Plan Review Details - Permit 16010839
Plan Review Stops For Permit 16010839
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-08 Cont ID  
Sent By jgomez Date 2016-04-08 Time 15:56 Rev Time 0.00
Received By jgomez Date 2016-04-08 Time 15:48 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By jgomez Date 2016-02-18 Time 16:26 Rev Time 0.00
Received By jgomez Date 2016-02-18 Time 16:21 Sent To  
Notes
2016-02-18 16:31:59RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ENGINEER OF RECORD TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE TO ALL DRAWINGS AS REQUIRED BY CHAPTER 471
 FL. ST. RUBBER STAMP IS NOT ALLOWED.
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW EXTERIOR OPENINGS INFILL CONSTRUCTION. SPECIFY ALL
 FRAMING MEMBERS, CONNECTORS, SHEATHING AND EXTERIOR AND
 INTERIOR FINISHES, ETC. SEC. R301 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 3- PROVIDE COMPLETE FRAMING DETAILS FOR ALL NEW
 EXTERIOR DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW REAR
 DECK. SPECIFY ALL FRAMING MEMBERS, CONNECTORS,
 FOOTINGS, ETC. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 5- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE NEW DECK GUARDRAIL SHOWING COMPLIANCE WITH THE LIVE
 LOADS OF FOOTNOTES "D" AND "F" OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW DECK GUARDRAIL SHOWING COMPLIANCE WITH SEC. R312 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW DECK STEPS SHOWING COMPLIANCE WITH SEC. R311.7.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- SINGLE HUNG WINDOW NOA 15-0512.09 SUBMITTED:
 A) CLARIFY WHERE IS THIS TYPE OF WINDOW GOING TO BE
 INSTALLED. PLANS DON'T SHOW ANY NEW SINGLE HUNG
 WINDOWS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) GLAZED OPENINGS NEED LARGE MISSILE IMPACT PROTECTION
 AS REQUIRED BY SEC. R301.2.1.2 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). NOA 15-0512.09 IS FOR SMALL MISSILE
 IMPACT PROTECTION. IT CAN'T BE USED.
  
 8- CLARIFY WHERE IS ALUMINUM "INSWING" DOOR NOA
 14-1103.06 SUBMITTED GOING TO BE INSTALLED. PLANS DON'T
 SPECIFY ANY "INSWING" DOOR. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR ALL SIMPSON OR USP STRUCTURAL
 CONNECTORS SPECIFIED ON THE STRUCTURAL PLANS AND
 DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER (2014 CODE
 VERSION) NEXT TO EACH SPECIFIED CONNECTOR.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-22 Cont ID  
Sent By rlecky Date 2016-03-22 Time 11:18 Rev Time 0.00
Received By rlecky Date 2016-03-22 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-23 Cont ID  
Sent By rlecky Date 2016-02-23 Time 14:41 Rev Time 0.00
Received By rlecky Date 2016-02-22 Time 13:35 Sent To HIST
Notes
2016-02-23 14:42:02 
 SHOW LOCATION OF THE MAIN ELECTRICAL DISCONNECT AND
 ELECTRICAL PANELS. VERIFY ALL REQUIRED SAFETY
 CLEARANCES. NEC 110.26; FBC R E3405.3
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOM.
 NEC 210.11 (C) (3); FBC R E3703.4
  
 PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2);
  
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED FOR THE NEW
 ELECTRICAL SERVICE. NEC 250.52; FBC R E3608.1.4
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED. 2014
 FBC R 314, 315
  
 PROVIDE A ADDITIONAL COUNTER TOP RECEPTACLE FOR THE
 ISLAND COUNTER TOP ON THE OPPOSITE SIDE. NEC 210.52(C)
 (2); FBC R E3901.4.3
  
 RECESSED LIGHTS IN CONTACT WITH INSULATION MUST BE IC
 LISTED. NEC 410.116; FBC R 4004.8
  
 CEILING ELECTRICAL BOXES IF INTENDED FOR SUPPORT OF
 PADDLE FANS MUST BE LISTED FOR THAT USE. NEC 422.18;
 FBC R 3905.9
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-01-31 Cont ID  
Sent By tklarge Date 2016-01-31 Time 05:15 Rev Time 0.00
Received By tklarge Date 2016-01-31 Time 05:13 Sent To  
Notes
2016-01-31 05:15:02GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-04-08 Cont ID  
Sent By fmittner Date 2016-04-08 Time 15:06 Rev Time 0.00
Received By fmittner Date 2016-04-05 Time 13:48 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-03-01 Cont ID  
Sent By fmittner Date 2016-03-01 Time 09:46 Rev Time 0.00
Received By fmittner Date 2016-03-01 Time 09:46 Sent To  
Notes
2016-03-01 09:47:21PLANS SUBMITTED INDICATE DEMO OF SUNROOM. APPLICANT WAS
 WAITING ON HPB APPROVAL AT A LATER DATE. REVISE PLANS
 OR CLARIFY SCOPE OF WORK.
  
 QUESTIONS, CONTACT FRIEDERIKE MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-09 Cont ID  
Sent By tklarge Date 2016-04-09 Time 05:20 Rev Time 0.00
Received By tklarge Date 2016-03-18 Time 09:54 Sent To  
Notes
2016-03-21 09:56:43R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-01 Cont ID  
Sent By cpuell Date 2016-03-01 Time 10:19 Rev Time 0.00
Received By cpuell Date 2016-01-27 Time 13:59 Sent To  
Notes
2016-01-28 14:00:49R06

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-09 Cont ID  
Sent By tklarge Date 2016-04-09 Time 05:20 Rev Time 0.00
Received By tklarge Date 2016-04-09 Time 05:02 Sent To  
Notes
2016-04-08 18:22:56NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-31 Cont ID  
Sent By tklarge Date 2016-01-31 Time 05:03 Rev Time 0.00
Received By tklarge Date 2016-01-31 Time 04:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By jroach Date 2016-04-05 Time 13:48 Rev Time 0.00
Received By jroach Date 2016-04-05 Time 13:48 Sent To HIST
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By jroach Date 2016-02-12 Time 09:54 Rev Time 0.00
Received By jroach Date 2016-02-08 Time 15:36 Sent To  
Notes
2016-02-12 09:55:11ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.12.2016
 PERMIT NO.: 16010839
 ADDRESS: 300 BUCKINGHAM ROAD
 CONTRACTOR/CONTACT: GREGORY DAVIES
 TELEPHONE NO.: 561.793.8225
 SCOPE OF REVIEW: REMODEL TO EXISTING RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY.
  
 2. PLEASE PROVIDE A SITE PLAN THAT SHOWS ALL STRUCTURES
 IN RELATION TO PROPERTY LINES, ETC. BE SURE ALL
 SETBACKS ARE PROVIDED, ESPECIALLY TO THE NEW DECK.
  
 3. ACCORDING TO THE EXISTING/PROPOSED ELEVATIONS, THERE
 APPEARS TO BE A SUBSTANTIAL AMOUNT OF WORK BEING DONE
 IN THE IN THE LEFT/REAR CORNER OF THE BUILDING. THIS
 SCOPE OF WORK (DEMOLITION?) IS NOT CLEAR FROM THE FLOOR
 PLANS. PLEASE PROVIDE A DEMOLITION PLAN, ETC. TO
 IDENTIFY THE FULL SCOPE OF THE WORK.
  
 4. ACCORDING TO THE FLOOR PLAN IT STATES THAT THERE
 WILL BE A NEW GAS FIREPLACE CONNECTED TO AN OUTSIDE GAS
 TANK. PLEASE IDENTIFY THE LOCATION OF THE TANK ON THE
 SITE PLAN WITH SETBACKS TO THE PROPERTY LINES. NOTE
 THAT SEPARATE PERMITS MAY BE REQUIRED.
  
 5. AS THE PROPERTY IS LOCATED WITHIN AN HISTORIC
 DISTRICT, APPROVAL FROM THE CITY?S HISTORIC
 PRESERVATION DIVISION IS REQUIRED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  