Plan Review Details - Permit 16010523
Plan Review Stops For Permit 16010523
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2017-01-11 Cont ID  
Sent By jgomez Date 2017-01-11 Time 16:40 Rev Time 0.00
Received By jgomez Date 2017-01-11 Time 14:55 Sent To M
Notes
2017-01-11 15:09:49 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2016-12-05 Cont ID  
Sent By jgomez Date 2016-12-05 Time 15:47 Rev Time 0.00
Received By jgomez Date 2016-12-05 Time 15:51 Sent To  
Notes
2016-12-05 11:42:34RESIDENTIAL (R3) ALTERATION SIXTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- NEW ENERGY CALCULATIONS SUBMITTED (FORM R405-2014):
 A) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) CLARIFY WHY THE COOLING SYSTEM IS ONLY 12.8 KBTU/HR,
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) ATTIC INFORMATION ON PAGE 2 OF 4 SPECIFIES A VENT
 RATIO OF 1/300. TYPICALLY, THE VENTILATION RATIO IS
 1/150. IN ORDER TO USE THE 1/300 VENT RATIO, THE
 ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE AS REQUIRED BY
 THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL, 5TH
 EDITION (2014). OTHERWISE, REVISE THE VENT RATIO TO
 1/150.
  
 D) THE EPL DISPLAY CARD NEEDS TO BE SIGNED BY THE
 BUILDER. ONLY THE NAME OF THE BUILDER WAS PROVIDED. THE
 SIGNATURE DOESN'T MATCH SIGNATURE SHOWN ON THE PERMIT
 APPLICATION. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 E) ENGINEER OF RECORD COMPLETING THE ENERGY
 CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S WHEN SUBMITTING
 DOCUMENTATION FOR PUBLIC RECORDS.
  
 NOTE:
 LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ARE
 REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT TAKING
 THE SOFTWARE DEFAULT FACTORS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2016-11-29 Cont ID  
Sent By jgomez Date 2016-11-29 Time 16:41 Rev Time 0.00
Received By jgomez Date 2016-11-29 Time 14:21 Sent To  
Notes
2016-11-29 14:36:25RESIDENTIAL (R3) ALTERATION FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL SUBMIT REQUIRED INFORMATION
 PRIOR TO INSPECTIONS TO AVOID DELAYS/CONFLICTS.
 REVISION FEES WILL APPLY EACH TIME INFORMATION IS
 RESUBMITTED. CONTRACTOR TO ADVICE IF PROVISO OPTION IS
 PREFERRED AT THIS TIME OR IF RESUBMITTING REQUIRED
 INFORMATION PRIOR TO ISSUING PERMIT.
  
  
 NEW COMMENT BASED ON THE ENERGY CALCULATIONS SUBMITTED:
 1- DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE INTERIOR AND
 EXTERIOR INSULATION REQUIREMENTS AS REQUIRED BY ENERGY
 CALCULATIONS SUBMITTED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 2- ENERGY CALCULATIONS SUBMITTED:
  
 NOTE: KEEP IN MIND THAT ENERGY CALCULATION SUBMITTED
 ARE DONE FOR THE ENTIRE HOUSE. ALL OF THE COMMENTS
 BELOW APPLY TO THE ENTIRE HOUSE.
  
  
 A) REVISE INFORMATION ON TABLE R402A SUBMITTED:
 (1) MASONRY WALLS REQUIRE "INSULATION ON WALL INTERIOR"
 OF R-4 AND "INSULATION ON WALL EXTERIOR" OF R-3. THE
 "INSTALLED VALUES" COLUMN WAS NOT COMPLETED. NEED TO
 COMPLETE THE "INSTALLED VALUES" COLUMN. (NOTE: SEE NOTE
 #4 AT THE BOTTOM OF THIS TABLE). SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 (2) THE CEILING INFORMATION WAS NOT COMPLETED ON THE
 "INSTALLED VALUES" COLUMN. NEED TO COMPLETE THE
 "INSTALLED VALUES" COLUMN. SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 (3) THE AIR HANDLER UNIT IS NOT ALLOWED IN THE ATTIC.
 REVISE THE "INSTALLED VALUES" COLUMN AS REQUIRED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 (4) THE ELECTRIC WATER HEATER EF VALUE SHOWN ON THE
 "INSTALLED VALUES" COLUMN DOESN'T COMPLY WITH THE
 PRESCRIPTIVE REQUIREMENTS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
  
 B) REVISE INFORMATION ON TABLE R402B SUBMITTED;
 (1) THE WATER HEATER COMPONENT WAS NOT CHECKED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
  
 C) THE HEATING INFORMATION SHOWN ON THE ENERGY
 CALCULATIONS ITEM #13A AND #13B DOESN'T MATCH TABLE
 R402A AND EQUIPMENT INFORMATION SHOWN ON THE MECHANICAL
 PLAN. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) PERSON DOING THE ENERGY CALCULATIONS NEED TO
 COORDINATE INFORMATION SHOWN ON THE FRONT PAGE OF THE
 ENERGY CALCULATIONS WIT INFORMATION SHOWN ON TABLE
 R402A. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
  
 NOTE: IF UNABLE TO COMPLY WITH THE ABOVE REQUIREMENTS
 USING THE PRESCRIPTIVE FORM R402-2014 SUBMITTED, THEN
 PERFORMANCE METHOD FORM R405-2014 MAY BE USED INSTEAD.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-10-27 Cont ID  
Sent By jgomez Date 2016-10-26 Time 16:38 Rev Time 0.00
Received By jgomez Date 2016-10-26 Time 15:35 Sent To M
Notes
2016-10-26 16:42:36RESIDENTIAL (R3) ALTERATION FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) INFORMATION SUBMITTED IS INCOMPLETE. MISSING TABLES
 R402A AND TABLE R402B. AND, BOTH NEED TO BE COMPLETE
 BEFORE SUBMITTAL.
  
 B) REVISE WALL TYPE AND INSULATION SHOWN ON ITEM #9.
 NEED TO SPECIFY THE INSULATION ON THE INTERIOR OF THE
 MASONRY WALL AND THE INSULATION ON THE EXTERIOR OF THE
 MASONRY WALL. NOTE: CALCULATIONS SUBMITTED ARE FOR THE
 ENTIRE HOUSE. THIS REQUIREMENTS APPLIES TO ALL EXISTING
 EXTERIOR WALLS. NEED TO PROVIDE PROOF THAT EXISTING
 WALLS WILL MEET THIS CRITERIA. ALSO, NEED TO SPECIFY
 THE INFILL WOOD FRAME WALL INSTALLED TO CLOSE THE
 EXISTING GARAGE DOOR OPENING. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: IF UNABLE TO COMPLY WITH THE ABOVE REQUIREMENTS
 USING THE PRESCRIPTIVE FORM R402-2014 SUBMITTED, THEN
 PERFORMANCE METHOD FORM R405-2014 MAY BE USED INSTEAD.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HORIZONTAL SLIDER WINDOWS THAT MEET THE CALCULATED
 DESIGN PRESSURES FOR THE HORIZONTAL SLIDERS IN THE
 LIVING ROOM. DRAWINGS SUBMITTED WITH FLORIDA PRODUCT
 APPROVAL FL15814-R2 DON'T MEET THE DESIGN PRESSURES
 SHOWN ON DRAWING A1.
  
 B) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL14569 DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. REPEAT
 COMMENT. THREE TIMES.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NEW COMMENTS:
 4- WINDOWS SHOWN ON DRAWING A1 WERE REVISED. THE
 FOLLOWING REVISIONS ARE REQUIRED:
 A) WINDOW SIZES FOR BEDROOM #3 DON'T COMPLY WITH THE
 EGRESS REQUIREMENTS. CLEARLY SPECIFY SIZE AND TYPE OF
 EXISTING WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 704 FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
  
 B) REVISE EXTERIOR ELEVATIONS ON SHEET A2 TO MATCH
 REVISED WINDOWS ON SHEET A1. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-06-07 Cont ID  
Sent By jgomez Date 2016-06-07 Time 18:45 Rev Time 0.00
Received By jgomez Date 2016-06-07 Time 07:50 Sent To  
Notes
2016-06-06 18:48:42RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 ****NOTE:
 THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND,
 THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE
 PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL
 DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON
 PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON
 THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED
 AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE
 NOT ALLOWED.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
 RESPONSE: REPEAT COMMENT (3 TIMES). NOT ADDRESSED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL15699-R2 DON'T MATCH. DRAWINGS
 SUBMITTED ARE FOR THE SH 3700 SERIES WINDOWS, WHILE
 FLORIDA PRODUCT APPROVAL FL15699-R2 IS FOR THE SH 3100
 SERIES WINDOWS. PROVIDE PRODUCT APPROVAL AND DRAWINGS
 THAT MATCH.
 RESPONSE: FLORIDA PRODUCT APPROVAL FL13406-R1 SUBMITTED
 NOW IS FOR HORIZONTAL SLIDER WINDOWS. THERE ARE NO
 HORIZONTAL SLIDER WINDOWS SPECIFIED ON PLANS. THIS
 FLORIDA PRODUCT APPROVAL IS FOR THE 2010 CODE VERSION.
 NEED PRODUCT APPROVAL FOR THE CURRENT 2014 CODE
 VERSION. THIS PRODUCT APPROVAL IS FOR NON-IMPACT
 WINDOWS (NON-IMPACT WINDOWS REQUIRE HURRICANE
 SHUTTERS). PROVIDE PRODUCT APPROVAL FOR THE WINDOW THAT
 IS SPECIFIED ON PLANS.
  
 NEW COMMENT:
 B) HURRICANE SHUTTERS IF THE WINDOWS AND DOORS DON'T
 HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE. PLEASE, CONTACT ME TO GUIDE
 YOU HOW TO GET THE CITY SAMPLE.
  
 ORIGINAL COMMENT:
 C) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL13540-R3 DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. ALSO,
 THE DRAWINGS ARE NOT LEGIBLE. PROVIDE PRODUCT APPROVAL
 THAT MEETS THE CALCULATED DESIGN PRESSURES AND PROVIDE
 LEGIBLE COPIES.
 RESPONSE: DOORS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL13540 DON'T MEET THE CALCULATED DESIGN PRESSURES.
 REPEAT COMMENT. NEED DOOR THAT MEETS THE CALCULATED
 DESIGN PRESSURES.
  
 ORIGINAL COMMENT:
 D) WINDOW MULLIONS:
 (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS
 FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014.
 (REPEAT COMMENT).
 (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). (REPEAT COMMENT).
 RESPONSE: COMMENTS NOT ADDRESSED AT ALL.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-10 Cont ID  
Sent By jgomez Date 2016-05-09 Time 18:39 Rev Time 0.00
Received By jgomez Date 2016-05-09 Time 18:36 Sent To M
Notes
2016-05-09 18:41:41RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- SCOPE OF WORK WAS CHANGED. REVISED PLANS SHOW
 CONVERSION OF THE GARAGE AND PORCH TO BEDROOMS. BRING
 PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT
 FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 3- SHEET A1:
 A) ENGINEER OF RECORD TO PROVIDE FRAMING DETAILS AND
 SPECIFICATIONS FOR THE INFILL OF ALL OPENINGS IN THE
 EXISTING PORCH AND GARAGE. SEC. R301.1 FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 B) NOTE #1 OF SCOPE OF WORK SAYS "DEMOLISH ENTIRE
 REMAINS OF THE FIRE DAMAGED ROOF AND INSTALL TOTALLY
 NEW ROOF". PLANS DON'T SHOW AREA OF FIRE AND DON'
 PROVIDE ANY SPECIFICATIONS REGARDING THE REQUIRED
 REPAIRS. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW THE AREA IS REPAIRED. SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) CLARIFY INFORMATION SHOWN ON THE "SPECIAL NOTES":
 WHAT'S "FEBC"?.. WHAT'S "ALTERATION LEVEL 11"?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) DOOR AND WINDOW SCHEDULE: CLARIFY WHAT'S "CAT 11
 IMP"?. SEC. 107.2.1 CITY AMENDMENTS.
  
 E) THERE IS AN ATTIC ACCESS DETAIL SHOWN ON THIS
 DRAWING. CLARIFY IF THE ATTIC ACCESS IS NEW. IF SO
 PROVIDE DIMENSIONS TO VERIFY COMPLIANCE WITH SEC. R807
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL15699-R2 DON'T MATCH. DRAWINGS
 SUBMITTED ARE FOR THE SH 3700 SERIES WINDOWS, WHILE
 FLORIDA PRODUCT APPROVAL FL15699-R2 IS FOR THE SH 3100
 SERIES WINDOWS. PROVIDE PRODUCT APPROVAL AND DRAWINGS
 THAT MATCH.
  
 B) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL13540-R3 DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. ALSO,
 THE DRAWINGS ARE NOT LEGIBLE. PROVIDE PRODUCT APPROVAL
 THAT MEETS THE CALCULATED DESIGN PRESSURES AND PROVIDE
 LEGIBLE COPIES.
  
 C) WINDOW MULLIONS:
 (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS
 FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014.
 (REPEAT COMMENT).
  
 (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). (REPEAT COMMENT).
  
 D) NEW COMMENT: ROOF PRODUCT APPROVAL. COORDINATE WITH
 REVISED PLANS AND ITEM #3(B) ABOVE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-26 Cont ID  
Sent By jgomez Date 2016-01-26 Time 14:40 Rev Time 0.00
Received By jgomez Date 2016-01-26 Time 07:59 Sent To E
Notes
2016-01-26 15:05:22RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- FLOOR PLAN SUBMITTED SHOWS A LIVING/DEN ROOM ON THE
 REAR OF THE HOUSE. ACCORDING TO CITY RECORDS AND THE
 PALM BEACH COUNTY PROPERTY APPRAISER THIS ROOM IS AN
 ENCLOSED PORCH NOT LIVABLE AREA. BRING PLANS TO PALM
 BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS FOR THE AREA CONVERTED
 FROM PORCH TO LIVABLE SPACE. SEC. R101.4.3 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE ENERGY CALCULATIONS INFORMATION WITH
 INFORMATION SHOWN ON THE INFORMATION REQUESTED ON ITEM
 #2 ABOVE.
  
 3- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- SPECIFY SIZE AND TYPE OF EXISTING WINDOWS (SPECIALLY
 THE BEDROOM WINDOWS) TO VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
  
 5- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL,
 THIS BUILDING IS LOCATED IN EXPOSURE "C". DESIGN
 PRESSURES SPECIFIED FOR THE DOORS AND WINDOWS ARE FOR
 EXPOSURE "B". REVISE THE DESIGN PRESSURES TO CORRESPOND
 TO EXPOSURE "C".
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL14604-R3 DON'T MATCH DRAWINGS
 SUBMITTED WITH FL14604-R3 FOR THE 2014 CODE VERSION.
 RE-SUBMIT COMPLETE PACKAGE THAT MATCHES. ALSO FLORIDA
 PRODUCT APPROVAL FL14604-R3 DOESN'T MATCH FLORIDA
 PRODUCT APPROVAL LISTED ON THE WINDOW/DOOR SCHEDULE
 SUBMITTED. REVISE AS REQUIRED.
  
 B) EXTERIOR DOORS. FLORIDA PRODUCT APPROVAL FL15558-R0
 SUBMITTED IS FOR 2010 CODE VERSION. NEED TO PROVIDE
 PRODUCT APPROVAL FOR THE CURRENT CODE VERSION. THE
 CURRENT CODE IS 2014. ALSO, REVISE THE WINDOW/DOOR
 SCHEDULE ACCORDINGLY.
  
 C) WINDOW MULLIONS:
 (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS
 FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014.
 ALSO, REVISE THE WINDOW/DOOR SCHEDULE ACCORDINGLY.
  
 (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- ALL DRAWINGS SUBMITTED NEED TO HAVE THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 10:09 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 10:09 Sent To M
Notes
2016-06-15 10:14:56REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH A PROVISO
  
 1) NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
  
 2) NEC 408.36 A PANELBOARD SHALL BE PROTECTED BY AN
 OCPD HAVING A RATING NOT GREATER THAN THAT OF THE
 PANELBOARD. ( SEE RED LINE MARKS ON PLANS )
2016-06-07 11:34:23NEW DRAWINGS SUBMITTED. JG.
  
  
 ****NOTE:
 THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND,
 THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE
 PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL
 DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON
 PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON
 THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED
 AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE
 NOT ALLOWED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-25 Cont ID  
Sent By mvaldes Date 2016-04-25 Time 09:54 Rev Time 0.00
Received By mvaldes Date 2016-04-25 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-28 Cont ID  
Sent By mvaldes Date 2016-01-28 Time 10:18 Rev Time 0.00
Received By mvaldes Date 2016-01-28 Time 10:18 Sent To  
Notes
2016-01-28 10:42:051ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1 FIRST AND FOURTH MOST TO COMPLY IN CONVERTING PORCH
 INTO LIVING DEN RECEPTACLE AND LIGHTING OUTLETS
 LOCATION WILL BE REQUIRED IN ACCORDANCE TO NEC 210.52 /
 210.70 FBC-R E3901.1 / E3903.1 ( FOLLOWING UP ON
 BUILDING COMMENTS. )
 2 SHOW LOCATION OF GFCI OUTLET IN BATHROOM ON FLOOR
 PLAN PLEASE COMPLY WITH NEC 210.52 D / 406.5 E AND
 FBC-R E3901.6
 3 R315.1CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES. (
 COMBINATION ALARM ACCEPTABLE. )
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-01-13 Cont ID  
Sent By cpuell Date 2017-01-13 Time 11:46 Rev Time 0.00
Received By cpuell Date 2017-01-05 Time 14:59 Sent To  
Notes
2017-01-06 14:59:11RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2016-12-05 Cont ID  
Sent By jgomez Date 2016-12-05 Time 15:52 Rev Time 0.00
Received By jgomez Date 2016-12-05 Time 15:52 Sent To  
Notes
2016-12-05 15:52:48REVISED ENERGY CALCULATIONS SUBMITTED VIA E-MAIL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-11-29 Cont ID  
Sent By jgomez Date 2016-11-29 Time 17:24 Rev Time 0.00
Received By jgomez Date 2016-11-21 Time 14:40 Sent To  
Notes
2016-11-28 18:53:37ROUTED TO JULIO GOMEZ 11/28/2016 - JORGE V.
2016-11-22 14:40:31R19

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-10-28 Cont ID  
Sent By cpuell Date 2016-10-28 Time 07:43 Rev Time 0.00
Received By cpuell Date 2016-10-03 Time 09:29 Sent To  
Notes
2016-10-04 09:29:37R01

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-24 Cont ID  
Sent By skennedy Date 2016-06-24 Time 08:50 Rev Time 0.00
Received By skennedy Date 2016-05-24 Time 12:36 Sent To  
Notes
2016-05-25 12:36:44R09

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-12 Cont ID  
Sent By lmarchan Date 2016-05-12 Time 08:01 Rev Time 0.00
Received By lmarchan Date 2016-04-18 Time 13:53 Sent To  
Notes
2016-05-06 11:20:14JGOMEZ'S DESK
2016-04-18 13:54:04R03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-28 Cont ID  
Sent By cpuell Date 2016-01-28 Time 17:08 Rev Time 0.00
Received By cpuell Date 2016-01-19 Time 11:42 Sent To  
Notes
2016-01-20 11:42:51R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-06-06 Cont ID  
Sent By jgomez Date 2016-06-06 Time 18:57 Rev Time 0.00
Received By jgomez Date 2016-06-06 Time 18:57 Sent To  
Notes
2016-06-06 18:58:25NO FEES DUE. MU-2016-12628.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-05-10 Cont ID  
Sent By jgomez Date 2016-05-10 Time 14:01 Rev Time 0.00
Received By jgomez Date 2016-05-10 Time 14:01 Sent To  
Notes
2016-05-10 14:01:381- SCOPE OF WORK WAS CHANGED. REVISED PLANS SHOW
 CONVERSION OF THE GARAGE AND PORCH TO BEDROOMS. BRING
 PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT
 FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-26 Cont ID  
Sent By jgomez Date 2016-01-26 Time 15:06 Rev Time 0.00
Received By jgomez Date 2016-01-26 Time 15:06 Sent To  
Notes
2016-01-26 15:07:28 
 1- FLOOR PLAN SUBMITTED SHOWS A LIVING/DEN ROOM ON THE
 REAR OF THE HOUSE. ACCORDING TO CITY RECORDS AND THE
 PALM BEACH COUNTY PROPERTY APPRAISER THIS ROOM IS AN
 ENCLOSED PORCH NOT LIVABLE AREA. BRING PLANS TO PALM
 BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2017-01-12 Cont ID  
Sent By jvalido Date 2017-01-12 Time 17:46 Rev Time 0.00
Received By jvalido Date 2017-01-12 Time 17:46 Sent To  
Notes
2017-01-11 16:10:01NEW LOAD CALCULATIONS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-11-28 Cont ID  
Sent By jvalido Date 2016-11-28 Time 18:52 Rev Time 0.00
Received By jvalido Date 2016-11-28 Time 17:55 Sent To B
Notes
2016-11-28 18:43:40CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE ACCURATE CFM DISTRIBUTION FOR ALL SUPPLY
 OUTLETS AS PER UNIT INSTALLED.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-10-27 Cont ID  
Sent By jvalido Date 2016-10-27 Time 16:55 Rev Time 0.00
Received By jvalido Date 2016-10-27 Time 16:05 Sent To  
Notes
2016-10-27 17:05:25CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE ACCURATE CFM DISTRIBUTION FOR ALL SUPPLY
 OUTLETS AS PER UNIT INSTALLED.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-06-15 Cont ID  
Sent By jvalido Date 2016-06-15 Time 10:45 Rev Time 0.00
Received By jvalido Date 2016-06-15 Time 10:28 Sent To  
Notes
2016-06-15 10:45:38CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL - 107.2 CONSTRUCTION DOCUMENTS - 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 PROVIDE CFM QUANTITIES OF ALL SUPPLY AIR OUTLETS.
  
 FLORIDA ENERGY CODE - FBC 2014
  
 PROVIDE AHRI
2016-06-07 13:39:57****NOTE:
 THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND,
 THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE
 PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL
 DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON
 PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON
 THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED
 AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE
 NOT ALLOWED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-11 Cont ID  
Sent By jvalido Date 2016-05-11 Time 16:16 Rev Time 0.00
Received By jvalido Date 2016-05-11 Time 16:14 Sent To  
Notes
2016-05-11 16:16:51MANUAL J SHOWS A GOODMAN 2 TON PACKAGE UNIT.
  
 PLANS SHOW A PACKAGE UNIT. EQUIPMENT SCHEDULE SHOWS A
 GOODMAN 2.5 TON SPLIT SYSTEM. CONFIRM TYPE OF SYSTEM
 INSTALLING AND MAKE CORRECTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-19 Cont ID  
Sent By jvalido Date 2016-04-19 Time 18:16 Rev Time 0.00
Received By jvalido Date 2016-04-19 Time 17:29 Sent To  
Notes
2016-04-19 17:49:23CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1 - 109.3
 PERMIT APPLICATION DOES NOT INCLUDE MECHANICAL WORK.
 INCLUDE MECHANICAL WORK ON PERMIT APPLICATION AND
 ADJUST TOTAL VALUE.
  
 PLANS SHOW A PACKAGE UNIT. EQUIPMENT SCHEDULE SHOWS A
 SPLIT SYSTEM. CONFIRM TYPE OF SYSTEM INSTALLING AND
 MAKE CORRECTIONS.
  
 TOTAL CFM ON PLANS EXCEED TOTAL CFM OUTPUT OF AHU
 STATED ON PLANS AND OF PACKAGE UNIT STATED ON MANUAL J.
 CONFIRM TOTAL OUTPUT OF AHU/PACKAGE UNIT AND MAKE
 CORRECTIONS TO PLANS OR PROVIDE CORRECT AHU.
  
 PROVIDE AHRI FOR EQUIPMENT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-09 Cont ID  
Sent By gjohnson Date 2016-06-09 Time 06:23 Rev Time 0.00
Received By gjohnson Date 2016-06-09 Time 06:23 Sent To  
Notes
2016-06-09 06:24:10REVIEWED AND APPROVED BY GEORGE EARL
2016-06-07 09:34:47NEW DRAWINGS SUBMITTED. JG.
  
 ****NOTE:
 THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND,
 THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE
 PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL
 DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON
 PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON
 THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED
 AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE
 NOT ALLOWED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-02 Cont ID  
Sent By tklarge Date 2016-05-02 Time 10:02 Rev Time 0.00
Received By tklarge Date 2016-04-29 Time 06:16 Sent To  
Notes
2016-05-06 11:19:36JGOMEZ'S DESK

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-23 Cont ID  
Sent By tklarge Date 2016-01-23 Time 10:38 Rev Time 0.00
Received By tklarge Date 2016-01-23 Time 10:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2016-11-23 Time   Rev Time 0.00
Received By awooten Date 2016-11-23 Time 11:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-31 Cont ID  
Sent By njwira Date 2016-05-31 Time 16:03 Rev Time 0.00
Received By njwira Date 2016-05-31 Time 15:55 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-10 Cont ID  
Sent By ajones Date 2016-05-10 Time 15:30 Rev Time 0.00
Received By ajones Date 2016-05-10 Time 15:30 Sent To  
Notes
2016-05-09 18:50:43REVISED PLANS SUBMITTED SHOWING CONVERSION OF GARAGE
 AND PORCH TO BEDROOMS. JG.