Plan Review Details - Permit 16020067
Plan Review Stops For Permit 16020067
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-11 Cont ID  
Sent By jwitmer Date 2016-05-11 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2016-05-07 Time 13:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By jwitmer Date 2016-02-08 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2016-02-05 Time 15:45 Sent To  
Notes
2016-02-08 07:07:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020067
 ADD: 1200 S. FLAGLER DR. SUITE # 105
 CONT: TROTTCO ENTERPRISES
 TEL: 561-719-3010
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 08/2016
 ACTION: DENIED
  
 1) THE COVERSHEET AS1 LIST THIS 19 STORY CONDOMINIUM AS
 A BUILDING TYPE: 5B AND OCCUPANCY TYPE A R3. THE 2014
 FBC-B CODE FOR A 19 STORY HIGHRISE REQUIRES THE
 BUILDING TYPE TO BE A BUILDING TYPE IA (2014 FBC-B
 TABLE 503). R3 OCCUPANCIES ARE USUALLY SINGLE FAMILY
 RESIDENCE OR A SINGLE RESIDENTIAL UNIT IN A MIXED
 OCCUPANCY. CONDOMINIUMS AND APARTMENT BUILDINGS ARE
 CONSIDERED R2 OCCUPANCIES SEE 2014 FBC-B 310.4.
  
 2) THE SUBMITTED NOA 15-0106.08 PGT 770-HP ALUMINUM
 SLIDING GLASS DOORS W/ REINFORCEMENT L. M. I. TABLE 1
 THE CIRCLED DOOR SIZES ARE 42/48X98 INCHES TABLE ! THE
 PRESSURES ARE GOOD TO +90/-130. THE LIMITING FACTOR IS
 IN TABLE1A. THE SILL HEIGHT CIRCLED IS +60 PSF. TIS
 APPEARS TO BE LIMITED AT +60PSF
 FOR THE MEDIUM 3 1/4 INCH SILL HEIGTH. A 4 INCH SILL
 GIVES A +PRESSURE OF 90.
  
 3) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) THE COVERSHEET ALSO LIST NEW FLOOR COVERINGS. FOR
 TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
  
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-16 Cont ID  
Sent By vperez Date 2016-05-16 Time 13:36 Rev Time 0.00
Received By vperez Date 2016-05-16 Time 13:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-09 Cont ID  
Sent By rlecky Date 2016-02-09 Time 14:00 Rev Time 0.00
Received By rlecky Date 2016-02-08 Time 14:30 Sent To  
Notes
2016-02-09 14:02:20PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A FEEDER DETAIL AND A SUMMARY LOAD CALCULATION
 FOR THIS OCCUPANCY. INDICATE THE LOCATION AND SIZE OF
 THE MAIN BREAKER. NEC 215.5
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
 VERIFY THAT ALL RECEPTACLE OUTLETS ARE TAMPER
 RESISTANT. NEC 406.13
 VERIFY THE BATH LIGHTING IN THE TUB/SHOWER AREA IS
 LISTED FOR DAMP LOCATION AND LOCATED AT THE CORRECT
 HEIGHT. NEC 410.10(D)
 PROVIDE A DETAIL FOR THE CLOSET LIGHTING INDICATING THE
 TYPE OF FIXTURES AND THE LOCATION FROM THE STORAGE
 AREA. NEC 410.16
 VERIFY THAT ALL RECEPTACLE OUTLETS ARE PROPERLY SPACED.
 THE GUEST BEDROOM REQUIRES AN ADDITIONAL RECEPTACLE.
 NEC 210.52
 VERIFY THAT ALL CEILING ELECTRICAL BOXES ARE LISTED FOR
 HANGING PADDLE FANS. NEC 422.18
 VERIFY THERE IS A GFCI PROTECTED OUTLET LOCATED ON THE
 PATIO. NEC 210.8
 PROVIDE A DEDICATED LAUNDRY CIRCUIT AND RECEPTACLE. NEC
 210.11(C)2
 PROVIDE A DEDICATED 20 AMPERE BRANCH CIRCUIT TO THE
 BATHROOMS. NEC 210.11(C)3
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By pleduc Date 2016-05-05 Time   Rev Time 0.00
Received By pleduc Date 2016-05-05 Time 11:21 Sent To  
Notes
2016-05-05 11:23:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS AND /OR CEILINGS REQUIRE AN EVALUATION.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-16 Cont ID  
Sent By vperez Date 2016-05-16 Time 13:39 Rev Time 0.00
Received By vperez Date 2016-05-16 Time 13:39 Sent To  
Notes
2016-05-03 15:35:25B17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-24 Cont ID  
Sent By gjohnson Date 2016-02-24 Time 09:52 Rev Time 0.00
Received By gjohnson Date 2016-02-24 Time 09:52 Sent To  
Notes
2016-02-16 16:29:17CCOLE CLOSED OUT I STOP BEFORE REVIEW FINISHED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-11 Cont ID  
Sent By ccole Date 2016-02-11 Time 11:24 Rev Time 0.00
Received By ccole Date 2016-02-02 Time 10:47 Sent To  
Notes
2016-02-03 10:47:44B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-10 Cont ID  
Sent By ccole Date 2016-05-10 Time 11:58 Rev Time 0.00
Received By ccole Date 2016-05-10 Time 11:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By ccole Date 2016-02-10 Time 10:46 Rev Time 0.00
Received By ccole Date 2016-02-10 Time 10:46 Sent To  
Notes
2016-02-11 11:34:311ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020067
 2/10/16
  
 1) SUBMIT TWO COPIES OF THE CITY OF WPB AC CHANGE OUT
 FORM FOR THE REPLACED HEAT PUMP.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-24 Cont ID  
Sent By gjohnson Date 2016-02-24 Time 09:46 Rev Time 0.00
Received By gjohnson Date 2016-02-24 Time 09:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By ccole Date 2016-02-10 Time 11:19 Rev Time 0.00
Received By ccole Date 2016-02-10 Time 11:36 Sent To  
Notes
2016-02-11 11:35:542/10/16
  
 DISREGARD PLAN REVIEW, ACCIDENTAL ENTRY.
 NEW PLUMBING STOP INSERTED.
  
 CCOLE