| Plan Review Stops For Permit 16010523 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2017-01-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-01-11 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-01-11 |
Time |
14:55 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2016-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-12-05 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-12-05 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2016-12-05 11:42:34 | RESIDENTIAL (R3) ALTERATION SIXTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- NEW ENERGY CALCULATIONS SUBMITTED (FORM R405-2014): | | | A) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | B) CLARIFY WHY THE COOLING SYSTEM IS ONLY 12.8 KBTU/HR, | | | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | C) ATTIC INFORMATION ON PAGE 2 OF 4 SPECIFIES A VENT | | | RATIO OF 1/300. TYPICALLY, THE VENTILATION RATIO IS | | | 1/150. IN ORDER TO USE THE 1/300 VENT RATIO, THE | | | ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS | | | AND SPECIFICATIONS SHOWING COMPLIANCE AS REQUIRED BY | | | THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL, 5TH | | | EDITION (2014). OTHERWISE, REVISE THE VENT RATIO TO | | | 1/150. | | | | | | D) THE EPL DISPLAY CARD NEEDS TO BE SIGNED BY THE | | | BUILDER. ONLY THE NAME OF THE BUILDER WAS PROVIDED. THE | | | SIGNATURE DOESN'T MATCH SIGNATURE SHOWN ON THE PERMIT | | | APPLICATION. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | | | | E) ENGINEER OF RECORD COMPLETING THE ENERGY | | | CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS | | | REQUIRED BY CHAPTER 471 F.S WHEN SUBMITTING | | | DOCUMENTATION FOR PUBLIC RECORDS. | | | | | | NOTE: | | | LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND | | | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ARE | | | REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT TAKING | | | THE SOFTWARE DEFAULT FACTORS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2016-11-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-11-29 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-29 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2016-11-29 14:36:25 | RESIDENTIAL (R3) ALTERATION FIFTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS THAT CONTRACTOR WILL SUBMIT REQUIRED INFORMATION | | | PRIOR TO INSPECTIONS TO AVOID DELAYS/CONFLICTS. | | | REVISION FEES WILL APPLY EACH TIME INFORMATION IS | | | RESUBMITTED. CONTRACTOR TO ADVICE IF PROVISO OPTION IS | | | PREFERRED AT THIS TIME OR IF RESUBMITTING REQUIRED | | | INFORMATION PRIOR TO ISSUING PERMIT. | | | | | | | | | NEW COMMENT BASED ON THE ENERGY CALCULATIONS SUBMITTED: | | | 1- DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND | | | SPECIFICATIONS SHOWING COMPLIANCE WITH THE INTERIOR AND | | | EXTERIOR INSULATION REQUIREMENTS AS REQUIRED BY ENERGY | | | CALCULATIONS SUBMITTED. SEC. R103.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | 2- ENERGY CALCULATIONS SUBMITTED: | | | | | | NOTE: KEEP IN MIND THAT ENERGY CALCULATION SUBMITTED | | | ARE DONE FOR THE ENTIRE HOUSE. ALL OF THE COMMENTS | | | BELOW APPLY TO THE ENTIRE HOUSE. | | | | | | | | | A) REVISE INFORMATION ON TABLE R402A SUBMITTED: | | | (1) MASONRY WALLS REQUIRE "INSULATION ON WALL INTERIOR" | | | OF R-4 AND "INSULATION ON WALL EXTERIOR" OF R-3. THE | | | "INSTALLED VALUES" COLUMN WAS NOT COMPLETED. NEED TO | | | COMPLETE THE "INSTALLED VALUES" COLUMN. (NOTE: SEE NOTE | | | #4 AT THE BOTTOM OF THIS TABLE). SEC. R101.5.1.1.1 | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | (2) THE CEILING INFORMATION WAS NOT COMPLETED ON THE | | | "INSTALLED VALUES" COLUMN. NEED TO COMPLETE THE | | | "INSTALLED VALUES" COLUMN. SEC. R101.5.1.1.1 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | (3) THE AIR HANDLER UNIT IS NOT ALLOWED IN THE ATTIC. | | | REVISE THE "INSTALLED VALUES" COLUMN AS REQUIRED. SEC. | | | R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | (4) THE ELECTRIC WATER HEATER EF VALUE SHOWN ON THE | | | "INSTALLED VALUES" COLUMN DOESN'T COMPLY WITH THE | | | PRESCRIPTIVE REQUIREMENTS. REVISE AS REQUIRED. SEC. | | | R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | | | | B) REVISE INFORMATION ON TABLE R402B SUBMITTED; | | | (1) THE WATER HEATER COMPONENT WAS NOT CHECKED. SEC. | | | R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | | | | C) THE HEATING INFORMATION SHOWN ON THE ENERGY | | | CALCULATIONS ITEM #13A AND #13B DOESN'T MATCH TABLE | | | R402A AND EQUIPMENT INFORMATION SHOWN ON THE MECHANICAL | | | PLAN. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.1 | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | D) PERSON DOING THE ENERGY CALCULATIONS NEED TO | | | COORDINATE INFORMATION SHOWN ON THE FRONT PAGE OF THE | | | ENERGY CALCULATIONS WIT INFORMATION SHOWN ON TABLE | | | R402A. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | | | | | | | NOTE: IF UNABLE TO COMPLY WITH THE ABOVE REQUIREMENTS | | | USING THE PRESCRIPTIVE FORM R402-2014 SUBMITTED, THEN | | | PERFORMANCE METHOD FORM R405-2014 MAY BE USED INSTEAD. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2016-10-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-10-26 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-10-26 |
Time |
15:35 |
Sent To |
M |
|
| Notes |
| 2016-10-26 16:42:36 | RESIDENTIAL (R3) ALTERATION FOURTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- ENERGY CALCULATIONS SUBMITTED: | | | A) INFORMATION SUBMITTED IS INCOMPLETE. MISSING TABLES | | | R402A AND TABLE R402B. AND, BOTH NEED TO BE COMPLETE | | | BEFORE SUBMITTAL. | | | | | | B) REVISE WALL TYPE AND INSULATION SHOWN ON ITEM #9. | | | NEED TO SPECIFY THE INSULATION ON THE INTERIOR OF THE | | | MASONRY WALL AND THE INSULATION ON THE EXTERIOR OF THE | | | MASONRY WALL. NOTE: CALCULATIONS SUBMITTED ARE FOR THE | | | ENTIRE HOUSE. THIS REQUIREMENTS APPLIES TO ALL EXISTING | | | EXTERIOR WALLS. NEED TO PROVIDE PROOF THAT EXISTING | | | WALLS WILL MEET THIS CRITERIA. ALSO, NEED TO SPECIFY | | | THE INFILL WOOD FRAME WALL INSTALLED TO CLOSE THE | | | EXISTING GARAGE DOOR OPENING. SEC. R101.5.1.1.1 | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | NOTE: IF UNABLE TO COMPLY WITH THE ABOVE REQUIREMENTS | | | USING THE PRESCRIPTIVE FORM R402-2014 SUBMITTED, THEN | | | PERFORMANCE METHOD FORM R405-2014 MAY BE USED INSTEAD. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) HORIZONTAL SLIDER WINDOWS THAT MEET THE CALCULATED | | | DESIGN PRESSURES FOR THE HORIZONTAL SLIDERS IN THE | | | LIVING ROOM. DRAWINGS SUBMITTED WITH FLORIDA PRODUCT | | | APPROVAL FL15814-R2 DON'T MEET THE DESIGN PRESSURES | | | SHOWN ON DRAWING A1. | | | | | | B) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA | | | PRODUCT APPROVAL FL14569 DON'T MEET THE DESIGN | | | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. REPEAT | | | COMMENT. THREE TIMES. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | NEW COMMENTS: | | | 4- WINDOWS SHOWN ON DRAWING A1 WERE REVISED. THE | | | FOLLOWING REVISIONS ARE REQUIRED: | | | A) WINDOW SIZES FOR BEDROOM #3 DON'T COMPLY WITH THE | | | EGRESS REQUIREMENTS. CLEARLY SPECIFY SIZE AND TYPE OF | | | EXISTING WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS | | | REQUIREMENTS OF SEC. 704 FBC-EXISTING BUILDING, 5TH | | | EDITION (2014). | | | | | | B) REVISE EXTERIOR ELEVATIONS ON SHEET A2 TO MATCH | | | REVISED WINDOWS ON SHEET A1. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2016-06-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-06-07 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-06-07 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2016-06-06 18:48:42 | RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING | | | REVIEW CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | ****NOTE: | | | THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND, | | | THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE | | | PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL | | | DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON | | | PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON | | | THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED | | | AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE | | | NOT ALLOWED. | | | | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT | | | COMMENT). | | | RESPONSE: REPEAT COMMENT (3 TIMES). NOT ADDRESSED. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | ORIGINAL COMMENT: | | | A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA | | | PRODUCT APPROVAL FL15699-R2 DON'T MATCH. DRAWINGS | | | SUBMITTED ARE FOR THE SH 3700 SERIES WINDOWS, WHILE | | | FLORIDA PRODUCT APPROVAL FL15699-R2 IS FOR THE SH 3100 | | | SERIES WINDOWS. PROVIDE PRODUCT APPROVAL AND DRAWINGS | | | THAT MATCH. | | | RESPONSE: FLORIDA PRODUCT APPROVAL FL13406-R1 SUBMITTED | | | NOW IS FOR HORIZONTAL SLIDER WINDOWS. THERE ARE NO | | | HORIZONTAL SLIDER WINDOWS SPECIFIED ON PLANS. THIS | | | FLORIDA PRODUCT APPROVAL IS FOR THE 2010 CODE VERSION. | | | NEED PRODUCT APPROVAL FOR THE CURRENT 2014 CODE | | | VERSION. THIS PRODUCT APPROVAL IS FOR NON-IMPACT | | | WINDOWS (NON-IMPACT WINDOWS REQUIRE HURRICANE | | | SHUTTERS). PROVIDE PRODUCT APPROVAL FOR THE WINDOW THAT | | | IS SPECIFIED ON PLANS. | | | | | | NEW COMMENT: | | | B) HURRICANE SHUTTERS IF THE WINDOWS AND DOORS DON'T | | | HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. PLEASE, CONTACT ME TO GUIDE | | | YOU HOW TO GET THE CITY SAMPLE. | | | | | | ORIGINAL COMMENT: | | | C) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA | | | PRODUCT APPROVAL FL13540-R3 DON'T MEET THE DESIGN | | | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. ALSO, | | | THE DRAWINGS ARE NOT LEGIBLE. PROVIDE PRODUCT APPROVAL | | | THAT MEETS THE CALCULATED DESIGN PRESSURES AND PROVIDE | | | LEGIBLE COPIES. | | | RESPONSE: DOORS SUBMITTED WITH FLORIDA PRODUCT APPROVAL | | | FL13540 DON'T MEET THE CALCULATED DESIGN PRESSURES. | | | REPEAT COMMENT. NEED DOOR THAT MEETS THE CALCULATED | | | DESIGN PRESSURES. | | | | | | ORIGINAL COMMENT: | | | D) WINDOW MULLIONS: | | | (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS | | | FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL | | | FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014. | | | (REPEAT COMMENT). | | | (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). (REPEAT COMMENT). | | | RESPONSE: COMMENTS NOT ADDRESSED AT ALL. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-05-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-05-09 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-05-09 |
Time |
18:36 |
Sent To |
M |
|
| Notes |
| 2016-05-09 18:41:41 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING | | | REVIEW CHECKLIST. | | | CODE: FBC-5TH EDITION (2014) | | | | | | 1- SCOPE OF WORK WAS CHANGED. REVISED PLANS SHOW | | | CONVERSION OF THE GARAGE AND PORCH TO BEDROOMS. BRING | | | PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT | | | FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND | | | COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | 2- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT | | | COMMENT). | | | | | | 3- SHEET A1: | | | A) ENGINEER OF RECORD TO PROVIDE FRAMING DETAILS AND | | | SPECIFICATIONS FOR THE INFILL OF ALL OPENINGS IN THE | | | EXISTING PORCH AND GARAGE. SEC. R301.1 FBC-RESIDENTIAL, | | | 5TH EDITION (2014). | | | | | | B) NOTE #1 OF SCOPE OF WORK SAYS "DEMOLISH ENTIRE | | | REMAINS OF THE FIRE DAMAGED ROOF AND INSTALL TOTALLY | | | NEW ROOF". PLANS DON'T SHOW AREA OF FIRE AND DON' | | | PROVIDE ANY SPECIFICATIONS REGARDING THE REQUIRED | | | REPAIRS. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS | | | SHOWING HOW THE AREA IS REPAIRED. SEC. R301.1 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | C) CLARIFY INFORMATION SHOWN ON THE "SPECIAL NOTES": | | | WHAT'S "FEBC"?.. WHAT'S "ALTERATION LEVEL 11"?. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | D) DOOR AND WINDOW SCHEDULE: CLARIFY WHAT'S "CAT 11 | | | IMP"?. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | E) THERE IS AN ATTIC ACCESS DETAIL SHOWN ON THIS | | | DRAWING. CLARIFY IF THE ATTIC ACCESS IS NEW. IF SO | | | PROVIDE DIMENSIONS TO VERIFY COMPLIANCE WITH SEC. R807 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA | | | PRODUCT APPROVAL FL15699-R2 DON'T MATCH. DRAWINGS | | | SUBMITTED ARE FOR THE SH 3700 SERIES WINDOWS, WHILE | | | FLORIDA PRODUCT APPROVAL FL15699-R2 IS FOR THE SH 3100 | | | SERIES WINDOWS. PROVIDE PRODUCT APPROVAL AND DRAWINGS | | | THAT MATCH. | | | | | | B) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA | | | PRODUCT APPROVAL FL13540-R3 DON'T MEET THE DESIGN | | | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. ALSO, | | | THE DRAWINGS ARE NOT LEGIBLE. PROVIDE PRODUCT APPROVAL | | | THAT MEETS THE CALCULATED DESIGN PRESSURES AND PROVIDE | | | LEGIBLE COPIES. | | | | | | C) WINDOW MULLIONS: | | | (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS | | | FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL | | | FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014. | | | (REPEAT COMMENT). | | | | | | (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). (REPEAT COMMENT). | | | | | | D) NEW COMMENT: ROOF PRODUCT APPROVAL. COORDINATE WITH | | | REVISED PLANS AND ITEM #3(B) ABOVE. | | | | | | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-01-26 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-01-26 |
Time |
07:59 |
Sent To |
E |
|
| Notes |
| 2016-01-26 15:05:22 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. | | | CODE: FBC-5TH EDITION (2014) | | | | | | 1- FLOOR PLAN SUBMITTED SHOWS A LIVING/DEN ROOM ON THE | | | REAR OF THE HOUSE. ACCORDING TO CITY RECORDS AND THE | | | PALM BEACH COUNTY PROPERTY APPRAISER THIS ROOM IS AN | | | ENCLOSED PORCH NOT LIVABLE AREA. BRING PLANS TO PALM | | | BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT FEES | | | ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF | | | PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | 2- PROVIDE ENERGY CALCULATIONS FOR THE AREA CONVERTED | | | FROM PORCH TO LIVABLE SPACE. SEC. R101.4.3 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | NOTE: COORDINATE ENERGY CALCULATIONS INFORMATION WITH | | | INFORMATION SHOWN ON THE INFORMATION REQUESTED ON ITEM | | | #2 ABOVE. | | | | | | 3- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED | | | BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | 4- SPECIFY SIZE AND TYPE OF EXISTING WINDOWS (SPECIALLY | | | THE BEDROOM WINDOWS) TO VERIFY COMPLIANCE WITH THE | | | EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING | | | BUILDING, 5TH EDITION (2014). | | | | | | 5- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL, | | | THIS BUILDING IS LOCATED IN EXPOSURE "C". DESIGN | | | PRESSURES SPECIFIED FOR THE DOORS AND WINDOWS ARE FOR | | | EXPOSURE "B". REVISE THE DESIGN PRESSURES TO CORRESPOND | | | TO EXPOSURE "C". | | | | | | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA | | | PRODUCT APPROVAL FL14604-R3 DON'T MATCH DRAWINGS | | | SUBMITTED WITH FL14604-R3 FOR THE 2014 CODE VERSION. | | | RE-SUBMIT COMPLETE PACKAGE THAT MATCHES. ALSO FLORIDA | | | PRODUCT APPROVAL FL14604-R3 DOESN'T MATCH FLORIDA | | | PRODUCT APPROVAL LISTED ON THE WINDOW/DOOR SCHEDULE | | | SUBMITTED. REVISE AS REQUIRED. | | | | | | B) EXTERIOR DOORS. FLORIDA PRODUCT APPROVAL FL15558-R0 | | | SUBMITTED IS FOR 2010 CODE VERSION. NEED TO PROVIDE | | | PRODUCT APPROVAL FOR THE CURRENT CODE VERSION. THE | | | CURRENT CODE IS 2014. ALSO, REVISE THE WINDOW/DOOR | | | SCHEDULE ACCORDINGLY. | | | | | | C) WINDOW MULLIONS: | | | (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS | | | FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL | | | FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014. | | | ALSO, REVISE THE WINDOW/DOOR SCHEDULE ACCORDINGLY. | | | | | | (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | 7- ALL DRAWINGS SUBMITTED NEED TO HAVE THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS | | | REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-06-15 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-06-15 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-06-15 |
Time |
10:09 |
Sent To |
M |
|
| Notes |
| 2016-06-15 10:14:56 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | PASSED WITH A PROVISO | | | | | | 1) NEC 250.94 BONDING FOR OTHER SYSTEMS. THE | | | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE | | | INSTALLED. | | | | | | 2) NEC 408.36 A PANELBOARD SHALL BE PROTECTED BY AN | | | OCPD HAVING A RATING NOT GREATER THAN THAT OF THE | | | PANELBOARD. ( SEE RED LINE MARKS ON PLANS ) | | 2016-06-07 11:34:23 | NEW DRAWINGS SUBMITTED. JG. | | | | | | | | | ****NOTE: | | | THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND, | | | THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE | | | PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL | | | DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON | | | PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON | | | THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED | | | AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE | | | NOT ALLOWED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-04-25 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-04-25 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-25 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-01-28 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-01-28 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-01-28 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2016-01-28 10:42:05 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | | | | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | 1 FIRST AND FOURTH MOST TO COMPLY IN CONVERTING PORCH | | | INTO LIVING DEN RECEPTACLE AND LIGHTING OUTLETS | | | LOCATION WILL BE REQUIRED IN ACCORDANCE TO NEC 210.52 / | | | 210.70 FBC-R E3901.1 / E3903.1 ( FOLLOWING UP ON | | | BUILDING COMMENTS. ) | | | 2 SHOW LOCATION OF GFCI OUTLET IN BATHROOM ON FLOOR | | | PLAN PLEASE COMPLY WITH NEC 210.52 D / 406.5 E AND | | | FBC-R E3901.6 | | | 3 R315.1CARBON MONOXIDE PROTECTION. | | | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING | | | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS | | | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR | | | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER | | | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE | | | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL | | | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 | | | MM) OF EACH ROOM USED FOR SLEEPING PURPOSES. ( | | | COMBINATION ALARM ACCEPTABLE. ) | | | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | | MENTIONED DEFICIENCIES. | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD | | | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE | | | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2017-01-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-01-13 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-01-05 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2017-01-06 14:59:11 | RESUB ROUTED TO JGOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2016-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-12-05 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-12-05 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2016-12-05 15:52:48 | REVISED ENERGY CALCULATIONS SUBMITTED VIA E-MAIL. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-11-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-11-29 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-11-21 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2016-11-28 18:53:37 | ROUTED TO JULIO GOMEZ 11/28/2016 - JORGE V. | | 2016-11-22 14:40:31 | R19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-10-28 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-10-28 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-10-03 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-06-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-06-24 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-05-24 |
Time |
12:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-05-12 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-05-12 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-04-18 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2016-05-06 11:20:14 | JGOMEZ'S DESK | | 2016-04-18 13:54:04 | R03 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-01-28 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-01-28 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-01-19 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2016-06-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-06-06 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-06-06 |
Time |
18:57 |
Sent To |
|
|
| Notes |
| 2016-06-06 18:58:25 | NO FEES DUE. MU-2016-12628. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2016-05-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-05-10 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-05-10 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2016-05-10 14:01:38 | 1- SCOPE OF WORK WAS CHANGED. REVISED PLANS SHOW | | | CONVERSION OF THE GARAGE AND PORCH TO BEDROOMS. BRING | | | PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT | | | FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND | | | COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-01-26 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-01-26 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2016-01-26 15:07:28 | | | | 1- FLOOR PLAN SUBMITTED SHOWS A LIVING/DEN ROOM ON THE | | | REAR OF THE HOUSE. ACCORDING TO CITY RECORDS AND THE | | | PALM BEACH COUNTY PROPERTY APPRAISER THIS ROOM IS AN | | | ENCLOSED PORCH NOT LIVABLE AREA. BRING PLANS TO PALM | | | BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT FEES | | | ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF | | | PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE | | | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2017-01-12 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2017-01-12 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2017-01-12 |
Time |
17:46 |
Sent To |
|
|
| Notes |
| 2017-01-11 16:10:01 | NEW LOAD CALCULATIONS SUBMITTED. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2016-11-28 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-11-28 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-11-28 |
Time |
17:55 |
Sent To |
B |
|
| Notes |
| 2016-11-28 18:43:40 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) PROVIDE ACCURATE CFM DISTRIBUTION FOR ALL SUPPLY | | | OUTLETS AS PER UNIT INSTALLED. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2016-10-27 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-10-27 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-10-27 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2016-10-27 17:05:25 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) PROVIDE ACCURATE CFM DISTRIBUTION FOR ALL SUPPLY | | | OUTLETS AS PER UNIT INSTALLED. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2016-06-15 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-06-15 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-06-15 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2016-06-15 10:45:38 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL - 107.2 CONSTRUCTION DOCUMENTS - 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | PROVIDE CFM QUANTITIES OF ALL SUPPLY AIR OUTLETS. | | | | | | FLORIDA ENERGY CODE - FBC 2014 | | | | | | PROVIDE AHRI | | 2016-06-07 13:39:57 | ****NOTE: | | | THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND, | | | THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE | | | PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL | | | DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON | | | PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON | | | THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED | | | AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE | | | NOT ALLOWED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-05-11 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-05-11 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-05-11 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2016-05-11 16:16:51 | MANUAL J SHOWS A GOODMAN 2 TON PACKAGE UNIT. | | | | | | PLANS SHOW A PACKAGE UNIT. EQUIPMENT SCHEDULE SHOWS A | | | GOODMAN 2.5 TON SPLIT SYSTEM. CONFIRM TYPE OF SYSTEM | | | INSTALLING AND MAKE CORRECTIONS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-04-19 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-04-19 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-04-19 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2016-04-19 17:49:23 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.2.1 - 109.3 | | | PERMIT APPLICATION DOES NOT INCLUDE MECHANICAL WORK. | | | INCLUDE MECHANICAL WORK ON PERMIT APPLICATION AND | | | ADJUST TOTAL VALUE. | | | | | | PLANS SHOW A PACKAGE UNIT. EQUIPMENT SCHEDULE SHOWS A | | | SPLIT SYSTEM. CONFIRM TYPE OF SYSTEM INSTALLING AND | | | MAKE CORRECTIONS. | | | | | | TOTAL CFM ON PLANS EXCEED TOTAL CFM OUTPUT OF AHU | | | STATED ON PLANS AND OF PACKAGE UNIT STATED ON MANUAL J. | | | CONFIRM TOTAL OUTPUT OF AHU/PACKAGE UNIT AND MAKE | | | CORRECTIONS TO PLANS OR PROVIDE CORRECT AHU. | | | | | | PROVIDE AHRI FOR EQUIPMENT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2016-06-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-06-09 |
Time |
06:23 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-06-09 |
Time |
06:23 |
Sent To |
|
|
| Notes |
| 2016-06-09 06:24:10 | REVIEWED AND APPROVED BY GEORGE EARL | | 2016-06-07 09:34:47 | NEW DRAWINGS SUBMITTED. JG. | | | | | | ****NOTE: | | | THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND, | | | THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE | | | PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL | | | DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON | | | PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON | | | THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED | | | AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE | | | NOT ALLOWED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-05-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-05-02 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-04-29 |
Time |
06:16 |
Sent To |
|
|
| Notes |
| 2016-05-06 11:19:36 | JGOMEZ'S DESK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-01-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-23 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-23 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2016-11-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2016-11-23 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-05-31 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-05-31 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-05-31 |
Time |
15:55 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2016-05-10 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2016-05-10 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2016-05-10 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2016-05-09 18:50:43 | REVISED PLANS SUBMITTED SHOWING CONVERSION OF GARAGE | | | AND PORCH TO BEDROOMS. JG. |
|
|