Plan Review Details - Permit 16010539
Plan Review Stops For Permit 16010539
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-21 Cont ID  
Sent By ccole Date 2016-01-21 Time 11:21 Rev Time 0.00
Received By ccole Date 2016-01-19 Time 14:48 Sent To  
Notes
2016-01-20 14:48:26REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-21 Cont ID  
Sent By ccole Date 2016-01-21 Time 13:20 Rev Time 0.00
Received By ccole Date 2016-01-21 Time 13:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-21 Cont ID  
Sent By ccole Date 2016-01-21 Time 11:21 Rev Time 0.00
Received By ccole Date 2016-01-21 Time 11:21 Sent To  
Notes
2016-01-21 11:25:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010539
 1/21/16
  
 1) THE PLAN INDICATES 300 CFM'S OF AIR BEING RETURNED
 FROM THE BEDROOM WHERE ONLY 196 CFM'S OF AIR IS BEING
 SUPPLIED- PLEASE CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  