Plan Review Details - Permit 16020038
| Plan Review Stops For Permit 16020038 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-02-09 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-02-09 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2016-02-09 14:06:54 | BUILDING PROVISO: SHEET A4.0 DETAIL # 4 COVED/ SOFFET | | | DETAIL, THE DROPPED CEILING SUB-BASE 3/4 INCH PLYWOOD | | | IS REQUIRED TO BE FIRE RESISTANCE-RATED OR | | | NONCOMBUSTILE. | | | 2014 FBC-B 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS | | | AND CEILINGS ARE REQUIRED TO BE OF | | | FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION | | | AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES | | | GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A | | | FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR | | | 803.1.2, SHALL BE USED. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-02-08 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-02-08 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2016-02-08 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2016-02-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-02-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-02-10 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-02-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-11 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-01 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-02-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-16 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-16 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2016-02-16 15:24:47 | MECHANICAL PROVISIO | | | PERMIT #16020038 | | | 2/16/16 | | | | | | A REVISION TO THE ARCHITECTURAL AND MECHANICAL PLANS | | | ARE REQUIRED TO CLEARLY SHOW THE 1" CONTINUOUS RETURN | | | AIR SPACE AT THE CEILINGS OF ROOMS 1001 & 1015. PLEASE | | | INCLUDE FREE AIR SPACE CALCULATIONS AND DIMENSIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-02-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-11 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-11 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2016-02-11 10:33:44 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020038 | | | 2/11/16 | | | | | | 1) SHEET M2.1: NOTE #15 INDICATES A 1" CONTINUOUS AIR | | | PATH IN LIEU OF THE REMOVED RETURNS AT THE CONFERENCE | | | AND RECEPTION ROOMS. PLEASE PROVIDE A DETAIL TO CLARIFY | | | HOW THIS IS BEING ACCOMPLISHED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-02-09 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-02-09 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy