Plan Review Details - Permit 16010661
Plan Review Stops For Permit 16010661
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-05-06 Cont ID  
Sent By skennedy Date 2016-05-06 Time 14:57 Rev Time 0.00
Received By skennedy Date 2016-05-06 Time 14:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2016-05-06 Time 07:01 Sent To  
Notes
2016-05-06 07:17:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010661
 ADD: 505 CLEMATIS ST.
 CONT: WELLINGTON EQUESTRIAN
 TEL: 561-296-3090
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. MAY 06/ 2016
 ACTION: DENIED
  
 1) CONTRACTOR FAILED TO COLATE NEW SHEETS AND INSTALL
 NEW SHEETS IN THE PERMIT PACKAGE SEET OF PLANS AND
 REMOVE OLD SHEETS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-22 Cont ID  
Sent By jwitmer Date 2016-03-22 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2016-03-22 Time 06:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-29 Cont ID  
Sent By   Date 2016-01-29 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2016-01-29 Time 06:04 Sent To  
Notes
2016-01-29 07:06:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010661
 ADD: 505 CLEMATIS ST.
 CONT: WELLINGTON EQUESTRIAN
 TEL: 561-296-3090
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 29/ 2016
 ACTION: DENIED
  
 1) SHEET LS1 THE WORK THAT IS BEING COMPLETED IN THE
 NEW TENANT SPACE. THE PLAN DOESN'T SHOW THECURRENT
 CONFIGURATION OF THE OUTSIDE SEASONAL SEATING. WITH THE
 ADDITIONAL OCCUPANT LOADS WITH THE SEASONAL SEATING THE
 OCCUPANT LOAD SERVED WILL WELL BE OVER 50 MAKING THIS
 SPACE AN A2 OCCUPANCY, 2014 FBC-B 303.3.
 ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK
 CONSUMPTION INCLUDING OR A MIXES USE OCCUPANCY SINCE
 THERE IS ALSO A MERCANTILE ELEMENT SEE FBC-B 309.1.
 WITH A MIXED USE OCCUAPNCY THE DESIGNER WILL NEED TO
 DECLARE IS THE DESIGN FOR THE MIXED USE IS SEPERATED
 PER SECTION FBC-B 508.2.4 OR NON-SEPERATED PER SECTION
 FBC-B 508.3.1 OF THE 2014 FBC-B.
  
 2) 2014 EXISITNG BUILDING CODE 1001.3.1 PARTIAL CHANGE
 OF OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY.
 WITH A MIXED USE OCCUAPNCY THE DESIGNER WILL NEED TO
 DECLARE IS THE DESIGN FOR THE MIXED USE IS SEPERATED
 PER SECTION FBC-B 508.2.4 OR NON-SEPERATED PER SECTION
 FBC-B 508.3.1 OF THE 2014 FBC-B.
  
 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION AND THAT PORTION IS NOT
 SEPARATED FROM THE REMAINDER OF THE BUILDING WITH FIRE
 BARRIERS HAVING A FIRE-RESISTANCE RATING AS REQUIRED IN
 THE FLORIDA BUILDING CODE, BUILDING FOR THE SEPARATE
 OCCUPANCY, THE ENTIRE BUILDING SHALL COMPLY WITH ALL OF
 THE REQUIREMENTS OF CHAPTER 9 APPLIED THROUGHOUT THE
 BUILDING FOR THE MOST RESTRICTIVE OCCUPANCY
 CLASSIFICATION IN THE BUILDING AND WITH THE
 REQUIREMENTS OF THIS CHAPTER.
  
 1012.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
 WHERE A PORTION OF AN EXISTING BUILDING THAT IS CHANGED
 TO A NEW OCCUPANCY CLASSIFICATION AND THAT PORTION IS
 SEPARATED FROM THE REMAINDER OF THE BUILDING WITH FIRE
 BARRIERS HAVING A FIRE-RESISTANCE RATING AS REQUIRED IN
 THE FLORIDA BUILDING CODE, BUILDING FOR THE SEPARATE
 OCCUPANCY, THAT PORTION SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS OF CHAPTER 9 FOR THE NEW OCCUPANCY
 CLASSIFICATION AND WITH THE REQUIREMENTS OF THIS
 CHAPTER.
  
 3) 2014 EXISITNG BUILDING CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 3A) PLEASE SHOW COMPLIANCE WITH: 2014 FBC-ACCESSIBILITY
 CODE 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 3B) PLEASE SHOW COMPLIANCE WITH: 226.2 DISPERSION.
 DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES.
  
 3C) PLEASE SHOW COMPLIANCE WITH: 902.3 HEIGHT. THE TOPS
 OF DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 3D) THE LIFE SAFETY PLAN SHOWS TABLES WITH STACKED
 COFFEE BEAN BAGS, DISPLAY TABLES AND WHAT APPEARS TO BE
 KIOSK. PLEASE SHOW COMPLIANCE WITH:902.1 GENERAL.
 WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38
 INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. THE TOP OF THE COUNTER EDGE PROTECTION SHALL BE
 2 INCHES (51 MM) MAXIMUM ABOVE THE TOP OF THE COUNTER
 SURFACE ON THE AISLE SIDE OF THE CHECK-OUT COUNTER.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 4) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-21 Cont ID  
Sent By mvaldes Date 2016-03-21 Time 11:02 Rev Time 0.00
Received By mvaldes Date 2016-03-21 Time 11:02 Sent To  
Notes
2016-03-21 11:10:13REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PERMIT WILL BE ISSUED WITH A PROVISO FROM PREVIOUS
 COMMENTS
  
 - SUBJECT TO FIELD INSPECTOR TO VERIFY ON SITE AT THE
 THE TIME OF SCHEDULED INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-25 Cont ID  
Sent By mvaldes Date 2016-01-25 Time 18:26 Rev Time 0.00
Received By mvaldes Date 2016-01-25 Time 18:26 Sent To  
Notes
2016-01-25 18:31:53FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 PROVISO :
  
 -AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF
 A
 SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR
 MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA MEASURED
 HORIZONTALLY
 AT ITS MAXIMUM WIDTH. NEC 210.62
  
 -NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
  
 -NEC 600.5(A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE OUTLET
 IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH
 TENANT SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE.
 THE OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT
 RATED AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD.
 SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-28 Cont ID  
Sent By scaldero Date 2016-04-28 Time 11:39 Rev Time 0.00
Received By scaldero Date 2016-04-28 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-26 Cont ID  
Sent By scaldero Date 2016-01-26 Time 12:36 Rev Time 0.00
Received By scaldero Date 2016-01-26 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-09 Cont ID  
Sent By tklarge Date 2016-05-09 Time 10:04 Rev Time 0.00
Received By tklarge Date 2016-05-06 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2016-04-25 Time 08:27 Sent To  
Notes
2016-04-26 08:27:44B16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-24 Cont ID  
Sent By tklarge Date 2016-03-24 Time 12:50 Rev Time 0.00
Received By tklarge Date 2016-03-16 Time 11:43 Sent To  
Notes
2016-03-17 11:44:02B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-29 Cont ID  
Sent By jwitmer Date 2016-02-08 Time 14:25 Rev Time 0.00
Received By skennedy Date 2016-01-21 Time 13:52 Sent To  
Notes
2016-01-22 13:52:33B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-05-09 Cont ID  
Sent By jwitmer Date 2016-05-09 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2016-05-09 Time 14:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-29 Cont ID  
Sent By jwitmer Date 2016-01-29 Time 6:56 Rev Time  
Received By jwitmer Date 2016-01-29 Time 06:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-03-22 Cont ID  
Sent By ccole Date 2016-03-22 Time 11:00 Rev Time 0.00
Received By ccole Date 2016-03-22 Time 11:00 Sent To  
Notes
2016-03-22 11:01:47MECHANICAL PROVISO:
 3/22/16
  
 SEPARATE PERMIT REQUIRED FOR THE WALK-IN COOLER AND
 REFRIGERATION SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By ccole Date 2016-02-08 Time 10:57 Rev Time 0.00
Received By ccole Date 2016-02-08 Time 10:57 Sent To  
Notes
2016-02-08 11:00:101ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING.
 PERMIT #16010661
 2/8/16
  
 1) THE PROPOSED EXPANSION OF THE COFFEE SHOP INTO THE
 FORMER BAKERY SPACE IS CLASSIFIED AS A CHANGE OF
 OCCUPANCY PER SECTION 1001.3.1 FBC-14 EXISTING BUILDING
 CODE. PLEASE PROVIDE MINIMUM VENTILATION CALCULATIONS
 FOR THE CHANGED ROOMS AND SPACES IN COMPLIANCE WITH
 TABLE 403.3 FBC-14 MECHANICAL. INDICATE HOW MANY CFM'S
 OF OUTSIDE AIR ARE REQUIRED PER THE TABLE, AND HOW MANY
 CFM'S ARE BEING PROVIDED BY THE EXISTING AC SYSTEMS OR,
 TO BE PROVIDED BY MODIFIED OR CHANGED AC SYSTEMS.
 PLEASE NOTE THAT MINIMUM EXHAUST RATE FOR THE KITCHEN
 IS 0.7 CFM PER SQ. FT, HOWEVER CURRENTLY THERE IS NO
 EXHAUST SYSTEM INDICATED ON THE PLANS.
 2) A SEPARATE PERMIT FOR A TYPE II EXHAUST HOOD IS
 REQUIRED FOR THE NEW CONVECTION OVEN. PLEASE SEE
 SECTION 507.2.2 AND SUBMIT MANUIFACTURER'S
 SPECIFICATIONS FOR THE OVEN AND PROVIDE AN AIR BALANCE
 CALCULATION ON THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2016-05-09 Cont ID  
Sent By tklarge Date 2016-05-09 Time 10:04 Rev Time 0.00
Received By tklarge Date 2016-05-09 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2016-05-05 Cont ID  
Sent By tklarge Date 2016-05-05 Time 13:29 Rev Time 0.00
Received By tklarge Date 2016-05-05 Time 13:14 Sent To  
Notes
2016-05-05 13:21:441) THE ZURN SPECIFICATION SHEET SHOWS A 3 INCH INLET
 AND OUTLET BUT THE PLUMBING SANITARY RISER SHOWS A 2
 INCH INLET AND OUTLET. CLARIFY.
 2) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE SIDE OF
 THE GREASE TRAP PER CITY ORD.
 3) THE SANITARY RISER FOR THE NEW PLUMBING ( FLOOR
 SINKS, PROPOSED HAND SINK, REROUTED FLOOR SINK, ETC.)
 DOES NOT COMPLY WITH 2014 FPC SEC.905.3 FOR THE WAY THE
 VENTS CONNECT TO THE DRAINAGE SYSTEM. SUBMIT A SANITARY
 RISER THAT COMPLIES WITH THE 2014 FPC.
 4) THE PLANS NEED TO BE COMPILED INTO TWO COMPLETE SETS
 FOR SUBMITTAL. FBC 107.1.
 5) THE GAS SHALL BE SUBMITTED UNDER A SEPARATE.
 6) THE WATER RISER STILL SHOWS THE TANKLESS WATER
 HEATER AS EXISTING. IT IS NOT EXISTING. IT IS NEW. IT
 REPLACED AN EXISTING ELECTRIC TANKLESS WATER HEATER.
 SHOW IT AS NEW ON THE RISER.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-05-04 Cont ID  
Sent By gearl Date 2016-05-04 Time 15:29 Rev Time 0.00
Received By gearl Date 2016-05-04 Time 15:29 Sent To  
Notes
2016-05-04 15:31:26 
  
  
  
 1. NO CORRECTION HAVE BE DONE ON PLANS -- 2ND REQUEST
 FOR CORRECTIONS
  
 GEORGE EARL PLUMBING PLANS REVIEWER 0013B

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-24 Cont ID  
Sent By tklarge Date 2016-03-24 Time 12:50 Rev Time 0.00
Received By tklarge Date 2016-03-23 Time 03:40 Sent To  
Notes
2016-03-23 13:59:271) THE TANKLESS WATER HEATER WAS SHOWN AS ELECTRIC ON
 THE PLANS FOR PERMIT # 11090836 FOR THIS SPACE.THE
 WATER HEATER WAS ALSO SHOWN ON THE OPPOSITE SIDE OF THE
 SPACE THAN WHERE IT IS NOW. CITY RECORDS DO NOT SHOW
 ANY ADDITIONAL PERMITS FOR THE RELOCATION OF THE
 TANKLESS WATER HEATER NOR FOR THE INSTALLATION OF THE
 GAS. THEREFORE, THE GAS TANKLESS WATER HEATER SHALL NOT
 BE NOTED AS EXISTING ON THE PLANS, IT SHALL BE SHOWN AS
 NEW SINCE IT WAS NEVER PERMITTED AND SHALL BE INCLUDED
 IN THIS SCOPE OF WORK. FBC 105.1.SEE COPIES OF FLOOR
 PLAN IN FOLDER. THE SUBMITTED PICTURE SHOWS A FAIRLY
 NEW TANKLESS WATER HEATER.
 2) SINCE THIS IS A CHANGE OF OCCUPANCY AND COMBINATION
 OF SPACE, THE PLANS WILL BE REQUIRED TO BE REVIEWED BY
 THE DEPT. OF BUSINESS AND PROFESSIONAL REGULATION,
 DIVISION OF HOTELS AND RESTAURANTS. SECOND REQUEST.
 3) SHT. LS-1 SHOWS THE OCCUPANT LOAD AS 150 PERSONS ON
 THE PLUMBING FIXTURE CALCULATION TABLE AND ALSO ON THE
 PLAN. I DO NOT SEE WHERE THE SEATS AND BENCH LOCATED ON
 THE EXTERIOR OF THE BUILDING ON THE SOUTH END OF THE
 STRUCTURE HAVE BEEN INCLUDED IN THE OCCUPANT LOAD.
 CLARIFY.SUBMIT A TOTAL OCCUPANT LOAD.
 4) THE NEW FLOOR SINKS ARE STILL NOT VENTED IN
 ACCCORDANCE WITH2014 FBC, PLUMBING SEC.901.2.1.
 5) SEE THE FOLLOWING REQUIREMENTS FOR A PROPER GAS
 REVIEW FOR THE GAS TANKLESS WATER HEATER.
  
 A).SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 B.)SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
 C)TYPE OF GAS (LP OR NATURAL).
 D) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
 E)SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 F)SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
 G)INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON
 THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
 H)SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
 I)SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
 6) SHT. P-1 - FLOW RATE CALCULATIONS - UNDER THE
 MULTIPLE FIXTURE DESIGN- EXPLAIN WHY ONLY 50% OF THE 2
 COMPARTMENT SINK IS BEING ADDED TO THE FLOW RATE
 INSTEAD OF THE CALCULATED FLOW RATE OF 22.85 GPM.
 7) SUBMIT A MANUFACTURER'S INSTALLATION MANUAL FOR THE
 GREASE INTERCEPTOR.WHERE IS THE VENTED INLET FLOW
 CONTROL DEVICE ON THE GREASE INTERCEPTOR?
 8) SHT. A-1 SHOWS THE GREASE INTERCEPTOR LOCATED IN THE
 WALK IN COOLER. THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING OFFICIAL
 PER 2014 FPC SEC.1003.2.PLEASE EXPLAIN HOW THIS
 LOCATION MAKES THE INTERCEPTOE ACCESSIBLE FOR
 MAINTENANCE AND REPAIR.
 (9 THE FOLLOWING TEXT IS FROM THE CWPB CODE OF
 ORDINANCES SEC.90-125 (7)
 INTERCEPTORS ARE TO BE INSTALLED OUTSIDE OF THE FOOD
 PREPARATION AREA WITH THE DISHWASHER DISCHARGING VIA A
 SEPARATE LINE.
 EACH INTERCEPTOR SHALL BE SO INSTALLED AS TO PROVIDE
 READY ACCESSIBILITY TO THE COVER, AND MEANS FOR
 SERVICING AND MAINTAINING THE INTERCEPTOR IN WORKING
 AND OPERATING CONDITION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-28 Cont ID  
Sent By tklarge Date 2016-01-28 Time 10:49 Rev Time 0.00
Received By tklarge Date 2016-01-27 Time 06:30 Sent To  
Notes
2016-01-28 10:15:161) THE PLANS NOTE THIS OCCUPANCY AS "MERCANTILE." THE
 PROPER OCCUPANCY CLASSIFICATION IS A-2 BASED ON THE
 OCCUPANT LOAD PER THE 2014 FBC SEC. 303.3. SINCE THIS
 WILL BE A CHANGE OF OCCUPANCY, COMPLIANCE WITH CHAPTER
 10 OF THE 2014 FBC-EXISTING BUILDING IS ALSO REQUIRED.
 2) SHT.LS-1 - THERE IS A NOTE ON THE PLAN NEXT TO ONE
 OF THE TABLES THAT READS" PROPOSED SERVICE SINK" BUT
 NOTHING IS SHOWN. CLARIFY.A SERVICE SINK IS REQUIRED BY
 2014 FBC TABLE 403.1.
 3) THIS SPACE ALSO HAS OUTDOOR SEATING ON THE FRONT AND
 ALSO ON THE SIDE. THESE SEATS SHALL ALSO BE INCLUDED IN
 THE OCCUPANT LOAD OF THE SPACE.FBC-PLUMBING
 SEC.403.1.4.
 4) SHT. LS-1 - THE PLUMBING FIXTURE CALCULATION TABLE
 SHOWS 4 WATER CLOSETS AND FOUR LAVATORIES BEING
 PROVIDED FOR THE MALES AND FEMALES WHEN IN THE FACT THE
 FIXTURE COUNT IS TWO WATER CLOSETS AND TWO LAVATORIES
 FOR THE MALES AND FEMALES. REVISE THE TABLE TO REFLECT
 THE CORRECT FIXTURE COUNT FOR THE OCCUPANT LOAD.
 5) SINCE THIS IS A CHANGE OF OCCUPANCY AND COMBINATION
 OF SPACE, THE PLANS WILL BE REQUIRED TO BE REVIEWED BY
 THE DEPT. OF BUSINESS AND PROFESSIONAL REGULATION,
 DIVISION OF HOTELS AND RESTAURANTS.
 6) THE ICE MACHINE SHALL BE EQUIPPED WITH A BACKFLOW
 PREVENTER ON THE WATER SUPPLY LINE PER THE 2014
 FBC-PLUMBING SEC.608.3.
 7) SUBMIT REVISED CALCULATIONS AND THE CAPACITY OF THE
 EXISTING GREASE INTERCEPTOR TO ENSURE THAT THE EXISTING
 INTERCEPTOR HAS THE CAPACITY TO HANDLE THE ADDITIONAL
 LOAD FROM THE ADDED SPACE.2014 FBC-PLUMBING SEC.1003.2.
 8) ALL SINKS/LAVATORIES SHALL BE EQUIPPED WITH HOT
 WATER PER THE 2014 FBC-PLUMBING SEC. 607.1.
 9) CLEANOUTS ARE REQUIRED IN THE BASE OF WASTE STACKS
 PER 2014 FBC-PLUMBING SEC.708.3.4.
 10) THE DRAIN FOR THE ESPRESSO MACHINE IS NOT VENTED.
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER.
 12) THE NEW FLOOR SINKS SHALL BE TRAPPED PER 2014 FBCP
 SEC.802.2.
 13) SHT.E-2 - ELECTRIC PANEL B2 SHOWS THE TANKLESS
 WATER HEATER AS GAS. SUBMIT A GAS PIPING RISER DIAGRAM
 FOR REVIEW. PERMIT #11120186 SHOWS THIS TANKLESS WATER
 HEATER AS ELECTRIC. CLARIFY.
 14) SHOW THE PIPE SIZES ON THE WATER RISER.
 15) SHT. P-1 - THERE IS A REROUTED EXISTING FLOOR SINK
 ON THE RISER DIAGRAM THAT APPEARS TO CONNECT NOWHERE.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  