Plan Review Details - Permit 16020161
Plan Review Stops For Permit 16020161
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-31 Cont ID  
Sent By mvaldes Date 2016-03-31 Time 09:02 Rev Time 0.00
Received By mvaldes Date 2016-03-31 Time 09:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-24 Cont ID  
Sent By mvaldes Date 2016-02-24 Time 09:10 Rev Time 0.00
Received By mvaldes Date 2016-02-24 Time 09:10 Sent To  
Notes
2016-02-24 11:21:09JOB PERMIT NUMBER: 16020161
 JOB ADDRESS: 333 FERN STREET
 WEST PALM BEACH
 DATE: FEB 24 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1 THE ELECTRICAL REVIEW IN ENTIRELY IS RESERVED PENDING
 RESPONSES TO FIRE COMMENTS. (PUBLIC BATHROOMS MIGHT
 HAVE ADA ISSUES DEPENDING ON STALL HEIGHT EXTRA
 NOTIFICATION DEVICES WILL BE REQUIRED.)
 2 SITE CURRENT CODE STANDARDS NEC 2011, FBC 2014, NFPA
 72 2010, AND NFPA 101 2012.
 3 SMOKE DETECTION IS REQUIRED IN ALL MECHANICAL,
 ELECTRICAL / COMMUNICATION ROOMS. IN FRONT OF ALL FACP
 AND ELEVATORS WHICH IS MISSING IN 2ND & 4TH FLOOR FOR
 ELEVATOR 4. FBC SECTION 907
 4 ILLUMINATION IS REQUIRED IN FRONT OF ALL FACP NEC
 110.26 D AND THE LOCATION OF ANY REMOTELY LOCATED POWER
 SUPPLY SHALL BE IDENTIFIED AT THE MASTER CONTROL UNIT.
 NFPA 72 CHAPTER 10.5
 5 THE BRANCH CIRCUIT FEEDING THE FIRE ALARM SHALL BE
 DEDICATED AND LABELED IN"RED" MECHANICAL PROTECTION OF
 BREAKER WILL BE NEEDED. NEC 760.41 , 760.121
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 1ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-30 Cont ID  
Sent By scaldero Date 2016-03-30 Time 10:59 Rev Time 0.00
Received By scaldero Date 2016-03-30 Time 10:53 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By scaldero Date 2016-02-17 Time 14:43 Rev Time 0.00
Received By scaldero Date 2016-02-12 Time 12:01 Sent To E
Notes
2016-02-17 14:42:36PERMIT #16020161
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PLANS ARE MISSING THE ENGINEER OF RECORD'S SEAL.
 PLANS ARE SIGNED, BUT NOT SEALED.
  
 2) A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 3) PARKING GARAGE AREAS HAVE INADEQUATE NOTIFICATION
 COVERAGE IN VARIOUS AREAS. REVIEW AND CORRECT.
  
 4) AUDIBLE DEVICES ARE NEEDED IN THE PUBLIC RESTROOMS.
 IF THE STALLS ARE TO BE EQUIPPED WITH FULL HEIGHT
 WALLS, NOTIFICATION DEVICES WILL BE NEEDED INSIDE THE
 STALLS, AS WELL.
  
 5) BDA RADIO COVERAGE NEEDED. PHONE JACKS MAY BE USED
 AS BACK-UPS.
  
 6) ANNUNICIATOR PANEL NEEDED AT 1ST FLOOR MAIN
 ENTRANCE.
  
 7) NOTIFICATOIN DEVICES (A/V) NEEDED IN TRASH ROOMS.
  
 8) NOTIFICATION DEVICES (A/V) NEEDED IN BIKE STORAGE
 ROOMS.
  
 9) NOTIFICATOIN DEVICES (A/V) NEEDED ON TERRACES.
  
 10) ADDITIONAL SMOKE DETECTORS NEEDED IN CORRIDORS.
 (SEE SHEET FA-05)
  
 11) 14TH FLOOR (SHEET FA-14) MISSING A SMOKE DETECTOR
 IN THE CORRIDOR.
  
 12) SPECIAL INSPECTOR AND REPORTS NEEDED FOR SMOKE
 CONTROL SYSTEM.
  
 13) SEE PLAN REVIEW COMMENTS ON PLANS FOR SPECIFIC
 LOCATIONS AND/OR AREAS OF CONCERN.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-31 Cont ID  
Sent By mvaldes Date 2016-03-31 Time 09:02 Rev Time 0.00
Received By mvaldes Date 2016-03-23 Time 11:41 Sent To  
Notes
2016-03-23 11:41:14RESUB ROUTED TO SCALDERO VIA FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-24 Cont ID  
Sent By mvaldes Date 2016-02-24 Time 11:23 Rev Time 0.00
Received By mvaldes Date 2016-02-04 Time 13:19 Sent To  
Notes
2016-02-05 13:19:14ROUTED TO FIRE