Plan Review Details - Permit 16010542
Plan Review Stops For Permit 16010542
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-01-20 Cont ID  
Sent By tklarge Date 2016-01-20 Time 06:11 Rev Time 0.00
Received By tklarge Date 2016-01-20 Time 06:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-05 Cont ID  
Sent By tklarge Date 2016-04-05 Time 05:52 Rev Time 0.00
Received By tklarge Date 2016-04-05 Time 05:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-20 Cont ID  
Sent By tklarge Date 2016-01-20 Time 06:11 Rev Time 0.00
Received By tklarge Date 2016-01-19 Time 15:44 Sent To  
Notes
2016-01-19 15:44:58PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By tklarge Date 2016-04-05 Time 05:52 Rev Time 0.00
Received By tklarge Date 2016-04-05 Time 05:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-20 Cont ID  
Sent By tklarge Date 2016-01-20 Time 06:09 Rev Time 0.00
Received By tklarge Date 2016-01-20 Time 05:47 Sent To  
Notes
2016-01-20 06:09:131) THE PIPING SCHEMATIC THAT WAS SUBMITTED DOES NOT
 SHOW ANY PIPE SIZES.SIZE ALL PIPING ON THE SCHEMATIC
 AND SHOW THE TYPE OF PIPE MATERIAL.. WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
 2) THE ARE LETTERS ON THE PIPING SCHEMATIC IDENTIFYING
 THE SPECIFIC PARTS BUT THERE IS NO LEGEND EXPLAINING
 WHAT THESE ITEMS SRE. I CANNOT PERFORM A COMPREHENSIVE
 REVIEW WHEN THE PLANS LACK SUCH INFORMATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved