Plan Review Details - Permit 16010419
Plan Review Stops For Permit 16010419
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-09-13 Cont ID  
Sent By jwitmer Date 2016-09-13 Time 05:58 Rev Time 0.00
Received By jwitmer Date 2016-09-13 Time 05:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-11 Cont ID  
Sent By jwitmer Date 2016-08-11 Time 10:34 Rev Time 0.00
Received By jwitmer Date 2016-08-11 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-01-21 Cont ID  
Sent By jwitmer Date 2016-01-21 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2016-01-21 Time 06:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-13 Cont ID  
Sent By vperez Date 2016-09-13 Time 13:51 Rev Time 0.00
Received By vperez Date 2016-09-13 Time 13:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-12 Cont ID  
Sent By vperez Date 2016-08-12 Time 07:30 Rev Time 0.00
Received By vperez Date 2016-08-12 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-09 Cont ID  
Sent By rlecky Date 2016-02-09 Time 14:27 Rev Time 0.00
Received By rlecky Date 2016-02-09 Time 14:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-09-12 Cont ID  
Sent By scaldero Date 2016-09-12 Time 11:07 Rev Time 0.00
Received By scaldero Date 2016-09-12 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-18 Cont ID  
Sent By scaldero Date 2016-08-18 Time 14:17 Rev Time 0.00
Received By scaldero Date 2016-08-18 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-26 Cont ID  
Sent By scaldero Date 2016-01-26 Time 12:11 Rev Time 0.00
Received By scaldero Date 2016-01-26 Time 12:06 Sent To  
Notes
2016-01-26 12:11:46PERMIT # 16010419
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-16 Cont ID  
Sent By cpuell Date 2016-09-16 Time 11:34 Rev Time 0.00
Received By cpuell Date 2016-09-08 Time 15:50 Sent To  
Notes
2016-09-09 15:50:35B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-22 Cont ID  
Sent By scaldero Date 2016-08-22 Time 13:37 Rev Time 0.00
Received By scaldero Date 2016-08-05 Time 14:40 Sent To  
Notes
2016-08-08 14:40:22B31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-09 Cont ID  
Sent By rlecky Date 2016-02-09 Time 14:27 Rev Time 0.00
Received By rlecky Date 2016-01-14 Time 11:58 Sent To  
Notes
2016-01-19 11:58:22B25

Review Stop Z ZONING
Rev No 3 Status P Date 2016-09-16 Cont ID  
Sent By eschneid Date 2016-09-16 Time 11:04 Rev Time 0.25
Received By eschneid Date 2016-09-16 Time 11:04 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-17 Cont ID  
Sent By eschneid Date 2016-08-17 Time 15:32 Rev Time 0.25
Received By eschneid Date 2016-08-17 Time 09:13 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-01-28 Cont ID  
Sent By eschneid Date 2016-01-28 Time 14:32 Rev Time 0.25
Received By eschneid Date 2016-01-28 Time 14:24 Sent To  
Notes
2016-01-28 14:33:31FAILED
  
 1) LANDLORD APPROVAL STAMP IS REQUIRED ON THE PLANS.
  
 2) OTHERWISE, PLANS COMPLY WITH ZONING REQUIREMENTS.