Plan Review Details - Permit 16010532
Plan Review Stops For Permit 16010532
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-01-19 Cont ID  
Sent By shill Date 2016-01-19 Time 14:20 Rev Time 0.00
Received By shill Date 2016-01-19 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-17 Cont ID  
Sent By albarran Date 2016-02-16 Time 19:28 Rev Time 0.00
Received By albarran Date 2016-02-16 Time 18:51 Sent To I
Notes
2016-02-17 14:57:48I RECEIVED AN EMAIL FROM THE CONTRACTOR WITH THE NEEDED
 EXPLANATION.
2016-02-16 19:29:19PENDING ISSUE WITH MISMATCH DEMO ITEMS. AS SOON AS THIS
 IS EXPLAINED AND CORRECTED THIS CAN BE APPROVED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-04 Cont ID  
Sent By albarran Date 2016-02-04 Time 15:33 Rev Time 0.00
Received By albarran Date 2016-02-04 Time 14:00 Sent To  
Notes
2016-02-04 15:33:401ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. SHEET E1.0 MARK ON DEMO PLANS THE POLES BEING
 REMOVED.
 2. SHEET ES1.1 YOU NEED TO INDICATE ON THE PLANS THE
 LOCATION OF THE POWER SOURCE FOR THE SITE LIGHTING.
 3. SHEET ES1.1 PER FBC-EC405.2.4 EXTERIOR LIGHTING
 CONTROLS COMPLIANT WITH THIS SECTION IS MANDATORY.
 4. SHEET ES1.1 EXTERIOR LIGHTING SHALL COMPLY WITH
 FBC-EC405.6 YOU NEED TO SUBMIT A LIGHTING POWER DENSITY
 ALLOWANCE CHART TO INDICATE COMPLIANCE.
 5. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN
 FOR INSPECTION. NOT SITE TUBES WILL BE ALLOWED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-18 Cont ID  
Sent By lmarchan Date 2016-02-18 Time 16:01 Rev Time 0.00
Received By lmarchan Date 2016-02-16 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-04 Cont ID  
Sent By lmarchan Date 2016-02-04 Time 15:47 Rev Time 0.00
Received By lmarchan Date 2016-01-19 Time 09:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-02-19 Cont ID  
Sent By skennedy Date 2016-02-19 Time 13:26 Rev Time 0.00
Received By skennedy Date 2016-02-19 Time 13:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-02-04 Cont ID  
Sent By jroach Date 2016-02-04 Time 09:50 Rev Time 0.00
Received By jroach Date 2016-02-04 Time 09:50 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved