Plan Review Details - Permit 16020182
Plan Review Stops For Permit 16020182
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-11 Cont ID  
Sent By tklarge Date 2016-03-11 Time   Rev Time 0.00
Received By jwitmer Date 2016-03-11 Time 07:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By jwitmer Date 2016-02-10 Time 08:50 Rev Time  
Received By jwitmer Date 2016-02-10 Time 07:15 Sent To  
Notes
2016-02-10 08:01:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020182
 ADD: 5500 VILLAGE BLVD. # 201
 CONT: BLACK DIAMOND GENERAL CONTRACTING
 TEL: 561-746-3452
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 10/2016
 ACTION: DENIED
  
 1) THE COVERSHEET A1.1 CODE SUMMARY, APPLICABLE CODES
 NOTE 1.3 FIRE SPRINKLER WORK SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 13, 2010 EDITION. UNDERTHE HEADING
 BUILDING CODES NOTE NEW CONSTRUCTION 2.2 TYPE IIB / NOT
 SPRINKLERED. SHEET 3.1 NOTE: NEW SPRINKLER HEAD FOR NEW
 RECESSED COMMON AREA. THERE IS A DISCREPANCY IN THE
 PLANS, PLEASE CORRECT. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 2) SHEET 3.1:
 2A) THE MAIN ENTRY TO THE RECEPTION AREA SHOWS A PAIR
 OF DOUBLE DOORS ON MAGNETIC HOLD OPEN DEVICES AND A
 SECOND PAIR OF DOORS, THE ONE DOOR IS LABELED ENACTIVE.
 PLEASE PROVIDE THE TYPE OF HARDWARE ON THESE PAIRS OF
 DOORS. THE DOOR HARDWARE SHALL COMPLY WITH THE 2014
 FBC-B SECTION 1008.1.9.1 HARDWARE.
 DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING
 DEVICES ON DOORS REQUIRED TO BE ACCESSIBLE BY CHAPTER
 11 SHALL NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
 THE INACTIVE DOOR MUST RELEASE WHEN A PERSON IN A
 WHEELCHAIR NEEDS TO EXIT THE TENANT SPACE. 2014
 FBC-ACCESSIBILITY:
  
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 2B) THE 2ND ISSUE IS WITH THE NEW DOOR # 218A. SINCE
 BOTH DOORS OF DOOR 200 HAVE TO BE ACTIVE THEY BLOCK THE
 EGRESS OF DOOR 218A.
  
 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED,
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7
 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE
 THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-02 Cont ID  
Sent By rlecky Date 2016-03-02 Time 12:23 Rev Time 0.00
Received By rlecky Date 2016-03-02 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-10 Cont ID  
Sent By rlecky Date 2016-02-10 Time 13:02 Rev Time 0.00
Received By rlecky Date 2016-02-10 Time 12:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-03 Time   Rev Time 0.00
Received By pleduc Date 2016-03-03 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-02-09 Cont ID  
Sent By pleduc Date 2016-02-09 Time   Rev Time 0.00
Received By pleduc Date 2016-02-09 Time 13:18 Sent To  
Notes
2016-02-09 14:23:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET 1.1 SECTION 2.2 INDICATES "NOT SPRINKLERED",
 HOWEVER, GENERAL NOTES INCLUDE MAJOR CONSTRUCTION FIRE
 SPRINKLERS.
 SHEET 3.1 INDICATES A TABLE NOTE "NOT SPRINKLERED";
 HOWEVER, A NOTE BOX INDICATES FIRE SPRINKLERS IN COMMON
 AREA.
  
 PLEASE BETTER CLARIFY AND PROVIDE CONSISTENT NOTES ON
 EACH SHEET.
  
 2. SHEET 3.1 INDICATES A NEW DOOR LEADING TO THE
 CORRIDOR. IT ALSO INDICATES AN EXISTING DOUBLE DOOR
 NEXT TO IT THAT INDICATES A FIXED DOOR LEAF.
  
 PER NFPA 101, CHAPTER 7, DOOR SWING DIRECTION,
 7.2.1.4.2, DOOR IS REQUIRED TO SWING IN THE DIRECTION
 OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER
 PERSONS.
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PROVIDE OCCUPANCY LOAD CALCULATIONS FOR THE EXISTING
 BUSINESS AND WITH LIFE SAFETY PLAN DETAILS THAT SHOW
 THAT THE DOUBLE DOOR LEAF CAN BE FIXED AND THAT BOTH
 DOORS ARE NOT REQUIRED TO BE OPENED FOR EGRESS
 CALCULATIONS. OTHERWISE THE NEW DOOR PLACEMENT EGRESS
 IS IN VIOLATION DUE TO THE THAT DOUBLE DOOR LEAF BEING
 OPENED.
  
 3. SHEET 10.1 DOOR SCHEDULE AND EXIT DEVICE NOTE.
 PROVIDE JUSTIFICATION THAT THE EXIT DEVICE ON DOORS 218
 AND 218A ARE NOT REQUIRED TO HAVE PANIC HARDWARE
 INSTALLED. SHOULD PANIC HARDWARE BE REQUIRED, PROVIDE
 AN ACCURATE NOTE.
  
 PER NFPA 101, CHAPTERE 7, 7.2.1.5.1 DOOR LEAVES SHALL
 BE ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE
 WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.10 A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT MORE THAN ONE RELEASING OPERATION.
  
 4. SHEET 10.1 DOOR SCHEDULE. A DOOR CLOSER IS NOT
 INDICATED ON DOOR 218A; HOWEVER, IT IS A RATED DOOR AND
 REQUIRED TO HAVE A CLOSER PER NFPA 101, CHAPTER 7,
 7.2.1.8
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By tklarge Date 2016-03-14 Time 09:00 Rev Time 0.00
Received By tklarge Date 2016-03-01 Time 11:15 Sent To  
Notes
2016-03-01 11:15:38B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-18 Cont ID  
Sent By gjohnson Date 2016-02-18 Time 09:39 Rev Time 0.00
Received By gjohnson Date 2016-02-04 Time 13:42 Sent To  
Notes
2016-02-05 13:43:10B11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 11:57 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 11:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By ccole Date 2016-02-11 Time 11:37 Rev Time 0.00
Received By ccole Date 2016-02-11 Time 11:37 Sent To  
Notes
2016-02-11 11:41:111ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020182
 2/11/16
  
 1) SHEET MP1: IT APPEARS THAT RETURN AIR IS BEING
 TRANSFERRED INTO THE EGRESS CORRIDOR, HOWEVER CORRIDORS
 CANNOT SERVE AS VENTILATION DUCTS- SECTION 601.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-12 Cont ID  
Sent By tklarge Date 2016-03-12 Time 07:40 Rev Time 0.00
Received By tklarge Date 2016-03-12 Time 03:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-18 Cont ID  
Sent By gjohnson Date 2016-02-18 Time 09:39 Rev Time  
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***