| 2016-02-08 07:07:22 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020067 |
| | ADD: 1200 S. FLAGLER DR. SUITE # 105 |
| | CONT: TROTTCO ENTERPRISES |
| | TEL: 561-719-3010 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 08/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET AS1 LIST THIS 19 STORY CONDOMINIUM AS |
| | A BUILDING TYPE: 5B AND OCCUPANCY TYPE A R3. THE 2014 |
| | FBC-B CODE FOR A 19 STORY HIGHRISE REQUIRES THE |
| | BUILDING TYPE TO BE A BUILDING TYPE IA (2014 FBC-B |
| | TABLE 503). R3 OCCUPANCIES ARE USUALLY SINGLE FAMILY |
| | RESIDENCE OR A SINGLE RESIDENTIAL UNIT IN A MIXED |
| | OCCUPANCY. CONDOMINIUMS AND APARTMENT BUILDINGS ARE |
| | CONSIDERED R2 OCCUPANCIES SEE 2014 FBC-B 310.4. |
| | |
| | 2) THE SUBMITTED NOA 15-0106.08 PGT 770-HP ALUMINUM |
| | SLIDING GLASS DOORS W/ REINFORCEMENT L. M. I. TABLE 1 |
| | THE CIRCLED DOOR SIZES ARE 42/48X98 INCHES TABLE ! THE |
| | PRESSURES ARE GOOD TO +90/-130. THE LIMITING FACTOR IS |
| | IN TABLE1A. THE SILL HEIGHT CIRCLED IS +60 PSF. TIS |
| | APPEARS TO BE LIMITED AT +60PSF |
| | FOR THE MEDIUM 3 1/4 INCH SILL HEIGTH. A 4 INCH SILL |
| | GIVES A +PRESSURE OF 90. |
| | |
| | 3) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 4) THE COVERSHEET ALSO LIST NEW FLOOR COVERINGS. FOR |
| | TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO HAVE |
| | HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS: |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |