Plan Review Details - Permit 16020331
Plan Review Stops For Permit 16020331
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-02 Cont ID  
Sent By skennedy Date 2016-03-02 Time 12:34 Rev Time 0.00
Received By skennedy Date 2016-03-02 Time 12:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-19 Cont ID  
Sent By cthroop Date 2016-02-19 Time 13:31 Rev Time 0.00
Received By cthroop Date 2016-02-19 Time 13:31 Sent To  
Notes
2016-02-19 13:35:18CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE STRUCTURAL DETAIL FOR 1" ALUMINUM SUPPORTS,
 WELDS, BOLTS AND ATTACHMENT TO CEILING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-02 Cont ID  
Sent By vperez Date 2016-03-02 Time 05:54 Rev Time 0.00
Received By vperez Date 2016-03-02 Time 05:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-16 Cont ID  
Sent By vperez Date 2016-02-16 Time 07:14 Rev Time 0.00
Received By vperez Date 2016-02-16 Time 07:14 Sent To  
Notes
2016-02-16 07:16:25INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS ZONING COMMENTS FOR ELECTRICAL
 APPROVAL
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-02 Cont ID  
Sent By skennedy Date 2016-03-02 Time 12:34 Rev Time 0.00
Received By skennedy Date 2016-02-23 Time 12:48 Sent To  
Notes
2016-03-02 05:55:213/02 TO CAROLINE
2016-02-23 12:49:22ROUTED TO ZONING VIA ESCHNEIDER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-19 Cont ID  
Sent By cthroop Date 2016-02-19 Time 13:31 Rev Time 0.00
Received By cthroop Date 2016-02-16 Time 07:16 Sent To  
Notes
2016-02-16 07:17:21TO CAROLINE/LAURA
2016-02-09 15:50:40ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-01 Cont ID  
Sent By eschneid Date 2016-03-01 Time 17:39 Rev Time 0.75
Received By eschneid Date 2016-03-01 Time 17:39 Sent To E
Notes
2016-03-01 17:39:49NORTH ELEVATION SIGN
  
 ALLOWED SIGN AREA ? 125 SQ. FT.
 PROPOSED SIGN AREA - 74 SQ. FT.
  
 WEST ELEVATION SIGNS
  
 ALLOWED SIGN AREA - 70 SQ. FT.
 PROPOSED WALL SIGN AREA ? 51 SQ. FT.
 PROPOSED HANGING SIGNS (2) AREA - 9 SQ. FT. PER SIGN =
 18 SQ. FT. TOTAL.
 TOTAL SIGN AREA ? 69 SQ. FT.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By eschneid Date 2016-02-12 Time 09:57 Rev Time 3.00
Received By eschneid Date 2016-02-10 Time 15:11 Sent To  
Notes
2016-02-12 15:07:41FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THE CITYPLACE MANAGEMENT APPROVAL STAMP IS REQUIRED
 ON THE PLANS.
  
 2) THE PERMIT DESCRIPTION IS FOR SIX SIGNS; HOWEVER,
 THERE ARE ONLY THREE SIGNS SHOWN ON THE ELEVATION
 DRAWINGS. PLEASE EXPLAIN.
  
 NORTH ELEVATION SIGN - PROPOSED TO BE MOUNTED IN THE
 DOORWAY OPENING.
  
 3) THIS IS NOT A DESIGNATED SIGN ZONE LOCATION IN THE
 CITYPLACE MASTER SIGN PLAN. A MINOR PLANNED DEVELOPMENT
 AMENDMENT NEEDS TO BE SUBMITTED TO AND APPROVED BY THE
 PLANNING DIVISION TO PERMIT THE PROPOSED SIGN TO HAVE
 AN ALTERNATE VERTICAL PLACEMENT OUTSIDE THE SIGN ZONE
 DEPICTED ON THE DRAWINGS APPROVED AS PART OF THE
 CITYPLACE MASTER SIGN PLAN.
  
 4) THE ELEVATION DRAWING FOR THE SIGN NOT VISIBLE FROM
 THE STREET IS REQUIRED SO STAFF MAY VERIFY IF IT IS IN
 A SIGN ZONE DEPICTED ON THE CITYPLACE MASTER SIGN ZONE.
 IF THE PHOTOSHOP DRAWING IS ACCURATE, THEN THIS SIGN IS
 ALSO OUTSIDE OF THE SIGN ZONE.
  
 5) THE CITYPLACE MASTER SIGN PLAN MEASURES SIGNAGE
 ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR
 EACH ONE LINEAR FOOT OF STORE FRONTAGE. PLEASE PROVIDE
 THE LINEAR FEET OF STORE FRONTAGE.
  
 6) THE CITYPLACE MASTER SIGN PLAN PROHIBITS INTERNALLY
 ILLUMINATED SIGNS WITHIN THE INTERIOR OF THE ARCADE.
  
 7) THE SIGN IS SHOWN AS 4.5 FEET ABOVE THE FINISHED
 FLOOR. THE SIGNS SHALL HAVE A MINIMUM OF EIGHT (8) FEET
 OF CLEARANCE.
  
 ALLOWED SIGN AREA - INFORMATION NOT PROVIDED
 PROPOSED SIGN AREA - 9 SQ. FT.
  
 WEST ELEVATION SIGNS - PROPOSED TO BE MOUNTED BETWEEN
 THE EXISTING COLUMNS
  
 8) ) THIS IS NOT A DESIGNATED SIGN ZONE LOCATION IN THE
 CITYPLACE MASTER SIGN PLAN. A MINOR PLANNED DEVELOPMENT
 AMENDMENT NEEDS TO BE SUBMITTED TO AND APPROVED BY THE
 PLANNING DIVISION TO PERMIT THE PROPOSED SIGNS TO BE
 LOCATED OUTSIDE OF THE HORIZONTAL AND VERTICAL LINE OF
 THE SIGN ZONE DEPICTED ON THE DRAWINGS APPROVED AS PART
 OF THE CITYPLACE MASTER SIGN PLAN.
  
 9) THE SIGN IS SHOWN AS 4.5 FEET ABOVE THE FINISHED
 FLOOR. THE SIGNS SHALL HAVE A MINIMUM OF EIGHT (8) FEET
 OF CLEARANCE TO BE CONSISTENT WITH THE OTHER SIGNAGE
 ALONG THIS FRONTAGE.
  
 10) THE PLANS SHOW THAT THE SIGNS WILL BE MOUNTED TO
 EXISTING SUPPORTS. THE BUILDING-OUT PLANS FOR THE BAY
 (15100011) SHOW NO SUPPORTS AT THESE LOCATIONS. PLEASE
 EXPLAIN.
  
 11) WHERE WILL THE WIRING GO AFTER IT IS IN THE
 HORIZONTAL TUBING?
  
 ALLOWED SIGN AREA - 70 SQ. FT.
 PROPOSED SIGN AREA - 9 SQ. FT. PER SIGN = 18 SQ. FT.
 TOTAL.
  
 THESE COMMENTS HAVE BEEN SENT TO CARLOS BERNAL @
 CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ 822-1446.