Plan Review Details - Permit 16010944
Plan Review Stops For Permit 16010944
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-02-10 Cont ID  
Sent By cthroop Date 2016-02-10 Time 09:54 Rev Time 0.00
Received By cthroop Date 2016-02-10 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By vperez Date 2016-03-14 Time 10:58 Rev Time 0.00
Received By vperez Date 2016-03-14 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-25 Cont ID  
Sent By rlecky Date 2016-02-25 Time 11:14 Rev Time 0.00
Received By rlecky Date 2016-02-25 Time 10:12 Sent To  
Notes
2016-02-25 11:16:05THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SHOW LOCATION OF THE MAIN ELECTRICAL DISCONNECT AND
 ELECTRICAL PANELS. VERIFY ALL REQUIRED SAFETY
 CLEARANCES. VERIFY ALL REQUIRED SERVICE GROUNDING.
 PROVIDE AN ELECTRICAL PANEL SCHEDULE SHOWING ALL NEW
 AND EXISTING CIRCUITS. PROVIDE A SUMMARY LOAD
 CALCULATION. ON THE PLANS SHOW THE LOCATION OF ALL NEW
 AND EXISTING ELECTRICAL SWITCHES AND OUTLETS. NEC
 110.26; 215.5; 408.4, FBC R E3405.3, 3706.2
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOM.
 NEC 210.11 (C) (3); FBC R E3703.4
  
 PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2);
 FBC R 3703.3
  
 SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED. 2014
 FBC R 314, 315
  
 SHOW GFCI PROTECTED RECEPTACLES WHERE REQUIRED. NEC
 210.8; FBC R 3902
  
 VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12;
 FBC R 3902.12
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.2; FBC R4002.14
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-03-10 Cont ID  
Sent By tklarge Date 2016-03-10 Time 09:13 Rev Time 0.00
Received By tklarge Date 2016-03-10 Time 09:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-02-02 Cont ID  
Sent By tklarge Date 2016-02-02 Time 06:53 Rev Time 0.00
Received By tklarge Date 2016-02-02 Time 06:41 Sent To  
Notes
2016-02-02 06:47:021.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2.SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3.TYPE OF GAS (LP OR NATURAL).
  
 4.BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 5.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7.INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON
 THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8.SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426.
  
 9.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO THE CHIEF PLUMBING INSPECTOR AT
 561-805-6692.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By vperez Date 2016-03-14 Time 10:58 Rev Time 0.00
Received By vperez Date 2016-03-14 Time 10:58 Sent To  
Notes
2016-03-14 10:58:513/14 TO CAROLINE
2016-03-09 14:14:24RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-25 Cont ID  
Sent By rlecky Date 2016-02-25 Time 11:16 Rev Time 0.00
Received By rlecky Date 2016-01-28 Time 13:08 Sent To  
Notes
2016-01-29 13:09:47R09

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-02 Cont ID  
Sent By tklarge Date 2016-02-02 Time 06:41 Rev Time 0.00
Received By tklarge Date 2016-02-02 Time 06:29 Sent To  
Notes
***NONE***