| 2016-02-24 11:21:09 | JOB PERMIT NUMBER: 16020161 |
| | JOB ADDRESS: 333 FERN STREET |
| | WEST PALM BEACH |
| | DATE: FEB 24 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1 THE ELECTRICAL REVIEW IN ENTIRELY IS RESERVED PENDING |
| | RESPONSES TO FIRE COMMENTS. (PUBLIC BATHROOMS MIGHT |
| | HAVE ADA ISSUES DEPENDING ON STALL HEIGHT EXTRA |
| | NOTIFICATION DEVICES WILL BE REQUIRED.) |
| | 2 SITE CURRENT CODE STANDARDS NEC 2011, FBC 2014, NFPA |
| | 72 2010, AND NFPA 101 2012. |
| | 3 SMOKE DETECTION IS REQUIRED IN ALL MECHANICAL, |
| | ELECTRICAL / COMMUNICATION ROOMS. IN FRONT OF ALL FACP |
| | AND ELEVATORS WHICH IS MISSING IN 2ND & 4TH FLOOR FOR |
| | ELEVATOR 4. FBC SECTION 907 |
| | 4 ILLUMINATION IS REQUIRED IN FRONT OF ALL FACP NEC |
| | 110.26 D AND THE LOCATION OF ANY REMOTELY LOCATED POWER |
| | SUPPLY SHALL BE IDENTIFIED AT THE MASTER CONTROL UNIT. |
| | NFPA 72 CHAPTER 10.5 |
| | 5 THE BRANCH CIRCUIT FEEDING THE FIRE ALARM SHALL BE |
| | DEDICATED AND LABELED IN"RED" MECHANICAL PROTECTION OF |
| | BREAKER WILL BE NEEDED. NEC 760.41 , 760.121 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | [email protected] |
| | |