| Plan Review Stops For Permit 16010520 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-04-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-25 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-25 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2017-04-25 16:05:40 | PROVISO - PROVIDE FIXTURE CALCS AT INSPECTION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-03-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-03 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-03 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2017-03-03 07:19:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | COMMENTS FROM PREVIOUS REVIEW: | | | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED LIGHT | | | POLES, FBC 1609. INCLUDE WIND DESIGN CRITERIA. | | | | | | 2. PROVIDE CALCS FOR THE LIGHT POLES AND FIXTURES, FBC | | | 1609. | | | | | | IT IS NOT CLEAR HOW THESE ITEMS WERE ADDRESSED. A | | | RESPONSE LETTER WAS NOT PROVIDED, AND IT DOES NOT | | | APPEAR THAT THIS INFORMATION WAS ADDED TO THE PLAN. IF | | | YOU FEEL THAT THIS INFORMATION IS INCLUDED IN THE | | | SUBMITTAL, PLEASE ADVISE AS TO FILE NAMES. A DETAIL ON | | | AN ELECTRICAL SHEET WAS PROVIDED BUT IS NOT A COMPLETE | | | STRUCTURAL DETAIL. | | | | | | S003 INCLUDES WIND DESIGN CRITERIA, BUT I WAS NOT ABLE | | | TO LOCATE AN S SHEET WITH THE STRUCTURAL DETAIL FOR THE | | | LIGHT POLES, AND WAS NOT ABLE TO LOCATE THE | | | CALCULATIONS FOR THE POLES AND FIXTURES. THIS | | | INFORMATION IS OFTEN PROVIDED BY THE SPECIALTY | | | ENGINEER. IF PROVIDED BY A SPECIALTY ENGINEER, HAVE THE | | | DELEGATED ENGINEERING REVIEWED BY DOR PRIOR TO | | | SUBMITTAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-08-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-08-18 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-08-18 |
Time |
17:33 |
Sent To |
|
|
| Notes |
| 2016-08-18 17:34:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED LIGHT | | | POLES, FBC 1609. INCLUDE WIND DESIGN CRITERIA. | | | | | | 2. PROVIDE CALCS FOR THE LIGHT POLES AND FIXTURES, FBC | | | 1609. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2017-05-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-12 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-12 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-03-07 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-03-07 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2017-03-07 11:53:33 | PLEASE ADDRESS ZONING COMMENTS FOR AN ELECTRICAL | | | APPROVAL. | | | | | | V. PEREZ | | | *6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-07-02 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-07-02 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-07-02 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2016-07-02 11:18:15 | PENDING ZONING APPROVAL |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-03-29 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-03-29 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-03-29 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2016-03-29 13:13:31 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE ADDRESS ZONING COMMENTS FOR A COMPLETE | | | ELECTRICAL REVIEW. | | | 2. PLEASE PROVIDE ENGINEERED POLE DETAILS TO WITHSTAND | | | WIND LOADS FOR AREA OF INSTALLATION | | | 3. BUILDING REVIEW WILL BE REQUIRED FOR THE STRUCTURAL | | | CONCRETE POLE BASE DESIGN. | | | 4. COULD NOT LOCATE PHOTOMETRICS UNDER ORIGINAL | | | SUBMITTAL PLEASE CLARIFY. | | | 5. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD | | | YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-05-16 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-05-16 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-04-21 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-03-07 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-03-07 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-03-07 |
Time |
11:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-08-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-08-18 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-06-21 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2017-04-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-25 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-25 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2017-03-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-03 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-03 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2017-03-03 07:27:05 | PROVISO - NEW SHEETS AND DOCUMENTS SUBMITTED FOR REVIEW | | | #3 TO BE REVIEWED FOR DIGITAL SIGNATURE | | | SHEETS SUBMITTED TO DATE (A, E, S) SIGNATURES OK | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2017-05-16 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-05-16 |
Time |
14:30 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2017-05-16 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2017-02-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2017-02-28 |
Time |
17:23 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2017-02-28 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2017-02-28 17:22:45 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSES. | | | | | | 1) PLEASE EXPLAIN WHY THE FX12A GRADE RECESSED UPLIGHTS | | | ARE CAUSING SUCH HIGH FOOTCANDLES (WEST OF EITHER ENTRY | | | DRIVE. HOW WILL GLARE INTO THE OKEECHOBEE BOULEVARD | | | RIGHT-OF-WAY BE PREVENTED GIVEN THESE HIGH OUTPUTS? | | | | | | 2) THE SITE LAYOUT IS DIFFERENT FROM THE ONE APPROVED | | | BY RESOLUTION NO. 260-16. PRIOR TO THE C.O. OF THE | | | BUILDING THE AS BUILT PLANS SHALL BE SUBMITTED TO THE | | | PLANNING DIVISION AS A MINOR AMENDMENT. | | | | | | 3) PRIOR TO C.O., PROVIDE STAFF WITH THE FDOT PERMIT | | | AND SIGN-OFF FOR THE LIGHTS WITHIN THE RIGHT-OF-WAY. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-07-22 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-07-22 |
Time |
12:02 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2016-07-22 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2016-07-22 12:02:18 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSES. | | | | | | 1) THE SITE LAYOUT SHOWN ON THE PLANS IS DIFFERENT FROM | | | THE APPROVED PLANS. THE PROPOSED SITE LAYOUT IS | | | TENTATIVELY SCHEDULED TO BE HEARD BY THE CITY | | | COMMISSION ON AUGUST 29, 2016. ZONING CANNOT GIVE FINAL | | | APPROVAL OF THE PERMIT UNTIL AFTER THE COMMISSION | | | APPROVAL. | | | | | | 2) REPEAT COMMENT: THERE CONTINUE TO BE LIGHTS SHOWN ON | | | THE ELECTRICAL SITE PLAN THAT ARE NOT LISTED ON THE | | | ELECTRICAL SCHEDUL, EX. - ALL OF THE FX SERIES OF | | | LIGHTS. | | | | | | 3) REPEAT COMMENT: LIGHTS MAY NOT BE MOUNTED IN THE | | | TREES. THE ELECTRICAL SCHEDULE LISTS TREE TYPES F10 AND | | | F10A AS TREE MOUNTED. | | | | | | 4) REPEAT COMMENT: NO PHOTOMETRIC PLAN WAS PROVIDED. | | | | | | 5) THE ELECTRICAL SITE PLAN SHOWS AN F11 LIGHT TYPE | | | THAT IS NOT LISTED ON THE ELECTRICAL SCHEDULE. IS THIS | | | SUPPOSED TO BE THE FS2 BOLLARD LIGHT? | | | | | | 6) HOW TALL ARE THE BOLLARD LIGHTS? | | | | | | 7) WHAT DOES THE WR TYPE OF LIGHT LOOK LIKE? IT IS NOT | | | SHOWN ON SHEET LGT 251.1. DOES ANY PART OF THE WR LIGHT | | | EXTEND ABOVE THE WALL? | | | | | | 8) PROVIDE DETAILS, TO INCLUDE POLE HEIGHT, FOR THE | | | FS21 TYPE LIGHT. | | | | | | 9) THE ELECTRICAL SITE PLAN SHOWS THE POLE PLUS FIXTURE | | | FOR TYPE FS1 AT 16 FEET IN HEIGHT. THE ELECTRICAL | | | SCHEDULE LISTS TYPE FS1 AS HAVING A 10 FOOT POLE WITH A | | | 12 OVERALL HEIGHT. ALL PLANS SHALL SHOW SAME | | | CONDITIONS. PLEASE NOTE THAT THE 12 FOOT HEIGHT WORKS | | | BETTER WITH THE SPECIFIC TREES AND THEIR LOCATIONS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-01-26 |
Time |
17:59 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2016-01-26 |
Time |
17:59 |
Sent To |
|
|
| Notes |
| 2016-01-26 18:12:13 | FAILED | | | | | | 1) THE SITE, LANDSCAPE AND CIVIL PLANS SHOW EIGHT LIGHT | | | POLES AROUND THE PARKING LOT. THE ELECTRICAL SITE PLAN | | | SHOWS 19 POLES (FS1) AROUND THE PARKING LOT, TO INCLUDE | | | ONE IN THE DRAIN FLUE. THE 19 POLES SEEM EXCESSIVE. | | | | | | 2) THE POLE SHOWN ON SHEET E050 IS LABELED AS F51, YET | | | THIS DOES NOT EXIST ON THE PLAN. | | | | | | 3) LIGHTS MAY NOT BE MOUNTED IN THE TREES. | | | | | | 4) NO PHOTOMETRIC PLAN WAS PROVIDED. | | | | | | 5) WHERE ARE THE DETAILS FOR THE BOLLARD LIGHTS AND THE | | | WALL PACKS. | | | | | | 6) WHAT ARE THE WP, WR AND LA SERIES OF LIGHTS AND WHAT | | | DO THEY LOOK LIKE? | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|