| 2016-02-05 09:50:58 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010805 |
| | ADD: 1645 PALM BEACH LAKES SUITE # 1050 |
| | CONT: CHANDLER CONSTRUCTION |
| | TEL: 561-791-6934 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. FEB. 05/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2 VERSES A-3. INDICATED ON SHEET A-2 IN THE |
| | WALL LEGEND IS THE WALL TYPE FOR A 1-HOUR FIRE RATED |
| | PARTITION. SHEET A-2 SHOWS VARIOUS NEW WALLS WITHIN THE |
| | TENANT SPACE WITH A WALL DETAIL OF 1/A3 WHICH INDICATES |
| | THIS TYPE OF WALL AS A 1-HOUR FIRE RATED PARTITION. THE |
| | DESIGNER CAN DESIGN OVER AND ABOVE THE MINIMUM CODE, IF |
| | THIS THE ENTENT THEN THE DOORS WITHIN THE RATED WALL |
| | WILL ALSO NEED TO COMPLY WITH OPENING PROTECTIVES FOUND |
| | UNDER 2014 FBC-B TABLE716.5. |
| | |
| | 2) THE COMBINED AREA OF SUITE 1050 IS NOW 6098 OR |
| | 6098/100= 61 OCCUPANTS. THE FRONT ENTRY DOORS SWING, |
| | SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE |
| | SERVING A ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF |
| | 50 OR MORE PERSONS OR A GROUP H OCCUPANCY.2014 FBC-B |
| | 1008.1.2. NEW WORK SHALL NOT CREATE A NONCONFORMITY. |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3) SHEET A-3 THE BREAKROOM # 114 SHOWS A MICROWAVE ON A |
| | SHELF APPROXIMATELY 5 FEET ABOVE FINISH FLOOR. PLEASE |
| | REVIEW THE 2014 FBC-ACCESSIBILITY CODE FOR OPERABLE |
| | PARTS: |
| | 309.1 GENERAL. OPERABLE PARTS SHALL COMPLY WITH 309. |
| | |
| | 309.2 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL |
| | BE PROVIDED. |
| | |
| | 309.3 HEIGHT. |
| | OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF |
| | THE REACH RANGES SPECIFIED IN 308. |
| | |
| | 309.4 OPERATION. |
| | OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND |
| | SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING |
| | OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE |
| | PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |