Plan Review Details - Permit 16020027
Plan Review Stops For Permit 16020027
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-11 Cont ID  
Sent By mvaldes Date 2016-02-11 Time 13:33 Rev Time 0.00
Received By mvaldes Date 2016-02-11 Time 13:33 Sent To  
Notes
2016-02-11 13:34:07FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 PASS WITH A PROVISO
  
 - SPOKE TO CUSTOMER IN REFRENCE TO FACP IN STAIRWAY SHE
 STATED THERE UNDERNEATH. INSPECTOR TO VERIFY ON FIELD.
  
 - FOR FINAL INSPECTIONS FLOOR PLANS MUST BE PROPERLY
 LABELED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By mvaldes Date 2016-02-11 Time 10:06 Rev Time 0.00
Received By mvaldes Date 2016-02-11 Time 10:05 Sent To  
Notes
2016-02-11 10:27:20FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PLEASE PROVIDE A FLOOR PLAN THAT INDICATES THE USE OF
 ALL ROOMS. FBC 907.1.2 FIRE ALARM SHOP DRAWINGS
  
 - FACP NOT LOCATED OVER STEPS. OVERCURRENT DEVICES
 SHALL NOT BE LOCATED OVER STEPS OF A STAIRWAY. NEC
 240.24 F
 MUST ALSO COMPLY WITH NEC 110.26 WORKING CLEARANCE.
 PLEASE CLARIFY IF THIS PANEL IS OVER STEPS ?

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-05 Cont ID  
Sent By GJT Date 2016-02-05 Time   Rev Time  
Received By   Date 2016-02-05 Time   Sent To E
Notes
2016-02-05 12:28:58PASSED WITH THE FOLLOWING PROVISO: SYSTEM MUST PERFORM
 TO CURRENT NFPA 72 STANDARD INCLUDING MEETING 75DB AT
 THE PILLOW TOP IN EACH SLEEPING AREA.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-11 Cont ID  
Sent By cpuell Date 2016-02-11 Time 10:38 Rev Time 0.00
Received By cpuell Date 2016-02-01 Time 12:56 Sent To  
Notes
2016-02-02 12:57:03ROUTED TO FIRE