Plan Review Details - Permit 16010520
Plan Review Stops For Permit 16010520
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-25 Cont ID  
Sent By shill Date 2017-04-25 Time 16:05 Rev Time 0.00
Received By shill Date 2017-04-25 Time 16:05 Sent To  
Notes
2017-04-25 16:05:40PROVISO - PROVIDE FIXTURE CALCS AT INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-03 Cont ID  
Sent By shill Date 2017-03-03 Time 07:18 Rev Time 0.00
Received By shill Date 2017-03-03 Time 07:18 Sent To  
Notes
2017-03-03 07:19:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED LIGHT
 POLES, FBC 1609. INCLUDE WIND DESIGN CRITERIA.
  
 2. PROVIDE CALCS FOR THE LIGHT POLES AND FIXTURES, FBC
 1609.
  
 IT IS NOT CLEAR HOW THESE ITEMS WERE ADDRESSED. A
 RESPONSE LETTER WAS NOT PROVIDED, AND IT DOES NOT
 APPEAR THAT THIS INFORMATION WAS ADDED TO THE PLAN. IF
 YOU FEEL THAT THIS INFORMATION IS INCLUDED IN THE
 SUBMITTAL, PLEASE ADVISE AS TO FILE NAMES. A DETAIL ON
 AN ELECTRICAL SHEET WAS PROVIDED BUT IS NOT A COMPLETE
 STRUCTURAL DETAIL.
  
 S003 INCLUDES WIND DESIGN CRITERIA, BUT I WAS NOT ABLE
 TO LOCATE AN S SHEET WITH THE STRUCTURAL DETAIL FOR THE
 LIGHT POLES, AND WAS NOT ABLE TO LOCATE THE
 CALCULATIONS FOR THE POLES AND FIXTURES. THIS
 INFORMATION IS OFTEN PROVIDED BY THE SPECIALTY
 ENGINEER. IF PROVIDED BY A SPECIALTY ENGINEER, HAVE THE
 DELEGATED ENGINEERING REVIEWED BY DOR PRIOR TO
 SUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By shill Date 2016-08-18 Time 17:33 Rev Time 0.00
Received By shill Date 2016-08-18 Time 17:33 Sent To  
Notes
2016-08-18 17:34:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED LIGHT
 POLES, FBC 1609. INCLUDE WIND DESIGN CRITERIA.
  
 2. PROVIDE CALCS FOR THE LIGHT POLES AND FIXTURES, FBC
 1609.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-05-12 Cont ID  
Sent By jleahy Date 2017-05-12 Time 15:55 Rev Time 0.00
Received By jleahy Date 2017-05-12 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-03-07 Cont ID  
Sent By vperez Date 2017-03-07 Time 11:52 Rev Time 0.00
Received By vperez Date 2017-03-07 Time 11:52 Sent To  
Notes
2017-03-07 11:53:33PLEASE ADDRESS ZONING COMMENTS FOR AN ELECTRICAL
 APPROVAL.
  
 V. PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-02 Cont ID  
Sent By vperez Date 2016-07-02 Time 11:17 Rev Time 0.00
Received By vperez Date 2016-07-02 Time 11:17 Sent To  
Notes
2016-07-02 11:18:15PENDING ZONING APPROVAL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-29 Cont ID  
Sent By vperez Date 2016-03-29 Time 13:13 Rev Time 0.00
Received By vperez Date 2016-03-29 Time 13:13 Sent To  
Notes
2016-03-29 13:13:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE ADDRESS ZONING COMMENTS FOR A COMPLETE
 ELECTRICAL REVIEW.
 2. PLEASE PROVIDE ENGINEERED POLE DETAILS TO WITHSTAND
 WIND LOADS FOR AREA OF INSTALLATION
 3. BUILDING REVIEW WILL BE REQUIRED FOR THE STRUCTURAL
 CONCRETE POLE BASE DESIGN.
 4. COULD NOT LOCATE PHOTOMETRICS UNDER ORIGINAL
 SUBMITTAL PLEASE CLARIFY.
 5. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-16 Cont ID  
Sent By lmarchan Date 2017-05-16 Time 15:58 Rev Time 0.00
Received By lmarchan Date 2017-04-21 Time 13:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-07 Cont ID  
Sent By vperez Date 2017-03-07 Time 11:53 Rev Time 0.00
Received By vperez Date 2017-03-07 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-18 Cont ID  
Sent By shill Date 2016-08-18 Time 17:34 Rev Time 0.00
Received By shill Date 2016-06-21 Time 14:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2017-04-25 Cont ID  
Sent By shill Date 2017-04-25 Time 16:10 Rev Time 0.00
Received By shill Date 2017-04-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-03-03 Cont ID  
Sent By shill Date 2017-03-03 Time 07:26 Rev Time 0.00
Received By shill Date 2017-03-03 Time 07:26 Sent To  
Notes
2017-03-03 07:27:05PROVISO - NEW SHEETS AND DOCUMENTS SUBMITTED FOR REVIEW
 #3 TO BE REVIEWED FOR DIGITAL SIGNATURE
 SHEETS SUBMITTED TO DATE (A, E, S) SIGNATURES OK
  

Review Stop Z ZONING
Rev No 4 Status P Date 2017-05-16 Cont ID  
Sent By eschneid Date 2017-05-16 Time 14:30 Rev Time 0.50
Received By eschneid Date 2017-05-16 Time 14:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2017-02-28 Cont ID  
Sent By eschneid Date 2017-02-28 Time 17:23 Rev Time 0.50
Received By eschneid Date 2017-02-28 Time 17:23 Sent To  
Notes
2017-02-28 17:22:45FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) PLEASE EXPLAIN WHY THE FX12A GRADE RECESSED UPLIGHTS
 ARE CAUSING SUCH HIGH FOOTCANDLES (WEST OF EITHER ENTRY
 DRIVE. HOW WILL GLARE INTO THE OKEECHOBEE BOULEVARD
 RIGHT-OF-WAY BE PREVENTED GIVEN THESE HIGH OUTPUTS?
  
 2) THE SITE LAYOUT IS DIFFERENT FROM THE ONE APPROVED
 BY RESOLUTION NO. 260-16. PRIOR TO THE C.O. OF THE
 BUILDING THE AS BUILT PLANS SHALL BE SUBMITTED TO THE
 PLANNING DIVISION AS A MINOR AMENDMENT.
  
 3) PRIOR TO C.O., PROVIDE STAFF WITH THE FDOT PERMIT
 AND SIGN-OFF FOR THE LIGHTS WITHIN THE RIGHT-OF-WAY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-22 Cont ID  
Sent By eschneid Date 2016-07-22 Time 12:02 Rev Time 0.75
Received By eschneid Date 2016-07-22 Time 12:02 Sent To  
Notes
2016-07-22 12:02:18FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE SITE LAYOUT SHOWN ON THE PLANS IS DIFFERENT FROM
 THE APPROVED PLANS. THE PROPOSED SITE LAYOUT IS
 TENTATIVELY SCHEDULED TO BE HEARD BY THE CITY
 COMMISSION ON AUGUST 29, 2016. ZONING CANNOT GIVE FINAL
 APPROVAL OF THE PERMIT UNTIL AFTER THE COMMISSION
 APPROVAL.
  
 2) REPEAT COMMENT: THERE CONTINUE TO BE LIGHTS SHOWN ON
 THE ELECTRICAL SITE PLAN THAT ARE NOT LISTED ON THE
 ELECTRICAL SCHEDUL, EX. - ALL OF THE FX SERIES OF
 LIGHTS.
  
 3) REPEAT COMMENT: LIGHTS MAY NOT BE MOUNTED IN THE
 TREES. THE ELECTRICAL SCHEDULE LISTS TREE TYPES F10 AND
 F10A AS TREE MOUNTED.
  
 4) REPEAT COMMENT: NO PHOTOMETRIC PLAN WAS PROVIDED.
  
 5) THE ELECTRICAL SITE PLAN SHOWS AN F11 LIGHT TYPE
 THAT IS NOT LISTED ON THE ELECTRICAL SCHEDULE. IS THIS
 SUPPOSED TO BE THE FS2 BOLLARD LIGHT?
  
 6) HOW TALL ARE THE BOLLARD LIGHTS?
  
 7) WHAT DOES THE WR TYPE OF LIGHT LOOK LIKE? IT IS NOT
 SHOWN ON SHEET LGT 251.1. DOES ANY PART OF THE WR LIGHT
 EXTEND ABOVE THE WALL?
  
 8) PROVIDE DETAILS, TO INCLUDE POLE HEIGHT, FOR THE
 FS21 TYPE LIGHT.
  
 9) THE ELECTRICAL SITE PLAN SHOWS THE POLE PLUS FIXTURE
 FOR TYPE FS1 AT 16 FEET IN HEIGHT. THE ELECTRICAL
 SCHEDULE LISTS TYPE FS1 AS HAVING A 10 FOOT POLE WITH A
 12 OVERALL HEIGHT. ALL PLANS SHALL SHOW SAME
 CONDITIONS. PLEASE NOTE THAT THE 12 FOOT HEIGHT WORKS
 BETTER WITH THE SPECIFIC TREES AND THEIR LOCATIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-01-26 Cont ID  
Sent By eschneid Date 2016-01-26 Time 17:59 Rev Time 0.25
Received By eschneid Date 2016-01-26 Time 17:59 Sent To  
Notes
2016-01-26 18:12:13FAILED
  
 1) THE SITE, LANDSCAPE AND CIVIL PLANS SHOW EIGHT LIGHT
 POLES AROUND THE PARKING LOT. THE ELECTRICAL SITE PLAN
 SHOWS 19 POLES (FS1) AROUND THE PARKING LOT, TO INCLUDE
 ONE IN THE DRAIN FLUE. THE 19 POLES SEEM EXCESSIVE.
  
 2) THE POLE SHOWN ON SHEET E050 IS LABELED AS F51, YET
 THIS DOES NOT EXIST ON THE PLAN.
  
 3) LIGHTS MAY NOT BE MOUNTED IN THE TREES.
  
 4) NO PHOTOMETRIC PLAN WAS PROVIDED.
  
 5) WHERE ARE THE DETAILS FOR THE BOLLARD LIGHTS AND THE
 WALL PACKS.
  
 6) WHAT ARE THE WP, WR AND LA SERIES OF LIGHTS AND WHAT
 DO THEY LOOK LIKE?
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.