| 2016-02-03 06:26:03 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010495 |
| | ADD: 2060 PALM BEACH LAKES BLVD |
| | CONT: DM CONSTRUCTION |
| | TEL: 561-281-2311 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 03/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET UNDER THE HEADING OCCUPANT TYPE HAS |
| | THE OCCUPANT YTYPE AS MERCANTILE, UNDER THE 2010 FBC-B |
| | THIS WAS CORRECT. UNDERTHE 2014 FBC-B WHEN A RESTARAUNT |
| | HAS A OCCUPANT LOAD OF LESS THAN 50 IT IS CONSIDERED |
| | SMALL ASSEMBLY AND CLASSIFIED AS A GROUP B OCCUPANCY, |
| | 2014 FBC-B 303.1.2(1).. |
| | |
| | 2) SHEET A1.1 SHOWS ON THE INTERIOR OF THE TENANT SPACE |
| | 40 SEATS FOR THE RESTARAUNT. THE 2014 FBC-ACCESSIBILITY |
| | CODE SECTION 226.1 REQUIRES DINING SURFACES ARE |
| | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST |
| | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902 |
| | |
| | 3) NOTE IF THERE IS EXTERIOR SEASONAL SEATING THEN |
| | THOUGHS SEATS WILL ALSO NEED TO BE CONSIDERED IN THE 5 |
| | % OF THE OVERAL SEATING. COMPLIANCE WITH 226.2 OF THE |
| | ACCESSIBILITY CODE WOULD ALSO THEN BE A ISSUE. 226.2 |
| | DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED |
| | TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE |
| | SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK |
| | SURFACES. |
| | |
| | 4) THE DINING TABLE TOPS FOR THE ACCESSIBLE TABLES WILL |
| | NEED TO COMPLY WITH: 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 5) SHEET A2.1 & A2.2 SHOW A NEW PERGOLA, THIS IS |
| | CONSIDERED DECRATIVE INTERIOR TRIM AND WILL NEED TO |
| | MEET THE REQUIREMENTS OF 806.5 INTERIOR TRIM. |
| | MATERIAL, OTHER THAN FOAM PLASTIC USED AS INTERIOR |
| | TRIM, SHALL HAVE A MINIMUM CLASS C FLAME SPREAD AND |
| | SMOKE-DEVELOPED INDEX WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 84 OR UL 723, AS DESCRIBED IN SECTION 803.1.1. |
| | CLASS C FLAME SPREAD INDEX 76-200 / SMAOKE DEVELOPMENT |
| | OF 0-450. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |