| 2016-02-10 17:03:34 | RESIDENTIAL (R3) STRUCTURAL REVISION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE; FBC 5TH EDITION (2014). |
| | |
| | 1- STRUCTURAL PLANS SUBMITTING ARE MISSING CONNECTORS |
| | SPECIFICATIONS. CLEARLY SPECIFY THE CONNECTORS AT ALL |
| | FRAMING MEMBERS. SPECIFY THE CONNECTORS AT BOTH ENDS OF |
| | COLUMNS, WALL STUDS, BEAMS AND FLOOR JOISTS. SEC. |
| | R501.2 AND SEC. R601.2 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 2- ENGINEER TO PROVIDE COMPLETE DETAILS/SPECIFICATIONS |
| | SHOWING COMPLIANCE WITH THE PROTECTION OF THE WOOD |
| | FRAMING MEMBERS SHOWN ON FRAMING PLANS AND DETAILS |
| | SUBMITTED. SEE SEC. R317 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014) AND PROVIDE SUCH SPECIFICATIONS. |
| | |
| | 3- ENGINEER TO SPECIFY HOW MUCH EMBEDMENT IS REQUIRED |
| | FOR ALL BOLTS SPECIFIED ON DETAILS PROVIDED. SEC. R301 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- FOOTING DETAIL B/MF1: |
| | A) SPECIFY THE MINIMUM FOOTING DEPTH BELOW GRADE AS |
| | REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014) AND THE NUTTING ENGINEERS GEOTECHNICAL |
| | EXPLORATION REPORT SUBMITTED. |
| | |
| | B) SPECIFY THE MINIMUM CLEARANCE REQUIRED BETWEEN THE |
| | FINAL GRADE AND EXTERIOR WALL COVERING AS REQUIRED BY |
| | SEC. R318.7 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 5- PROVIDE COMPLETE WALL SECTION: PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS FOR THE WALL SHEATHING |
| | ATTACHMENT, FINISH MATERIALS ON BOTH SIDES (INTERIOR |
| | AND EXTERIOR), INSULATION, ETC. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 6- PROVIDE THE SIGNED AND SEALED SHORING DRAWINGS AND |
| | STEEL SHOP DRAWINGS FOR CONNECTORS AS SPECIFIED BY THE |
| | ENGINEER ON PLANS SUBMITTED. SUBMITTALS TO BE |
| | REVIEWED/APPROVED BY THE ENGINEER OF RECORD PRIOR TO |
| | SUBMITTAL TO THIS OFFICE. SEC. 107.3.4.2 CITY |
| | AMENDMENTS. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. NOTE: PROVIDE THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | ENGINEER TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO |
| | EACH SPECIFIED CONNECTOR. |
| | |
| | NOTE: PRODUCT APPROVALS FOR DOORS AND WINDOWS WILL BE |
| | REQUESTED WHEN-THE ARCHITECTURAL PLANS ARE SUBMITTED. |
| | |