Plan Review Details - Permit 16010503
Plan Review Stops For Permit 16010503
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-03 Cont ID  
Sent By albarran Date 2016-02-03 Time 10:33 Rev Time 0.00
Received By albarran Date 2016-02-03 Time 18:57 Sent To I
Notes
2016-02-03 10:35:38I CALLED THE OFFICE AND LEFT A MESSAGE FOR GEORGE TO
 CALL ME BACK. I CAN USE THE ATTACHED PROPOSAL IN LIEU
 OF THE SCOPE OF WORK BUT DOES HE WANT THIS MADE
 AVAILABLE TO THE EMPLOYEES.
  
 1ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. THE PLANS AS SUBMITTED DO NOT MEET MINIMUM CODE
 STANDARDS AND REQUIREMENTS. YOU SHALL INCLUDE ON THE
 DRAWINGS YOUR SCOPE OF WORK AND THE SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 2. YOU SHALL INCLUDE THE SIZE AND TYPE OF CONDUCTOR.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-28 Cont ID  
Sent By albarran Date 2016-01-28 Time 10:26 Rev Time 0.00
Received By albarran Date 2016-01-28 Time 09:00 Sent To I
Notes
2016-01-28 10:26:26THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. WPB AMENDMENTS TO FBC SECTION 107.2.1 - SUBMITTAL
 DOCUMENTS REQUIRES THAT AMONG OTHER THINGS, THE PLANS
 BE DRAWN WITH SUFFICIENT CLARITY TO INDICATE THE
 LOCATION OF THE JOB (ADDRESS) NATURE AND EXTENT OF THE
 WORK PROPOSED (SCOPE) AND SHOW THAT IT WILL CONFORM TO
 THE PROVISIONS OF THE CODE (INCLUDE CODE EDITION).
 FURTHERMORE ALL INFORMATION, DRAWINGS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 2. WPB AMENDMENTS TO FBC SECTION 107.2.5 - YOU SHALL
 PROVIDE A SIMPLE SITE PLAN TO INDICATE THE LOCATION OF
 THE PROPOSED WORK.
 3. YOU SHALL INCLUDE AN INTER-SYSTEM BONDING TERMINAL
 AS DICTATED IN NEC 250.694
 4. INDICATE THE FUSE RATING FOR THE MAIN TO THE
 PROPOSED PANEL.
 5. THE SUBMITTED PANEL SCHEDULES LABELS DO NOT MATCH
 THE RISER DIAGRAM. CORRECT THE LABELS SO I CAN FOLLOW
 THE RISER.
 6. YOU SHALL SUBMIT TWO COPIES OF THE DOCUMENTS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-03 Cont ID  
Sent By albarran Date 2016-02-03 Time 19:18 Rev Time 0.00
Received By albarran Date 2016-01-28 Time 15:22 Sent To  
Notes
2016-02-03 19:19:272/3/16 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT FILE TO SMALL READY BIN "A". MA
2016-01-28 15:22:20ROUTED TO ALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-28 Cont ID  
Sent By albarran Date 2016-01-28 Time 10:28 Rev Time 0.00
Received By albarran Date 2016-01-19 Time 13:18 Sent To  
Notes
2016-01-28 10:28:461/28/16 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT FILE TO SMALL DENIED BIN "A".MA
2016-01-20 13:18:49ELEC <5K