Plan Review Details - Permit 16010436
Plan Review Stops For Permit 16010436
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-02 Cont ID  
Sent By jwitmer Date 2016-09-02 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2016-09-02 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-04 Cont ID  
Sent By jwitmer Date 2016-02-04 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2016-02-04 Time 08:30 Sent To ENG
Notes
2016-02-04 11:30:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010436
 ADD: 326 FERN ST
 CONT: CB & I ENVIRONMENTAL & INFRASTRUCTURE
 TEL: 813-612-3678
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB. 04/ 2016
 ACTION: DENIED
  
 1) CBI PLANS SHEET # 9 WITH ENCLOSURE PANEL NOTES FOR
 THE WALL SYSTEM FL6231.3 THIS PRODUCT APPROVAL WAS
 UNDER THE 2007 FBC AND NOTE A CURRENT PRODUCT APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(G) EXTERIOR COOLER, FREEZERS
 2) CBI PLANS SHEET 8 PROVIDES THE WIND DESIGN AS 170
 VULT EXPOSURE B, THE BUILDING RISK CATEGORY I. FOR A
 BUILDING WITH A RISK CATEGORY I THE WIND SPEED IS 160
 VULT, INTERPOLATION BETWEEN THE CONTOUR LINES WILL
 PLACE THE WIND SPEED AT 155. THERE IS A DISCREPANCY
 BETWEEN THE WIND DESIGN SPEED AND THE RISK CATEGORY.
 SEE FBC-B TABLE 1604.5 AND FIGURES FIGURE1609A AND
 FIGURE 1609C.
  
 3) THE SUBMITTED FLORIDA APPROVAL15491.1-R3. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) PLEASE IDENTIFY BY CIRCLING FOR ENCLOSED STRUCTURES,
 MAXIMUM ALLOWABLE CLEAR SPAN, THE WIND SPEED, EXPOSURE
 LIVE LOADS AND UPLIFT AND DEFLECTION LIMITS AS WELL AS
 THE PANEL THICKNESS GAUGE OF SKIN FOR EVALUATION FOR
 CODE COMPLIANCE. . EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?2014 FBC-B 1604.4 ANALYSIS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-01 Cont ID  
Sent By vperez Date 2016-09-01 Time 07:04 Rev Time 0.00
Received By vperez Date 2016-09-01 Time 07:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By vperez Date 2016-02-11 Time 12:40 Rev Time 0.00
Received By vperez Date 2016-02-11 Time 12:40 Sent To  
Notes
2016-02-11 12:44:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE REVISE MAIN FUSES SELECTED TO SHOW 60AMP NOT
 40AMP WHICH IS UNDER THE REQUIRED SERVICE SIZE PER NEC
 230.79D
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-08-26 Cont ID  
Sent By Mgonzale Date 2016-08-26 Time   Rev Time 1.00
Received By mgonzale Date 2016-08-26 Time   Sent To I
Notes
2016-08-26 10:37:29NO CONFLICT WITH UTILITIES.
  
 CALL 811 BEFORE DIG
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-02 Cont ID  
Sent By jwitmer Date 2016-09-02 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2016-08-26 Time 09:31 Sent To  
Notes
2016-08-31 09:32:26RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-26 Cont ID  
Sent By cpuell Date 2016-08-26 Time 13:17 Rev Time 0.00
Received By cpuell Date 2016-01-20 Time 11:14 Sent To  
Notes
2016-01-20 11:28:30C15

Review Stop Z ZONING
Rev No 1 Status N Date 2016-03-16 Cont ID  
Sent By aaponte Date 2016-03-16 Time 16:25 Rev Time 0.00
Received By aaponte Date 2016-03-16 Time 16:25 Sent To  
Notes
***NONE***