Plan Review Details - Permit 16020086
Plan Review Stops For Permit 16020086
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-23 Cont ID  
Sent By cthroop Date 2016-02-23 Time 14:00 Rev Time 0.00
Received By cthroop Date 2016-02-23 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-19 Cont ID  
Sent By cthroop Date 2016-02-19 Time 11:25 Rev Time 0.00
Received By cthroop Date 2016-02-19 Time 11:25 Sent To  
Notes
2016-02-19 11:41:15CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 2ND REVIEW
  
 APPLICANT DID NOT COMPLY WITH 1ST REVIEW COMMENTS.
 RE-SUBMITTAL INCLUDED IMPACT SOUND TRANSMISSION TEST
 FOR SOUND GUARD UNDERLAYMENT AND PRODUCT DATA SHEET FOR
 ECO-ULTIMATE SILENCER UNDERLAYMENT.
 STATE WHAT UNDERLAYMENT PRODUCT WILL BE USED. PROVIDE
 IMPACT SOUND TRANSMISSION TEST (IIC) AND SOUND
 TRANSMISSION TEST (STC) FOR SPECIFIED PRODUCT. INCLUDE
 TEST RESULTS FOR SURFACE BURNING CHARACTERISTICS OF
 BUILDING MATERIALS (ASTM E-84-06) FOR SPECIFIED
 PRODUCT.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 603.1 FLAME SPREAD

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-03 Cont ID  
Sent By cthroop Date 2016-02-03 Time 12:57 Rev Time 0.00
Received By cthroop Date 2016-02-03 Time 12:57 Sent To  
Notes
2016-02-03 13:05:22CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE AIR-BORNE AND IMPACT-BORNE SOUND TRANSMISSION
 TEST RESULTS FROM AN ACCREDITED TESTING LABORATORY.
 PROVIDE FLAME SPREAD DATA FOR UNDERLAYMANT AND
 ADHESIVES.
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 FBC 603.1 FLAME SPREAD
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-23 Cont ID  
Sent By cthroop Date 2016-02-23 Time 14:00 Rev Time 0.00
Received By cthroop Date 2016-02-23 Time 09:08 Sent To  
Notes
2016-02-23 09:08:29RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-19 Cont ID  
Sent By cthroop Date 2016-02-19 Time 11:25 Rev Time 0.00
Received By cthroop Date 2016-02-17 Time 15:06 Sent To  
Notes
2016-02-17 15:07:11RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-03 Cont ID  
Sent By cthroop Date 2016-02-03 Time 12:57 Rev Time 0.00
Received By cthroop Date 2016-02-02 Time 10:39 Sent To  
Notes
2016-02-03 10:39:31BLDG -$5000