Plan Review Details - Permit 16010825
Plan Review Stops For Permit 16010825
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-05-24 Cont ID  
Sent By Mgonzale Date 2016-05-24 Time   Rev Time 1.00
Received By mgonzale Date 2016-05-24 Time   Sent To I
Notes
2016-05-24 19:30:30IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-03-31 Cont ID  
Sent By Mgonzale Date 2016-03-31 Time   Rev Time 1.00
Received By mgonzale Date 2016-03-31 Time   Sent To Z
Notes
2016-03-31 19:47:19PROVIDE SPECIFICATIONS SHEETS ON BACKFLOWS.
  
 BACKFLOWS MUST "LEAD FREE" TYPE.
  
 [email protected]
 (561)494-1085

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-03-16 Cont ID  
Sent By scaldero Date 2016-03-16 Time 17:26 Rev Time 0.00
Received By scaldero Date 2016-03-16 Time 15:19 Sent To  
Notes
2016-03-16 17:26:31PERMIT # 16010825
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO
  
 1) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 2) PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 3) PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 4) PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 5) SHEET FP5: PER NFPA 13 - 8.16.1.2.2: PRESSURE GAUGES
 SHALL BE INSTALLED ON THE INLET AND OUTLET SIDES OF
 EACH PRESSURE-REDUCING VALVE.
  
 6) SHEET FP7: THE LOCATION OF THE BACKFLOW PREVENTER
 FOR FIRE SUPPRESSION SYSTEMS MUST COMPLY AS LISTED
 BELOW. THE CURRENT LOCATION (ROOM 143) DOES NOT APPEAR
 TO BE A FULLY ENCLOSED FIRE-RATED ROOM.
  
 PER NFPA 24 - 6.2.11
 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
  
 (1)* A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
  
 (2) A WALL POST INDICATOR VALVE
  
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
  
 (4)* A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT
 (12 M) BUT AT LEAST AS FAR FROM THE BUILDING AS THE
 HEIGHT OF THE WALL FACING THE BACKFLOW PREVENTER.
  
 (5)* A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE
 VALVE WITH AN APPROVED ROADWAY BOX, COMPLETE WITH
 T-WRENCH, LOCATED NOT LESS THAN 40 FT (12 M) FROM THE
 BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE VALVE
 WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH,
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT
 (12 M) BUT AT LEAST AS FAR FROM THE BUILDING AS THE
 HEIGHT OF THE WALL FACING THE BACKFLOW PREVENTER.
  
 (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
  
 (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-02 Cont ID  
Sent By skennedy Date 2016-06-02 Time 14:33 Rev Time 0.00
Received By skennedy Date 2016-04-06 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-01 Cont ID  
Sent By lmarchan Date 2016-04-01 Time 08:03 Rev Time 0.00
Received By lmarchan Date 2016-02-29 Time 15:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-13 Cont ID  
Sent By ccole Date 2016-04-13 Time 09:44 Rev Time 0.00
Received By ccole Date 2016-04-13 Time 09:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-14 Cont ID  
Sent By ccole Date 2016-03-14 Time 10:51 Rev Time 0.00
Received By ccole Date 2016-03-14 Time 10:51 Sent To  
Notes
2016-03-14 11:04:371ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010825
 3/14/16
  
 1) PLEASE INCLUDE THE MANUFACTURER'S SPECIFICATIONS FOR
 DDCV BACKFLOW PREVENTER AND FOR COMPONENTS OF THE JOINT
 RESTRAINT SYSTEMS.
 2) PLEASE CLARIFY WHY MANY OF THE FLOORS WERE LEFT OUT
 OF THE UPLOADED HYDRAULIC CALUCLATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-06-02 Cont ID  
Sent By skennedy Date 2016-06-02 Time 14:33 Rev Time 0.00
Received By skennedy Date 2016-06-02 Time 14:33 Sent To  
Notes
***NONE***