| Notes |
| 2016-02-12 10:12:41 | THIS PLAN WAS REVIEWED AND PASSED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. THE PERMIT VALUE APPEARS TOO LOW FOR 6 TENTS AND | | | SHALL BE ADJUSTED TO REFLECT AN ACCURATE AMOUNT. | | | PROVIDE A COPY OF THE CONTRACT/INVOICE. | | | | | | 2. PROVIDE THE DESIGN/DRAWING/NOTE OF THE TIE DOWN FOR | | | SAFETY PER NFPA 25.2.3.4 & NFPA 101, 11.113.4 | | | | | | 3. FIRE EXTINGISHERS SHALL NOT BE TIE-WRAPED TO A FIXED | | | OBJECT. THE HANGER FOR THE FE CAN BE TIED BUT THE FE | | | SHALL REMAIN FREE TO REMOVE. | | | | | | 4. THE CERTIFICATE OF FLAME RESISTANCE SUBMITTED IS | | | DATED 10/3/89. PROVIDE A SAMPLE OF THE MATERAIL FOR | | | TESTING PER NPFA 25.2.2.1, 25.2.2.2 & NFPA 101, | | | 11.11.2.1, 11.11.2.2 OR PROVIDE A MORE RECENT | | | CERTIFICATE. | | | | | | | | | NEW CERTIFICATES PROVIDED 3/2/16.PML |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-02-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-02-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-02-09 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2016-02-09 13:39:35 | ROUTED TO TEMP TENT |
|
|
|