| 2016-02-17 15:49:33 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020377 |
| | ADD: 7000 OKEECHOBEE BLVD. / LEASING & RECREATION BLDG. |
| | CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 17/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS FOR THE LEASING/ RECREATION BLDG |
| | ONLYI, NOT FOR THE SITE PLAN, OR ANY ASSOCIATED |
| | AMENITIES. |
| | |
| | 1) THE PERMIT APPLICATION VALUE OF $9,000,000.00 |
| | DOLLARS IS ACTUALLY HIGH IN RELATION TO THE AUGUST 2015 |
| | ICC VALUATION TABLES. THE MEP AND ROOFING PERMITS, ARE |
| | SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT |
| | ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE |
| | OF THE BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED |
| | PERMITS. PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS |
| | FOR THE BUILDING, SUBMIT A LIST OF PERMITS AND |
| | BREAK-OUT THE VALUE FROM THE TOTAL COST TO DETERMINE |
| | THE FINAL VALUATION OF THE BUILDING PERMIT. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 2) PLEASE NOTE THIS BUILDING DOES NOT REQUIRE A |
| | THRESHOLD OR A RESIDENT INSPECTOR. PLEASE CONFIRM THAT |
| | THE CONTRACTOR IS GOING TO CALL IN INSPECTIONS FOR THE |
| | CITY INSPECTORS WILL BE DOING THE STRUCTURAL |
| | INSPECTIONS FOR THIS BUILDING OR WILL THE THRESHOLD |
| | INSPECTOR ALSO COMPLETE THE STRUCTURAL INSPECTIONS FOR |
| | THIS BUILDING AS WELL. |
| | |
| | THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING |
| | FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | A INTERVIEW MAYBE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | |
| | 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | |
| | 2G)NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE |
| | CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT |
| | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF |
| | JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6 |
| | THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) PLEASE NOTE THE SITE ADDRESS HAS BEEN PROVIDED AS |
| | 7000 OKEECHOBEE BLVD. PLEASE CONTACT THE CITY?S |
| | ADDRESSING SPECIALIST FOR ADDRESSING CONCERNS, EITHER |
| | STREET NAMES OR NUMERICAL ADDRESSES TO IDENTIFY EACH |
| | BUILDING. CITY MUNI CODE SEC.78-6 (1-7). |
| | (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE |
| | ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION |
| | OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR |
| | PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE |
| | READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR |
| | TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE |
| | ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE |
| | BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE |
| | HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE |
| | NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF |
| | NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE, |
| | SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE |
| | CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS |
| | WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL, |
| | INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A |
| | SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS |
| | SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL |
| | ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL |
| | ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE |
| | POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH |
| | A COMMON EXTERIOR ENTRANCE. |
| | (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE |
| | RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL |
| | DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE |
| | DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ |
| | INFORMATION TECHNOLOGY |
| | TEL: 561-494-1040 |
| | |
| | 4) MISSING FROM THE SUPPORTING DOCUMENT FOLDER IS |
| | COMPLIANCE WITH: 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 5A) MISSING FROM THE SUPPORTING DOCUMENT FOLDER IS A |
| | SURVEY. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE |
| | |
| | 5B) MISSING FROM THE PLANS IS A SITE PLAN THAT SHOWS |
| | THE ASSUMED PROPERTY LINE BETWEEN THE VARIOUS BUILDINGS |
| | WITH THE PERCENTAGE OF ALLOWABLE OPENINGS. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | SURVEY / FLOOD ZONE/ ASSUMED PROPERTY LINE |
| | |
| | 6) UNDER THE 2014 ENERGY CODE THIS BUILDING IS USING |
| | ASHRAE 90 FORMS FOR CODE COMPLIANCE. THE INPUT DATA |
| | REPORT ON PAGES 2 & 3 INDICATES THE USE OF ? INCH ISO |
| | BETWEEN ? INCH FURRING. PAGE 7 UNDER THE MATERIALS USED |
| | ALSO INDICATES THE USE OF 0.75 INCH ISO BETWEEN FURRING |
| | 24 INCHES ON CENTER. WHERE AS SHEET A.302R INDICATES |
| | R4.1 AL-FOIL INSULATION BETWEEN 1 X3 PT FURRING STRIPS. |
| | NOTE THERE IS A DISCREPANCY BETWEEN THE ENERGY |
| | CALCULATIONS AND THE WALL INSULATION INDICATED ON THE |
| | PLANS. |
| | |
| | 7A) SHEET A2.00 R IS THE LIFE SAFETY PLAN FOR THE |
| | LEASING AND RECREATION CENTER. THE SHEET INDICATES |
| | UNDER THE OCCUPANCY TYPE AN A3 FOR THE RECREATION |
| | CENTER. THE LEASING AREA OF THE BUILDING IS |
| | APPROXIMATELY 936 SQ. FT. OR 0.18 % OF THE FLOOR PLATE |
| | MAKING THIS A MIXED USE OCCUPANCY BETWEEN AN A3 |
| | OCCUPANCY AND A BUSINESS OCCUPANCY. IN THE 2014 FBC-B |
| | TABLE 508.4 BETWEEN AN A3 AND BUSINESS OCCUPANCY |
| | REQUIRES 2 HOUR SEPARATION FOR NON-SPRINKLERED |
| | BUILDINGS. THE DESIGNER OF RECORD HAS NOT DECLARED IF |
| | THE PLANS WERE DEVELOPED AS SEPARATION OF |
| | OCCUPANCIES(508.2.4) OR NON-SEPARATED OCCUPANCIES |
| | (508.3). |
| | |
| | 7B) THE RECREATION AND LEASING BUILDING WILL NOT ONLY |
| | NEED TO MEET THE REQUIREMENTS OF FAIR HOUSING BUT THE |
| | FBC-ACCESSIBILITY CODE AS WELL. THE FITNESS ROOM THE |
| | EXERCISE MACHINE AND EQUIPMENT WILL NEED TO MEET THE |
| | REQUIREMENTS OF FBC-ACCESSIBILITY CODE 1004.1. |
| | |
| | 7C) THIS SHEET SHOWS A KITCHEN/ BREAK ROOM. THE PLANS |
| | DO NOTE THAT THE SINK WILL BE LOCATED IN THE COUNTER |
| | TOP AT 34 INCHES ABOVE FLOOR LEVEL. THERE ARE NO OTHER |
| | DETAILS TO SHOW COMPLIANCE WITH FAIR HOUSING NOR THE |
| | FLORIDA ACCESSIBILITY CODE. |
| | |
| | 7D) THERE ARE NO ELEVATIONS OF THE BREAK ROOM. THERE |
| | ARE CONCERNS IF THERE WILL BE A MICROWAVE AND THE |
| | PLACEMENT OF THE UNIT FOR COMPLIANCE WITH REACH RANGES |
| | AND OPERABLE PARTS UNDER BOTH THE FAIR HOUSING AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | REACH RANGES UNDER 308. |
| | OPERABLE PARTS 309. |
| | |
| | 8A) SHEET A3.01R THE RIGHT SIDE OR ELEVATION SHOWS THE |
| | WINDOWS AND DOORS AS PROTECTED, WINDOWS A 1 HOUR FIRE |
| | RATING AND THE DOORS 45 MINUTES. THE 2014 FBC-B TABLE |
| | 716.5 FOR EXTERIOR WALLS THAT REQUIRE A 1 HOUR FIRE |
| | RATING THE OPENING PROTECTIVE WILL ONLY REQUIRE 45 |
| | MINUTE PROTECTIVE. PLEASE INDICATE ON THE WINDOWS HOW |
| | THIS WILL BE ACCOMPLISHED, FIRE SHUTTERS, FIRE RATED |
| | GLAZING AND FRAME? ? PLEASE ALSO BE AWARE THAT THERE |
| | ARE VERY FEW WINDOWS THAT ARE TESTED FOR A FIRE RATING |
| | AS WELL AS LARGE MISSILE IMPACT TESTING. |
| | |
| | 8B) SHEET A3.01R & A3.02R BOTH INDICATE THE USE OF |
| | CULTURED STONE. THERE IS A NOTE ON THE PLANS STONE |
| | VENEER BY CULTURED STONE LEDGE STONE VENEER TYPE. THIS |
| | PRODUCT HAS CODE COMPLIANCE EVALUATION AND LISTING, |
| | TEST ICC-ESESR-1364. PLEASE SUBMIT REPORT TO VERIFY |
| | COMPLIANCE WITH EITHER 1405.7 STONE VENEERS/ ANCHORED |
| | OR 1405.10 ADHERED MASONRY VENEERS. TO BE REVIEWED BY |
| | THE DESIGNER OF RECORD BEFORE BEING SUBMITTED TO THE |
| | BUILDING DEPARTMENT. |
| | |
| | 9) SHEET S-2 REC BUILDING NOTES. |
| | 9A) THE DESIGN PARAMETERS LIST THIS CONSTRUCTION AS |
| | BUILDING TYPE VB. WHEREAS THE LIFE SAFETY SHEET A2.00 |
| | INDICATES THE BUILDING TYPE IIIB. DISCREPANCY IN PLANS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 9B) THE DESIGN PARAMETERS AND ASSUMPTIONS LIST THE |
| | OCCUPANCY CLASSIFICATION AS R-3. NOTE THIS IS A MIXED |
| | USE OCCUPANCY A3/B. |
| | |
| | 9C) NO WIND LOAD CHART HAS BEEN PROVIDED FOR ZONES |
| | 1,2,3, 4 & 5. PLEASE PROVIDE THE POSITIVE AND NEGATIVE |
| | PRESSURES IN VASD SINCE THE PRODUCT APPROVALS ARE GIVEN |
| | IN VASD. PLEASE PROVIDE CALCULATIONS (STATING VASD) FOR |
| | 10 SQ. FT., 20 SQ. FT., 50 SQ. FT. & 100 SQ. FT. 2014 |
| | FBC-B 1603.1.4 WIND DESIGN DATA, WIND DESIGN PRESSURES. |
| | |
| | 10A) MISSING FROM THE SUBMITTED DOCUMENT FILE WERE |
| | PRODUCT APPROVAL DOCUMENTS. EITHER THE DESIGNER OF |
| | RECORD OR CONTRACTOR CAN SUBMIT THE PRODUCT APPROVAL |
| | DOCUMENTS OR ELECT TO HAVE THESE DOCUMENTS BE |
| | CONSIDERED AS A DEFERRED SUBMITTAL. IF THEY PREFER THE |
| | PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS THEY MUST |
| | STATE SO IN THE RESPONSE NARRATIVE. |
| | |
| | 10B) COMPONENTS & CLADDING. 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING |
| | BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 10D) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIXE. |
| | |
| | 10E) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| | ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| | ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| | IF ENHANCED FASTENING IS ALLOWED. IF SO RAS 117 |
| | CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT |
| | OR ENGINEER. |
| | |
| | 10F) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM |
| | THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014 |
| | FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | |
| | 11A) SHEET A3.02 INDICATES A AWNING DETAIL FOUND ON |
| | SHEET A8.01, THERE IS NO SUCH SHEET IN THIS SET OF |
| | DRAWINGS. PLEASE PROVIDE DOCUMENTATION AS TO IS THIS A |
| | FABRIC AWNING OR A RIGID FIXED AWNING? PLEASE PROVIDE |
| | TO WHICH DESIGN CRITERIA THE AWNING IS TO BE DESIGNED |
| | TOO? |
| | 2014 FBC-B 3105.4 DESIGN. |
| | 2014 FBC-B 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. |
| | |
| | 11B) 2014 FBC-B 3105.3.3.1 FABRIC USED FOR AWNINGS OR |
| | FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION |
| | PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD |
| | INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 84 OR UL 723. |
| | |
| | 12) SHEET S-4 DETAIL C SHOWS A DOUBLE LEDGER TO BE |
| | ATTACHED TO THE BLOCK WALL WITH FILED CELLS. |
| | 12A) THE PLANS DO NOT PROVIDE WHAT SIZE OF LUMBER THE |
| | LEDGER SHOULD BE NOR THE TYPE OF WOOD, SPECIES, & GRADE |
| | ? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 12B) THIS SAME DETAIL INDICATES THE LEDGER BE FASTENED |
| | TO THE FILED CELL BLOCK WALL, BUT MISSING THE TYPE OF |
| | ANCHOR, DIAMETER & LENGTH, AND AT WHAT CENTER TO CENTER |
| | ARE THEY TO BE PLACED. THE PLANS ALSO FAIL TO INDICATE |
| | THE LOCATION OF THE ANCHOR IN REGARDS TO THE FRAMING |
| | MEMBER, UPPER 1/3RD, CENTERED OR IN THE LOWER 1/3RD OR |
| | STAGGERED? ADDITIONAL INFORMATION IS REQUIRED. |
| | 107.2.1.3. |
| | |
| | 12C) THE TYPICAL CUT SECTION THROUGH A 1 STORY |
| | STRUCTURE LOWER RIGHT CORNER OF THE SHEET INDICATES |
| | 19/32 EXPOSURE1, EXTERIOR GRADE PLYWOOD |
| | SHEATHING(OPTION OSB). |
| | PLEASE REVIEW 2014 FLORIDA BUILDING CODE W 2014 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |