| Notes |
| 2016-01-22 12:56:58 | ELECTRICAL PROVISO TO PERMIT 16010486 | | | | | | 1. NEC 314.27(A) BOXES USED AT LUMINAIRE OR LAMPHOLDER | | | OUTLETS IN A CEILING SHALL BE REQUIRED TO SUPPORT A | | | LUMINAIRE WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE | | | NOTES ON CEILING BOXES ON PAGE. | | | 2. NEC 314.27(D) BOXES USED FOR THE SOLE SUPPORT OF | | | CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS | | | SUITABLE FOR THE PURPOSE, AND INDICATE THE WEIGHT | | | LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT PADDLE | | | FANS HEAVIER THAN 70 LBS. | | | 3. NEC 404.4. WHERE SWITCHES CONTROLLING LIGHTING LOADS | | | SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE GROUNDED | | | BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING | | | CIRCUIT SHALL BE PROVIDED AT THE SWITCH. | | | |
|
|