| 2016-01-22 13:13:02 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. THE APPLICABLE EDITION OF THE NEC IS THE 2011, AS |
| | REFERENCED IN THE 5TH EDITION OF THE FBC-2014. CORRECT |
| | ELECTRICAL LIGHTING SITE KEY NOTE 5. |
| | 2. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS |
| | PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL |
| | INSPECTOR. NO SITE TUBES WILL BE ACCEPTED |
| | 3. PROTECTION SHALL BE PROVIDED AT THE ENDS OF THE |
| | UNI-STRUT. END CAPS REQUIRED. |
| | 4. PHYSICAL PROTECTION FOR THE RACK AS DESCRIBED IN NEC |
| | 110.27(B) SHALL BE PROVIDED. |
| | 5. PROVIDE A LIGHT DENSITY ALLOWANCE CHART AS PER |
| | FBC-EC405.6.2; THIS SHALL INCLUDE EXISTING LIGHTING IN |
| | ADDITION TO THE PROPOSED. |
| | 6. PROVIDE SPECS FOR THE PROPOSED SIGNS. |
| | 7. NEC 408.4 REQUIRES A CIRCUIT DIRECTORY, THE SIGN |
| | CIRCUITS DO NOT APPEAR ON THE PANEL SCHEDULE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| | NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |