Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-10 Cont ID  
Sent By cthroop Date 2016-06-10 Time 14:10 Rev Time 0.00
Received By cthroop Date 2016-06-10 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-25 Cont ID  
Sent By cthroop Date 2016-05-25 Time 15:05 Rev Time 0.00
Received By cthroop Date 2016-05-25 Time 15:05 Sent To  
Notes
2016-05-25 15:08:372014 FLORIDA BUILDING CODE
 W/ 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHPT. 1, ADMINISTRATION
  
 2ND REVIEW
 DATE: 5/25/16
 ACTION: FAILED
  
 1. RE-SUBMITTAL MISSING PLAN PAGE 2.
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By cthroop Date 2016-02-09 Time 13:00 Rev Time 0.00
Received By cthroop Date 2016-02-09 Time 13:51 Sent To  
Notes
2016-02-09 15:23:49CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE SOILS REPORT.
 PROVIDE ENERGY CALCULATIONS.
 EXTERIOR DOOR JAMB DETAIL NOT LEGIBLE.
 PROVIDE DETAIL FOR LATERAL BRACING OF ROOF TRUSSES.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-03 Cont ID  
Sent By vperez Date 2016-05-03 Time 06:37 Rev Time 0.00
Received By vperez Date 2016-04-29 Time 15:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-16 Cont ID  
Sent By vperez Date 2016-02-16 Time 09:01 Rev Time 0.00
Received By vperez Date 2016-02-16 Time 09:01 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-01-28 Cont ID  
Sent By tklarge Date 2016-01-28 Time 06:49 Rev Time 0.00
Received By tklarge Date 2016-01-28 Time 06:49 Sent To  
Notes
2016-01-28 06:50:23GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-10 Cont ID  
Sent By cthroop Date 2016-06-10 Time 14:10 Rev Time 0.00
Received By cthroop Date 2016-05-27 Time 14:23 Sent To  
Notes
2016-05-27 14:24:03RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-25 Cont ID  
Sent By cthroop Date 2016-05-25 Time 15:05 Rev Time 0.00
Received By cthroop Date 2016-04-26 Time 08:32 Sent To  
Notes
2016-04-27 08:32:44R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-29 Cont ID  
Sent By ccole Date 2016-02-29 Time 14:28 Rev Time 0.00
Received By ccole Date 2016-02-16 Time 09:02 Sent To  
Notes
2016-02-16 09:02:45ROUTED TO LAURA
2016-01-25 09:29:29R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2016-02-09 Cont ID  
Sent By cthroop Date 2016-02-09 Time 14:30 Rev Time 0.00
Received By cthroop Date 2016-02-09 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By ccole Date 2016-05-23 Time 16:37 Rev Time 0.00
Received By ccole Date 2016-05-23 Time 16:39 Sent To  
Notes
2016-05-23 16:42:53MECHANICAL PROVISO
 5/23/16
  
 1) REVISION REQUIRED FOR FIREPLACE OUTSIDE COMBUSTION
 AIR INTAKE AND DUCT RUN.
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE FIREPLACE, VENTING, AND OUTSIDE
 AIR INTAKE SHALL BE ONSITE AT TIME OF INSPECTION.
 2) OWNWER MUST SIGN ENERGY CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-29 Cont ID  
Sent By ccole Date 2016-02-29 Time 13:03 Rev Time 0.00
Received By ccole Date 2016-02-29 Time 13:03 Sent To  
Notes
2016-02-29 14:25:461ST REVIEW: FBC 2014 RESIDENTIAL MECHANICAL
 PERMIT #16010755
 2/29/15
  
 1) ON OF THE SUBMITTED PLANS SETS IS MISSING THE
 ARCHITECT'S RAISED SEAL ON SHEETS 1, T1, AND M1.
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH ACCA MANUAL J & S OR OTHER APPROVED
 CALCULATION METHODOLGIES- SEE SECTION R403.6 FBC-14
 ENERGY CONSERVATION.
 3) PROVIDE ENERGY EFFICIENCY CALCULATIONS FOR THE NEW
 ADDITON IN COMPLIANCE WITH SECTION R101.4.3 AND
 R101.5.1. *ADVISORY*- "AIR HANDLING UNITS SHALL NOT BE
 INSTALLED IN THE ATTIC WHEN A HOME IS BROUGHT INTO CODE
 COMPLIANCE BY SECTION R402.
 4) IF THE AIR HANDLER IS TO REMAIN IN THE ATTIC, REVISE
 THE PLAN TO SHOW COMPLIANCE WITH THE FOLLOWING R403.2.4
 REQUIREMENTS:
 A) THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 B) A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 C) THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 D) A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 4) PROVIDE THE DIMENSIONS OF THE MAIN R/A GRILL AND
 INDICATE HOW AIR WILL BE RETURNED TO THE AIR HANDLER-
 THERE IS NO DUCT FROM THE GRILL TO THE UNIT.
 5) THE SUPERIOR WOOD BURNUING FIREPLACE MUST BE IN
 COMPLIANCE WITH R1005.3 SOLID-FUEL APPLIANCES.
 FACTORY-BUILT CHIMNEYS INSTALLED IN DWELLING UNITS WITH
 SOLID-FUEL-BURNING APPLIANCES SHALL COMPLY WITH THE
 TYPE HT REQUIREMENTS OF UL 103 AND SHALL BE MARKED
 "TYPE HT" AND "RESIDENTIAL TYPE AND BUILDING HEATING
 APPLIANCE CHIMNEY"
 6) THE SUPERIOR FIREPLACE MUST BE IN COMPLIANCE WITH
 EITHER SECTION G2434.1 OR G2435.1 WHICH REQUIRES
 APPROVALS IN ACCORDANCE WITH ANSI Z21.50 OR Z21.88
 RESPECTIVELY. THE SUBMITTAL FOR THE FIREPLACE IS
 INDICATING COMPLIANCE WITH ANSI Z21.60 OR Z21.84.
 7) INDICATE HOW OUTSIDE OR EXTERIOR AIR FOR COMBUSTION
 WILL BE PROVIDED TO THE FIREPLACE- REFER TO SECTION
 R1006.1.)
 8) REFER TO SECTION M1401.4 AND PROVIDE THE
 MANUFACTURER'S SPECIFICATIONS FOR ANCHORING THE
 EXTERIOR CONDENSER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-05-04 Cont ID  
Sent By gearl Date 2016-05-04 Time 15:58 Rev Time 0.00
Received By gearl Date 2016-05-04 Time 15:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-28 Cont ID  
Sent By tklarge Date 2016-01-28 Time 06:49 Rev Time 0.00
Received By tklarge Date 2016-01-28 Time 06:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-02-09 Cont ID  
Sent By cthroop Date 2016-02-09 Time 15:17 Rev Time 0.00
Received By cthroop Date 2016-02-09 Time 15:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-05-31 Cont ID  
Sent By njwira Date 2016-05-31 Time 14:40 Rev Time 0.00
Received By njwira Date 2016-05-31 Time 14:40 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-05-25 Cont ID  
Sent By njwira Date 2016-05-25 Time 09:46 Rev Time 0.00
Received By njwira Date 2016-05-12 Time 09:45 Sent To  
Notes
2016-05-25 14:48:335/25/16- FAILED- MISSING PAGE 2 WITH THE BUILDING
 ELEVATIONS.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-01 Cont ID  
Sent By sgraham Date 2016-02-01 Time 13:32 Rev Time 0.00
Received By sgraham Date 2016-02-01 Time 13:32 Sent To  
Notes
2016-02-01 13:34:152/1/16 ZONING FAILED
  
 1. SUBMIT TWO CERTIFIED SURVEYS SHOWING LOCATION OF
 ADDITION