Plan Review Details - Permit 16020245
Plan Review Stops For Permit 16020245
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By vperez Date 2016-03-07 Time 07:25 Rev Time 0.00
Received By vperez Date 2016-03-07 Time 07:25 Sent To  
Notes
2016-03-07 07:34:10INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES- BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE PROVIDE A COMPLETE PACKAGE REFLECTING THE
 GENERATOR INSTALLATION. SHOW ON ONE-LINE RISER; COMPLY
 WITH NEC ARTICLE 702 SIGNAGE REQUIREMENTS, ETC. SPECS
 ONLY NOT SUFFICIENT. FBC 107.3.5
 2.SEE ZONING COMMENTS.
 3.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER BELOW SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-07 Cont ID  
Sent By vperez Date 2016-03-07 Time 07:34 Rev Time 0.00
Received By vperez Date 2016-03-07 Time 07:34 Sent To  
Notes
2016-03-07 07:35:023/7 TO CAROLINE

Review Stop Z ZONING
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By ajones Date 2016-03-01 Time 17:46 Rev Time 0.00
Received By ajones Date 2016-03-01 Time 17:46 Sent To E
Notes
2016-03-01 17:48:043/1/16- FAILED NEED SITE PLAN OR SURVEY SHOWING
 LOCATION OF GENERATOR ON THE PRPERTY.
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]