| Plan Review Stops For Permit 16010493 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-02-09 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-02-09 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-02-09 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-02-09 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-02-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-02-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-02-11 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-01-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-01-26 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2016-01-26 13:00:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. PER NFPA 241- STANDARD FOR SAFEGUARDING | | | CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, | | | SECTION 4.2 TEMPORARY OFFICES AND SHEDS SHALL BE | | | SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN | | | ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | 2. PROVIDE A SITE PLAN, INCLUDING ALL DIMENSIONS TO | | | PROPOERTY LINES AND EXISTING AND PROPOSED BUILDINGS | | | THAT COMPLY WITH NFPA 241 AS NOTED ABOVE. | | | | | | 3. PROVIDE A STATEMENT INDICATING THE INSTALLATION OF A | | | FIRE SPRINKLER SYSTEM UNDER SEPARATE SHOP DRAWINGS IF | | | APPLICABLE FOR THE 75 PERCENT REDUCTION NOTED ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-02-23 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-02-23 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-02-09 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-02-09 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-01-19 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-02-09 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-02-09 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-02-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-05 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-05 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2016-02-05 08:04:47 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010493 | | | 2/5/16 | | | | | | 1) PLEASE REFER TO PARAGRAPH 3 OF THE SUBMITTED LETTER | | | FROM ROBERT LORENZO- DBPR MANUFFACTURED BUILDINGS | | | PROGRAM: "EACH CODE CHANGE WILL MAKE YOUR PLANS | | | OBSOLETE UNTIL THEY HAVE BEEN REVIEWED, APPROVED AND | | | INDICATED (ON THE FRONT COVER PAGE OF THE PLANS) FOR | | | COMPLIANCE WITH THE CODE BY YOUR THIRD PARTY AGENCY FOR | | | PLANS REVIEW". | | | PLEASE NOTE THE FRONT COVER PAGE OF THE SUBMITTED PLANS | | | IS INDICATING DESIGN IN ACCORDANCE WITH THE 2010 | | | FLORIDA BUILDING CODES, HOWEVER THE CURRENT CODE IN | | | EFFECT IS 2014- PLEASE UPDATE AND RE-SUBMIT THE PLANS | | | ACCORDINGLY | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-02-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-02-10 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-02-10 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-01-24 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-24 |
Time |
04:49 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-24 |
Time |
04:31 |
Sent To |
|
|
| Notes |
| 2016-01-24 04:41:01 | 1)SUBMIT A SITE PLAN SHOWING HOW WATER AND SEWER | | | SERVICE WILL BE PROVIDED TO THE MODULAR STRUCTURE.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 2) IF THE STRUCTURE WILL DISCHARGE TO A SEWAGE TANK, | | | SHOW THE LOCATION ON THE SITE PLAN AND INDICATE THE | | | CAPACITY OF THE TANK. TANKS EXCEEDING 300 GALLONS | | | REQUIRE A PERMIT FROM THE PALM BEACH COUNTY HEALTH | | | DEPT. | | | 3) THE WATER SERVICE TO THE STRUCTURE SHALL BE | | | PROTECTED BY A BACKFLOW PREVENTION DEVICE. THE DEVICE | | | SHALL BE LEAD FREE. SUBMIT TWO COPIES OF THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE BACKFLOW | | | PREVENTION DEVICE.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-02-23 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-02-23 |
Time |
10:52 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2016-02-23 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2016-02-23 10:52:31 | THE CONSTRUCTION TRAILER SHALL BE REMOVED WITHIN SEVEN | | | DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE CITY | | | AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-01-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-01-29 |
Time |
09:03 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2016-01-28 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2016-01-29 09:09:58 | FAILED | | | | | | 1) PROVIDE TWO COPIES OF THE SURVEY FOR THE SITE. | | | | | | 2) PROVIDE THE SITE PLAN FOR THE SITE THAT SHOWS THE | | | LOCATION OF THE TRAILER, THE ADA RAMP AND THE REQUIRED | | | FIVE (5) PARKING SPACES. IF AN ADA PARKING SPACE IS | | | REQUIRED, THEN IT SHALL BE PROVIDED (MAY BE ONE OF THE | | | FIVE SPACES) AND BE PAVED AND HAVE A PAVED ACCESS AISLE | | | AND BE APPROPRIATELY MARKED. DIMENSIONS TO THE PROPERTY | | | LINE AND FOR THE TRAILERS AND PARKING SHALL BE SHOWN ON | | | THE SITE PLAN. | | | | | | 3) THE CONSTRUCTION TRAILER SHALL BE REMOVED WITHIN | | | SEVEN DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE | | | CITY AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY. | | | | | | 4) THE TRAILER ITSELF COMPLIES WITH ZONING STANDARDS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|