Plan Review Details - Permit 16020199
Plan Review Stops For Permit 16020199
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2016-05-17 Cont ID  
Sent By shill Date 2016-05-17 Time 11:11 Rev Time 0.00
Received By shill Date 2016-05-17 Time 11:11 Sent To  
Notes
2016-05-17 11:12:02REPLAT IS IN PROCESS
  
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By shill Date 2016-04-04 Time 12:15 Rev Time 0.00
Received By shill Date 2016-04-04 Time 12:15 Sent To  
Notes
2016-04-04 12:16:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE BUILDING COMMENTS - THE ADDRESS FOR THIS JOB
 APPEARS TO BE ONLY ONE LOT OF SEVERAL FOR THIS PROJECT.
 PLEASE ADVISE; IS A RE-PLAT OR UNITY OF TITLE PENDING?
 FOR RECORD KEEPING PURPOSES, THE POLICY OF THIS
 DEPARTMENT IS THAT A SEPARATE PERMIT IS REQUIRED FOR
 EACH PARCEL. NOT ENOUGH INFORMATION HAS BEEN PROVIDED
 TO RESOLVE THIS ISSUE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-27 Cont ID  
Sent By shill Date 2016-05-27 Time 14:02 Rev Time 0.00
Received By shill Date 2016-05-27 Time 14:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-17 Cont ID  
Sent By shill Date 2016-05-17 Time 10:59 Rev Time 0.00
Received By shill Date 2016-05-17 Time 10:36 Sent To  
Notes
2016-05-17 11:11:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
 3. PROVIDE A CONTRACTOR RESUME WHICH INCLUDES SIMILAR
 PROJECTS, FBC 105.
  
 2ND REVIEW, THE RESPONSE LETTER STATES THIS WAS
 PROVIDED, BUT I AM UNABLE TO LOCATE IT. THE APPLICATION
 IS "TBD." PROVIDE THE REQUIRED INFORMATION SO THE FILE
 CAN BE DOCUMENTED THAT THE CONTRACTOR (CURRENTLY
 UNKNOWN) HAS THE LICENSURE AND EXPERIENCE TO WORK ON A
 THRESHOLD BUILDING, FS489.
  
 4. OK
  
 5. REVISE PLAN TO INCLUDE THE GOVERNING CODE, FBC 107.
  
 RESPONSE LETTER STATES PLAN HAS BEEN REVISED. PLEASE
 ADVISE AS TO LOCATION. OR, IF PLAN HAS NOT BEEN
 REVISED, IN LIEU OF RESUBMITTAL A DIGITALLY SIGNED AND
 SEALED LETTER FROM DOR MAY BE PROVIDED VIA EMAIL.
  
 6-7. OK
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 1. FBC 105.13, AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS, THE BUILDING OFFICIAL IS
 AUTHORIZED TO ISSUE A PERMIT FOR THE CONSTRUCTION OF
 FOUNDATIONS OR ANY OTHER PART OF A BUILDING OR
 STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS FOR THE
 WHOLE BUILDING OR STRUCTURE HAVE BEEN SUBMITTED. THE
 HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER PARTS
 OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDER'S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 2. PER APPLICANT, REPLAT IS IN PROGRESS. ADVISE AS TO
 BOOK/PAGE WHEN THIS IS RECORDED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By shill Date 2016-04-04 Time 11:44 Rev Time 0.00
Received By shill Date 2016-04-04 Time 11:44 Sent To  
Notes
2016-04-04 11:58:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE GEOTECHNICAL REPORT IS TO BE REVIEWED BY
 ENGINEER OF RECORD, FBC 107, FAC61G15-23. THIS MAY BE
 DEMONSTRATED BY PROVIDING THE PLAN PAGE WITH THE
 GEOTECHNICAL REPORT REFERENCE (IF APPLICABLE), A SHOP
 DRAWING REVIEW STAMP, OR A LETTER.
  
 2. PROVIDE INFORMATION REGARDING WHO WILL SUPERVISE THE
 PROPOSED WORK, FBC 110. PROVIDE A RESUME FOR THAT
 COMPANY AND INDIVIDUAL.
  
 3. PROVIDE A CONTRACTOR RESUME WHICH INCLUDES SIMILAR
 PROJECTS, FBC 105.
  
 4. DELEGATED ENGINEERING IS TO BE REVIEWED BY ENGINEER
 OF RECORD, FAC61G15-23.
  
 5. REVISE PLAN TO INCLUDE THE GOVERNING CODE, FBC 107.
  
 6. PROVIDE A SITE PLAN WHICH SHOWS LOCATION OF PROPOSED
 WORK, FBC 107.
  
 7. THE ADDRESS FOR THIS JOB APPEARS TO BE ONLY ONE LOT
 OF SEVERAL FOR THIS PROJECT. PLEASE ADVISE; IS A
 RE-PLAT OR UNITY OF TITLE PENDING? FOR RECORD KEEPING
 PURPOSES, THE POLICY OF THIS DEPARTMENT IS THAT A
 SEPARATE PERMIT IS REQUIRED FOR EACH PARCEL. NOT ENOUGH
 INFORMATION HAS BEEN PROVIDED TO RESOLVE THIS ISSUE.
  
 8. FBC 105.13, AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS, THE BUILDING OFFICIAL IS
 AUTHORIZED TO ISSUE A PERMIT FOR THE CONSTRUCTION OF
 FOUNDATIONS OR ANY OTHER PART OF A BUILDING OR
 STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS FOR THE
 WHOLE BUILDING OR STRUCTURE HAVE BEEN SUBMITTED. THE
 HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER PARTS
 OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2016-05-27 Cont ID  
Sent By Mgonzale Date 2016-05-27 Time   Rev Time 1.00
Received By mgonzale Date 2016-05-27 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2016-05-23 Cont ID  
Sent By mgonzale Date 2016-05-23 Time   Rev Time 0.00
Received By mgonzale Date 2016-05-23 Time   Sent To  
Notes
2016-05-23 13:05:38ADDRESS BUILDING COMMENTS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-04-10 Cont ID  
Sent By Mgonzale Date 2016-04-10 Time   Rev Time 1.00
Received By mgonzale Date 2016-04-10 Time   Sent To ENG
Notes
2016-04-10 16:59:53#1 ADDRESS BUILDING DEPARTMENT COMMENTS.
 #2 VIBRO SHALL TAKE IN ACCOUNT EXISTINGCITY OF WPB
 INFRSTRAUCTURE FOR WATER SEWER STORM ETC,
 LOCATES WILL BE REQUIRED INSIDE AND AROUND THE EXISTING
 ROW AND ADJACENT PROPERTIES.
  
 [email protected]
 MANNY GONZALEZ
 PUBLIC WORKS ENGINEERING SERVICES
 (561) 494-185
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-31 Cont ID  
Sent By shill Date 2016-05-31 Time 09:31 Rev Time 0.00
Received By shill Date 2016-05-25 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-23 Cont ID  
Sent By lmarchan Date 2016-05-23 Time 13:10 Rev Time 0.00
Received By lmarchan Date 2016-05-04 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-11 Cont ID  
Sent By cpuell Date 2016-04-11 Time 13:00 Rev Time 0.00
Received By cpuell Date 2016-03-31 Time 13:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2016-05-27 Cont ID  
Sent By shill Date 2016-05-27 Time 13:14 Rev Time 0.00
Received By shill Date 2016-05-27 Time 13:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-05-17 Cont ID  
Sent By shill Date 2016-05-17 Time 11:12 Rev Time 0.00
Received By shill Date 2016-05-17 Time 11:12 Sent To  
Notes
2016-05-17 11:14:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE GEOTECHNICAL REPORT IS NOT DIGITALLY SIGNED AND
 SEALED. EITHER SUBMIT A DIGITALLY SIGNED AND SEALED
 REPORT PER FS471 OR PROVIDE SIGNATURE DOCUMENTS. A
 PAPER SIGNED AND SEALED REPORT MAY ALSO BE PROVIDED;
 SUBMIT AT THE BUILDING DIVISION COUNTER AND NOTE THAT
 THEY ARE SIGNATURE DOCUMENTS.
  
 2. SHEET HB2 IS NOT DIGITALLY SIGNED AND SEALED. THIS
 MAY SENT VIA EMAIL DIRECTLY TO ME.
  
 3. INFORMATIONAL ONLY; SHEET S5.0 IS NOT DIGITALLY
 SIGNED AND SEALED BUT IS FOR THE PURPOSE OF SHOP
 DRAWING REVIEW. A DIGITALLY SIGNED AND SEALED ORIGINAL
 IS TO BE PROVIDED WITH THE BUILDING PERMIT.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By shill Date 2016-04-04 Time 11:44 Rev Time 0.00
Received By shill Date 2016-04-04 Time 11:44 Sent To  
Notes
2016-04-04 11:15:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE GEOTECHNICAL REPORT IS NOT DIGITALLY SIGNED AND
 SEALED. EITHER SUBMIT A DIGITALLY SIGNED AND SEALED
 REPORT PER FS471 OR PROVIDE SIGNATURE DOCUMENTS.
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status N Date 2016-05-31 Cont ID  
Sent By shill Date 2016-05-31 Time 09:30 Rev Time 0.00
Received By shill Date 2016-05-27 Time 13:14 Sent To  
Notes
2016-05-27 13:15:08CONTRACTOR (HAYWARD BAKER) RESUME ROUTED TO KEN CONRAD
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2016-04-11 Cont ID  
Sent By aaponte Date 2016-04-11 Time 10:16 Rev Time 0.00
Received By aaponte Date 2016-04-11 Time 10:16 Sent To  
Notes
***NONE***