Plan Review Details - Permit 16020303
Plan Review Stops For Permit 16020303
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By cthroop Date 2016-05-04 Time 15:37 Rev Time 0.00
Received By cthroop Date 2016-05-04 Time 15:31 Sent To THRESHOLD
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-29 Cont ID  
Sent By cthroop Date 2016-02-29 Time 12:54 Rev Time 0.00
Received By cthroop Date 2016-02-25 Time 13:36 Sent To  
Notes
2016-02-29 13:08:551ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. THE REPORT OF A LIMITED GEOTECHNICAL EXPLORATION BY
 UNIVERSAL ENGINEERING SCIENCES REFERENCES THE PROPOSED
 TOWER TO BE 130 FT. IN HEIGHT. (SEE PG 2 OF REPORT).
 RE-ISSUE REPORT ADDRESSING THE PROPOSED 90 FT TOWER.
  
 2. SUBMIT APPLICATION FOR RESIDENT INSPECTOR PER CITY
 OF WEST PALM BEACH LOCAL AMENDMENTS SECTION 110.3.9
 (7).
  
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By vperez Date 2016-05-04 Time 15:04 Rev Time 0.00
Received By vperez Date 2016-05-04 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By vperez Date 2016-02-18 Time 08:37 Rev Time 0.00
Received By vperez Date 2016-02-18 Time 08:37 Sent To  
Notes
2016-02-18 08:38:13APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE SIZE OF THE SERVICE CONDUCTORS FOR
 THE NEW SERVICE SHOWN, FBC 107.3.5
 2. SHOW ACTUAL AIC CALCULATIONS FOR THE NEW SERVICE
 SHOWN. FBC 107.3.5
 3. PROVIDE PER FBC EC 405.7 FEEDER VOLTAGE DROP
 CALCULATIONS
 4. GENERAL NOTES TO INDICATE REQUIREMENTS OF FBC EC
 405.4 COMPLETION DOCUMENTS SEE VERBIAGE IN THE CODE. A
 NOTE WILL SUFFICE.
 5. CLARIFY AS THE RISER DIAGRAM REFLECTING THE ONE-LINE
 FOR THE NEW ELECTRICAL SERVICE DOES NOT HAVE CONDUCTOR
 SIZES; SIZE OF THE MCB, SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR AND SIZE OF THE FEEDER CONDUCTORS. PROVIDE
 ALL FOR A COMPLETE REVIEW OF ELECTRICAL SERVICE. NEC
 250.66, 310.15B16 FBC 107.3.5
 6. PROVIDE DATA SHEETS FOR ALL ELECTRICAL EQUIPMENT
 THAT IS PART OF THIS PROJECT.
 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-05 Cont ID  
Sent By cthroop Date 2016-05-05 Time 10:29 Rev Time 0.00
Received By cthroop Date 2016-04-25 Time 16:12 Sent To  
Notes
2016-04-25 16:12:39RESUB ROUTED TO JROACH VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-29 Cont ID  
Sent By cthroop Date 2016-02-29 Time 12:53 Rev Time 0.00
Received By cthroop Date 2016-02-09 Time 14:06 Sent To Z
Notes
2016-02-18 08:38:32TO CAROLINE 2/18

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By kconrad Date 2016-05-05 Time 09:38 Rev Time 0.00
Received By kconrad Date 2016-05-05 Time 09:38 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By jroach Date 2016-05-04 Time 08:58 Rev Time 0.00
Received By jroach Date 2016-05-03 Time 15:00 Sent To E
Notes
2016-05-04 08:58:53ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.04.2016
 PERMIT NO.: 16020303
 ADDRESS: 3410 ELECTRONICS WAY
 CONTRACTOR/CONTACT: CORNELIUS COX
 TELEPHONE NO.: 912.220.8296
 SCOPE OF REVIEW: NEW COMMUNICATIONS TOWER.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO FINAL INSPECTION, PERMIT APPLICATIONS FOR
 LANDSCAPE AND IRRIGATION NEED TO BE OBTAINED. EACH
 APPLICATION SHALL BE ACCOMPANIED WITH TWO (2) SETS OF
 PLANS AND A CERTIFIED COST ESTIMATE (MATERIALS +
 LABOR).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-16 Cont ID  
Sent By cthroop Date 2016-02-29 Time 12:54 Rev Time 0.00
Received By jroach Date 2016-02-16 Time 13:47 Sent To E
Notes
2016-02-16 13:48:01ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.16.2016
 PERMIT NO.: 16020303
 ADDRESS:3410 ELECTRONICS WAY
 CONTRACTOR/CONTACT: INFINITY CONSTRUCTION
 TELEPHONE NO.: 770.831.9801
 SCOPE OF REVIEW: INSTALLATION OF 90 FOOT MONOPOLE CELL
 TOWER.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY.
  
 2. PURSUANT TO THE FINAL ORDER FOR WIRELESS
 TELECOMMUNICATIONS FACILITIES (WCF) CASE NO. 15-05, AN
 UPDATED FALL ZONE LETTER SHALL BE PROVIDED FROM A
 REGISTERED PROFESSIONAL ENGINEERING SUPPORTING THAT THE
 FALL ZONE DOES MEET THE BREAKPOINT TECHNOLOGY PROPOSED
  
 3. PROPOSED LANDSCAPING SHALL BE SUBMITTED UNDER A
 SEPARATE LANDSCAPE PERMIT.
  
 4. PROPOSED IRRIGATION SHALL BE SUBMITTED UNDER A
 SEPARATE LANDSCAPE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved