTERIOR GRADE PLYWOOD
 SHEATHING(OPTION OSB).
 PLEASE REVIEW 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-12-15 Cont ID  
Sent By vperez Date 2016-12-15 Time 15:02 Rev Time 0.00
Received By vperez Date 2016-12-15 Time 15:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-04 Cont ID  
Sent By vperez Date 2016-04-04 Time 11:24 Rev Time 0.00
Received By vperez Date 2016-04-04 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By vperez Date 2016-02-18 Time 09:27 Rev Time 0.00
Received By vperez Date 2016-02-18 Time 09:27 Sent To  
Notes
2016-02-18 09:27:22INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM,
 ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE
 REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM
 COVER REQUIREMENTS FOR CONDUITS AND THE PLACEMENT OF A
 WARNING RIBBON FOR THE SERVICE LATERAL CONDUCTORS SHOWN
 FOR THIS PROJECT. A NOTE WILL SUFFICE.
 3. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION.
 4. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY UTILITY FOR APPROVAL. NEC 110.24 FBC 107
 5. LABEL MAINS TO INDICATE MAIN 1 OF 3 AND 2 OF 3 AND 3
 OF 3, FOR THE 600A MLO ALSO COMPLY WITH THE REQUIRED
 SIGNAGE TO ASSIST FIRST RESPONDERS. NEC 230.70B
 6. LABEL RISER 600A DP PANEL TO BE RATED FOR SERVICE
 ENTRANCE.
 7. PLEASE LABEL THE KITCHEN RECEPTACLE OUTLET WITHIN
 6FT OF SINK TO BE GFCI PROTECTED. NEC 210.8B5
 8. CLARIFY IF THE TRASH COMPACTOR IS BEING FED FROM
 THIS SERVICE. FBC 107.3
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-03-15 Cont ID  
Sent By   Date 2016-03-15 Time   Rev Time  
Received By scaldero Date 2016-03-15 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-12-14 Cont ID  
Sent By scaldero Date 2016-12-14 Time 15:36 Rev Time 0.00
Received By scaldero Date 2016-12-14 Time 15:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By scaldero Date 2016-04-07 Time 14:36 Rev Time 0.00
Received By scaldero Date 2016-04-07 Time 10:22 Sent To  
Notes
2016-04-07 14:36:35PERMIT # 16020377
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW
 APPROVED PROVISO:
  
 1) NO CORRECTIONS MADE ON THIS SHEET. CORRECTION AND
 COMPLIANCE WILL BE VERIFIED IN THE FIELD -- SHEET
 A2.00R - THE DOOR LEADING INTO THE RESTROOMS VESTIBULE
 AND THE DOOR FOR THE JANITOR'S CLOSET OPEN INTO
 EACHOTHER. CHANGE THE SWING DIRECTION FOR ONE OF THE
 TWO DOORS.
 NOTE: ALLOWABLE TRAVEL DISTANCE FOR A NON-SPRINKLERED
 BUILDING IS 200 FEET. NOTE ON SHEET INCORRECTLY STATES
 250 FEET.
  
 2) NO CORRECTIONS MADE ON THIS SHEET. COMPLIANCE WILL
 BE VERIFIED IN THE FIELD. - - SHEET A3.03R - STRUCTURES
 WITH LIGHT FRAME FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE
 IDENTIFIED WITH A SIGN AFFIXED TO THE BUILDING. THE
 SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE AND
 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE COLOR
 AND BEAR THE APPROPRIATE LETTER R/F/RF DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By scaldero Date 2016-03-03 Time 10:33 Rev Time 0.00
Received By scaldero Date 2016-03-03 Time 09:34 Sent To  
Notes
2016-03-03 10:33:11PERMIT # 16020377
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2009. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 2) SHEET A2.00R - THE DOOR LEADING INTO THE RESTROOMS
 VESTIBULE AND THE DOOR FOR THE JANITOR'S CLOSET OPEN
 INTO EACHOTHER. CHANGE THE SWING DIRECTION FOR ONE OF
 THE TWO DOORS.
  
 3) SHEET A3.03R - STRUCTURES WITH LIGHT FRAME
 FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE IDENTIFIED WITH
 A SIGN AFFIXED TO THE BUILDING. THE SIGN SHALL FEATURE
 A MALTESE CROSS 8-INCHES WIDE AND 8-INCHES TALL AND BE
 OF A BRIGHT RED REFLECTIVE COLOR AND BEAR THE
 APPROPRIATE LETTER R/F/RF DESIGNATION PER FLORIDA
 STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 4) REVIEW AND RESPOND TO ALL PLAN REVIEWER COMMENTS AND
 MAKE CORRECTIONS AS NEEDED; TO INCLUDE BUILDING,
 ELECTRICAL, MECHANICAL, ETC.
  
 GENERAL NOTE: SHEET A2.00R INDICATES THAT FIVE (5)
 EXTINGUISHERS, SIZE 4A 30BC, ARE TO BE PROVIDED. THE
 REQUIRED SIZE IS 2A 10BC. YOU ARE WELCOMED TO PROVIDE
 LARGER ONES, SUCH AS A 4A 30BC, BUT IT IS NOT REQUIRED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-01-04 Cont ID  
Sent By jwitmer Date 2017-01-04 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2017-01-03 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2016-12-30 Cont ID  
Sent By lmarchan Date 2016-12-30 Time 08:36 Rev Time 0.00
Received By lmarchan Date 2016-12-12 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-09-20 Cont ID  
Sent By lmarchan Date 2016-09-20 Time 14:26 Rev Time 0.00
Received By lmarchan Date 2016-08-30 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-06-07 Cont ID  
Sent By lmarchan Date 2016-06-07 Time 09:36 Rev Time 0.00
Received By lmarchan Date 2016-05-18 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2016-04-22 Time 12:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-19 Cont ID  
Sent By jwitmer Date 2016-04-19 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2016-04-01 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-15 Cont ID  
Sent By lmarchan Date 2016-03-15 Time 13:23 Rev Time 0.00
Received By lmarchan Date 2016-02-16 Time 12:10 Sent To  
Notes
2016-02-18 09:30:17ELECT 2/18 EMAIL TO CAROLINE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 7 Status P Date 2016-12-28 Cont ID  
Sent By jwitmer Date 2016-12-28 Time 07:21 Rev Time 0.00
Received By jwitmer Date 2016-12-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status F Date 2016-12-14 Cont ID  
Sent By jwitmer Date 2016-12-14 Time 07:19 Rev Time 0.00
Received By jwitmer Date 2016-12-14 Time 07:18 Sent To  
Notes
2016-12-14 07:19:16IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2016-09-20 Cont ID  
Sent By jwitmer Date 2016-09-20 Time 14:04 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2016-09-20 14:04:53IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2016-06-07 Cont ID  
Sent By jwitmer Date 2016-06-07 Time   Rev Time 0.00
Received By jwitmer Date 2016-06-07 Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-06-07 Cont ID  
Sent By   Date 2016-06-07 Time   Rev Time 0.00
Received By   Date 2016-06-07 Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-06-07 Cont ID  
Sent By   Date 2016-06-07 Time   Rev Time 0.00
Received By   Date 2016-06-07 Time   Sent To  
Notes
2016-06-07 08:39:10IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By jwitmer Date 2016-02-17 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2016-02-17 Time 15:49 Sent To  
Notes
2016-02-17 15:50:27BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 17:13 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 17:13 Sent To  
Notes
2016-12-27 17:18:46DIGITAL SIGNATURE ON THE NEW M1 SHEET
 VERIFIED/CCOLE/12/27/16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-06 Cont ID  
Sent By ccole Date 2016-05-06 Time 12:12 Rev Time 0.00
Received By ccole Date 2016-05-06 Time 12:12 Sent To  
Notes
2016-05-06 12:14:44MECHANICAL PROVISO:
 5/6/16
  
 1) SHEET M3 MUST BE DIGITALLY SIGNED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-11 Cont ID  
Sent By ccole Date 2016-04-11 Time 13:49 Rev Time 0.00
Received By ccole Date 2016-04-08 Time 15:49 Sent To  
Notes
2016-04-11 14:09:522ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020377
 4/11/16
  
 1) THE REVISED ENERGY CALCULATIONS WERE NOT UPLOADED
 FOR REVIEW.
 2) SHEET M1: DUCT SIZES NOT SHOWN FOR BRANCH RETURNS AT
 THE YOGA ROOM, KIDS ROOM, AND FITNESS ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-26 Cont ID  
Sent By ccole Date 2016-02-26 Time 07:35 Rev Time 0.00
Received By ccole Date 2016-02-26 Time 07:35 Sent To  
Notes
2016-02-26 08:12:161ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020377
 2/26/16
  
 1) SHEETS M1 & M2: THE VENTILATION SCHEDULE INDICATES
 342 CFM O/A FOR THE HEALTH CLUB/WEIGHT ROOM, HOWEVER
 AH/CU-1 SUPPLYING THAT AREA IS ONLY PROVIDING 200 CFM
 O/A AIR PER THE SCHEDULE. THERE IS ONE 350 CFM DIFFUSER
 FROM AH/CU-2 SUPPLYING THE AREA BUT IT DOES NOT APPEAR
 THE PERCENTAGE OF O/A FROM THAT DIFFUSER WOULD MAKE UP
 THE DIFFERENCE.
 2) M1 & M2: PLEASE CLARIFY WHY AH/CU- 2, 4, & 5 SHOWN
 IN THE AC SCHEDULE TO BE 3.5-TON SYSTEMS ARE ONLY
 PROVIDING APPROXIMATELY 2/3 (800 CFM EACH) OF THEIR
 RESPECTIVE 1100 CFM SUPPLY AIR CAPACITIES. PLEASE NOTE
 THAT THE 3-TON UNITS WILL SUPPLY UP TO 1000 CFM. IT
 APPEARS THAT THE 3.5 TON SYSTEMS MAY BE OVERSIZED.
 3) THE COMPLIANCE DATA FOR THE AC SYSTEMS LISTED IN THE
 SUBMITTED ENERGY CONSERVATION FORM CONFLICTS WITH THE
 AC EQUIPMENT SCHEDULE. THE FORM LISTS SYSTEM 1 AT 13
 SEER/ HOWEVER THE SCHEDULE INDICATES 14 SEER, FORM
 LISTS SYSTEM 5 AS BOTH THE 42,000 CAPACITY SYSTEM AND A
 6000 CAPACITY SYSTEM EACH AT 13 SEER. THE 6000 APPEARS
 TO BE A TYPO AND SHOULD BE CORRECTED TO 60,000. THE
 SCHEDULE LISTS THE 60,000 SYSTEM AT 13.25 SEER, AND
 LISTS 4- 46,200 CAPACITY SYSTEMS AT 14 SEER. PLEASE
 CORRECT ALL THESE CONFLICTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-12-29 Cont ID  
Sent By gjohnson Date 2016-12-29 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2016-12-29 Time 16:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-19 Cont ID  
Sent By tklarge Date 2016-04-19 Time 05:28 Rev Time 0.00
Received By tklarge Date 2016-04-19 Time 05:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-27 Cont ID  
Sent By tklarge Date 2016-02-27 Time 05:19 Rev Time 0.00
Received By tklarge Date 2016-02-27 Time 03:50 Sent To  
Notes
2016-02-27 05:19:391) AS DRAWN, THE SANITARY RISER FOR TOILET ROOMS #118 &
 #119 DOES NOT COMPLY WITH THE 2014 FPC SEC. 912.1. ONLY
 THE TYPE AND NUMBER OF FIXTURES IN THE BATHROOM GROUP
 SHALL CONNECT TO THE HORIZONTAL WET VENT (SEE THE
 DEFINITION OF "BATHROOM GROUP" IN THE DEFINITIONS). A
 MAXIMUM OF 2 WATER CLOSETS AND 2 LAVATORIES ARE
 PERMITTED ON THE WET VENT AND URINALS ARE NOT PERMITTED
 ON THE WET VENT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2016-09-20 Cont ID  
Sent By jwitmer Date 2016-09-20 Time 14:07 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2016-09-20 14:07:03ROOFING/ BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020377
 ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 5TH REVIEW
 DATE: TUES. SEPT. 20/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG
 ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED
 AMENITIES.
  
 1) ROOFING IS TO BE A DEFERRED SUBMITTAL TO BE
 SUBMITTED AFTER PERMIT ISSUANCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-04-19 Cont ID  
Sent By jwitmer Date 2016-04-19 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2016-04-19 Time 12:41 Sent To  
Notes
2016-04-19 12:43:46ROOFING APPROVAL DEFERRED SUBMITTAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By jwitmer Date 2016-02-17 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2016-02-17 Time 15:50 Sent To  
Notes
2016-02-17 15:52:37ROOFING: NO PRODUCT APPROVALS WERE SUBMITTED IN THIS
 ROUND OF REVIEWS.
 1) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED. IF SO RAS 117
 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT
 OR ENGINEER.
  
 2) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2017-01-04 Cont ID  
Sent By jwitmer Date 2017-01-04 Time 09:36 Rev Time 0.00
Received By jwitmer Date 2017-01-04 Time 08:46 Sent To  
Notes
2017-01-04 09:37:13REVIEWED THE MISSING SIGNATURES ON P3, M3, M4 & E3, ALL
 OK TO ISSUE. JW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2016-12-29 Cont ID  
Sent By gjohnson Date 2016-12-29 Time 16:22 Rev Time 0.00
Received By gjohnson Date 2016-12-29 Time 16:22 Sent To  
Notes
2016-12-29 16:22:4912/29/16
  
 P3, M3, M4, CLUB E3 ARE MISSING DIGITAL SIGNATURES
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
2016-12-14 07:22:0912/14/2016
 BUILDING REVIEW ARCHITECTURAL AND STRUCTURAL SHEETS NOT
 SIGNED AND SEALED:
 A0.01R
 A1.01
 A2.02R
 A4.02R
 A6.01R
 A8.01R
 A8.02R
 A8.03R
 S2
 S4
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2016-09-20 Cont ID  
Sent By jwitmer Date 2016-09-20 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2016-09-20 Time 14:22 Sent To  
Notes
2016-09-20 14:21:31BUILDING REVIEW # 5
 SHEETS NOT ELECTRONICALLY SIGNED AND SEALED
 A1.01
 A2.00R
 A2.02R
 A3.02R
 A3.03R
 A4.02R
 A6.01R
 A8.01R
 A8.02R
 A8.03R
 S1
 S2
 S3
 S4
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-05-13 Cont ID  
Sent By jwitmer Date 2016-05-13 Time   Rev Time 0.00
Received By jwitmer Date 2016-05-13 Time   Sent To  
Notes
2016-05-13 13:54:16) BEFORE PERMIT ISSUANCE CAN OCCUR ONE SET OF SIGNED
 AND SEALED DOCUMENTS (PLANS, SOILS REPORTS, & ENERGY
 CALCULATIONS) WILL BE SUBMITTED TO THE BUILDING
 DEPARTMENT FOR THE RECORD RETENTION PROGRAM AND
 REVIEWED WITH THE ELECTRONIC PLANS FOR ACCURACY AND
 CODE COMPLIANCE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-04-19 Cont ID  
Sent By jwitmer Date 2016-04-19 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2016-04-19 Time   Sent To  
Notes
2016-04-19 13:39:13SIGNATURE PAGE
 W. P. B. PERMIT: 16020377
 ADD: 7130 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG.
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. APRIL 19/2016
 ACTION: DENIED
  
 1) NEITHER THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL
 SHEETS HAVE ELECTRONIC SIGNATURES. THE CITY NO LONGER
 ACCEPTS THE PEDDS SIGNATURE, 61G15-23.005 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO SEAL ENGINEERING WORK SHALL HAVE THEIR
 IDENTITY AUTHENTICATED BY A CERTIFICATION AUTHORITY AND
 SHALL ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT;
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE MEP SHEETS THAT ARE DIGITALLY SIGNED BY RANDALL
 STOFFER DO NOT HAVE THE SIGNATURE LINKED TO BE ABLE OF
 VERIFICATION.
  
 3) THE ENERGY GAUGE CHECK LIST DIGITALLY SIGNED BY
 RANDALL STOFFER IS VALID ELECTRONIC DIGITAL SIGNATURE.

Review Stop Z ZONING
Rev No 5 Status P Date 2016-09-02 Cont ID  
Sent By ajones Date 2016-09-02 Time 12:01 Rev Time 0.00
Received By ajones Date 2016-09-02 Time 12:01 Sent To  
Notes
2016-09-02 14:15:49"PROVISOS:
 1.) APPLICANT SHALL OBTAIN A ROW PERMIT FROM THE PALM
 BEACH COUNTY DEPARTMENT OF ENGINEERING AND PUBLIC WORKS
 FOR THE ACCESS POINT ON SKEES RD. PRIOR TO FIRST
 INSPECTION.
 2.) ALL OTHER CONDITIONS OF APPROVAL IN RESOLUTION NO.
 322-15 REMAIN IN EFFECT."
  

Review Stop Z ZONING
Rev No 4 Status F Date 2016-05-26 Cont ID  
Sent By llouie Date 2016-05-26 Time 16:14 Rev Time 0.00
Received By llouie Date 2016-05-26 Time 16:14 Sent To  
Notes
2016-05-26 16:14:48** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON
 THE PLANS WHERE APPLICABLE:
  
 1.) RESOLUTION NO. 322-15, APPROVING THE OKEECHOBEE
 COMMONS RESIDENTIAL DSI PROJECT, REQUIRES THAT CERTAIN
 CONDITIONS ARE MET PRIOR TO THE APPROVAL OF ANY
 BUILDING PERMIT BY THE ZONING DIVISION. PLEASE PROVIDE
 ANY DOCUMENTATION TO THE DEVELOPMENT SERVICES
 DEPARTMENT-PLANNING DIVISION VERIFYING THAT THE
 CONDITIONS HAVE BEEN MET. [2/10/16, 4/7/16, 4/27/16
 REPEAT COMMENT]
  
 2.) ANY CHANGES TO THE SITE PLAN WILL REQUIRE AN
 AMENDMENT TO THE DSI. [4/7/16 AND 4/27/16 REPEAT
 COMMENT]
  
 3.) PROPOSED A/C UNITS ON THE NORTH SIDE OF THE
 RECREATION/LEASING BUILDING SHALL BE SCREENED FROM VIEW
 WITH LANDSCAPING. [4/7/16 AND 4/27/16 REPEAT COMMENT]
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status F Date 2016-04-27 Cont ID  
Sent By llouie Date 2016-04-27 Time   Rev Time 0.00
Received By llouie Date 2016-04-27 Time   Sent To  
Notes
2016-04-27 16:59:27** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON
 THE PLANS WHERE APPLICABLE:
  
 1.) RESOLUTION NO. 322-15, APPROVING THE OKEECHOBEE
 COMMONS RESIDENTIAL DSI PROJECT, REQUIRES THAT CERTAIN
 CONDITIONS ARE MET PRIOR TO THE APPROVAL OF ANY
 BUILDING PERMIT BY THE ZONING DIVISION. PLEASE PROVIDE
 ANY DOCUMENTATION TO THE DEVELOPMENT SERVICES
 DEPARTMENT-PLANNING DIVISION VERIFYING THAT THE
 CONDITIONS HAVE BEEN MET. [2/10/16, 4/7/16 REPEAT
 COMMENT]
  
 2.) ANY CHANGES TO THE SITE PLAN WILL REQUIRE AN
 AMENDMENT TO THE DSI. [4/7/16 REPEAT COMMENT]
  
 3.) PROPOSED A/C UNITS ON THE NORTH SIDE OF THE
 RECREATION/LEASING BUILDING SHALL BE SCREENED FROM VIEW
 WITH LANDSCAPING. [4/7/16 REPEAT COMMENT]
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2016-04-07 Cont ID  
Sent By llouie Date 2016-04-07 Time   Rev Time 0.00
Received By llouie Date 2016-04-07 Time   Sent To  
Notes
2016-04-07 14:54:15** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING AND/OR
 ON THE PLANS WHERE APPLICABLE:
  
 1.) RESOLUTION NO. 322-15, APPROVING THE OKEECHOBEE
 COMMONS RESIDENTIAL DSI PROJECT, REQUIRES THAT CERTAIN
 CONDITIONS ARE MET PRIOR TO THE APPROVAL OF ANY
 BUILDING PERMIT BY THE ZONING DIVISION. PLEASE PROVIDE
 ANY DOCUMENTATION TO THE DEVELOPMENT SERVICES
 DEPARTMENT-PLANNING DIVISION VERIFYING THAT THE
 CONDITIONS HAVE BEEN MET. [2/10/16 REPEAT COMMENT]
  
 2.) ANY CHANGES TO THE SITE PLAN WILL REQUIRE AN
 AMENDMENT TO THE DSI.
  
 3.) PROPOSED A/C UNITS ON THE NORTH SIDE OF THE
 RECREATION/LEASING BUILDING SHALL BE SCREENED FROM VIEW
 WITH LANDSCAPING.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By llouie Date 2016-03-01 Time 08:44 Rev Time 0.00
Received By llouie Date 2016-03-01 Time 08:44 Sent To  
Notes
2016-03-01 08:53:35** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING AND/OR
 ON THE PLANS WHERE APPLICABLE:
  
 1.) RESOLUTION NO. 322-15, APPROVING THE OKEECHOBEE
 COMMONS RESIDENTIAL DSI PROJECT, REQUIRES THAT CERTAIN
 CONDITIONS ARE MET PRIOR TO THE APPROVAL OF ANY
 BUILDING PERMIT BY THE ZONING DIVISION. PLEASE PROVIDE
 ANY DOCUMENTATION TO THE DEVELOPMENT SERVICES
 DEPARTMENT-PLANNING DIVISION VERIFYING THAT THE
 CONDITIONS HAVE BEEN MET.
  
 2.) CHANGES IN BUILDING FOOTPRINT DETECTED. ANY CHANGES
 TO THE BUILDING FOOTPRINT SHOULD BE REFLECTED IN THE
 APPLICATION FOR A MINOR DSI AMENDMENT.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.