Plan Review Details - Permit 16010403
Plan Review Stops For Permit 16010403
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-12 Cont ID  
Sent By jwitmer Date 2016-05-12 Time 07:41 Rev Time 0.00
Received By jwitmer Date 2016-05-12 Time 07:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 06:23 Rev Time 0.00
Received By jwitmer Date 2016-03-15 Time 05:46 Sent To  
Notes
2016-03-15 06:23:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010403
 ADD: 2255 PALM BEACH LAKES BLVD
 CONT: MCCABE BROTHERS
 TEL: 561-278-0404
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 15/ 2016
 ACTION: DENIED
  
 1) NEW COMMENT, DISCREPANCY IN PLANS, 107.2.1.3. THE
 A5.0 SHEET AND P2.1 SHEET DO NOT MATCH. THE NEW P2.1
 SHEET SHOWS A NEW SHOWER IN THE
 1ST FLOOR MENS RESTROOMS WHERE THE ARCHITECTURAL SHEETS
 DO NOT. IF THIS IS A REVISION TO THE PLANS THEN THE
 SHOWER WILL NEED TO BE ACCESSIBLE SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE:
  
 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET
 ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH
 603. WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING
 ROOM SHALL COMPLY WITH 603.
  
 213.3 PLUMBING FIXTURES AND ACCESSORIES. PLUMBING
 FIXTURES AND ACCESSORIES PROVIDED IN A TOILET ROOM OR
 BATHING ROOM REQUIRED TO COMPLY WITH 213.2 SHALL COMPLY
 WITH 213.3.
  
 213.3.6 BATHING FACILITIES. WHERE BATHTUBS OR SHOWERS
 ARE PROVIDED, AT LEAST ONE BATHTUB COMPLYING WITH 607
 OR AT LEAST ONE SHOWER COMPLYING WITH 608 SHALL BE
 PROVIDED.
  
 608.1 GENERAL. SHOWER COMPARTMENTS SHALL COMPLY WITH
 608. 608.2 SIZE AND CLEARANCES FOR SHOWER COMPARTMENTS.
 SHOWER COMPARTMENTS SHALL HAVE SIZES AND CLEARANCES
 COMPLYING WITH 608.2.
  
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. TRANSFER
 TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES (915 MM) BY
 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS MEASURED AT
 THE CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36
 INCH (915 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE
 SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES (915 MM)
 WIDE MINIMUM BY 48 INCHES (1220 MM) LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
  
 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM)
 DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-26 Cont ID  
Sent By jwitmer Date 2016-01-26 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2016-01-26 Time 05:58 Sent To  
Notes
2016-01-26 09:30:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010403
 ADD: 2255 PALM BEACH LAKES BLVD
 CONT: MCCABE BROTHERS
 TEL: 561-278-0404
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 26/ 2016
 ACTION: DENIED
  
 1) THE COVERSHEET A1.0:
 1A) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010
 FBC. PLEASE BE AWARE THE EDITION OF THE CODE CHANGED ON
 JUNE 30/ 2015 TO THE 5TH EDITION (2014) OF THE FLORIDA
 BUILDING CODE.
  
 1B) ONLY THE COVERSHEET, A1.0 HAS AN ORIGINAL SIGNATURE
 AND SEAL THE REST OF THE SHEETS WITHIN THE SET OF PLAN
 HAVE SEALS AND COPIED SIGNATURES.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS.
 2) SHEET A2.0:
 2A) THIS BUILDING IS BEING CLASSIFIED AS A TYPE II
 BUILDING. PLEASE IDENTIFY UNDER WHICH CODE YOU ARE
 CLASSIFYING THIS BUILDING TYPE AS A TYPE II BUILDING.
 UNDER THE 2001 FBC-B THE BUILDING TYPE II WAS
 RECLASSIFIED AS A BUILDING TYPE IA UNDER THE 2004 FBC
 AND SINCE. SEE 2007 CODE COMMENTARY FIGURE 600.
  
 2B) IN THE OCCUPANCY CLASSIFICATIONS WAREHOUSE 33,112
 SQ. FT./500= 66 OCCUPANTS, & BUSINESS 2528 SQ.
 FT./100=25 OCCUPANTS. PLEASE BE AWARE YOU ALWAYS ROUND
 UP TO THE NEXT WHOLE PERSON YOU HAVE NO PARTIAL PEOPLE.
 2014 FBC-B 1004.1.
  
 BOAF INFORMAL CODE INTERPRETATION
 DATE: TUE DEC 18 2007
 REPORT #: 5479
 CODE: BUILDING
 SECTION: 1004.1.2
 QUESTION:
 IS IT THE INTENT OF SECTION 1004.1.2 TO ALLOW THE
 LARGEST NUMBER COMPUTED IN ACCORDANCE WITH
 TABLE 1004.1.2 TO BE ROUNDED TO THE NEAREST WHOLE
 NUMBER? COMMENT: FOR EXAMPLE, A
 BUSINESS OCCUPANCY IN A BUILDING WITH 3215 GROSS SQUARE
 FEET, CALCULATED OCCUPANCY LOAD
 WOULD BE 32.15 WOULD I ROUND DOWN TO 32 OCCUPANTS OR
 WOULD I BE REQUIRED TO ROUND UP TO
 33 OCCUPANTS
 ANSWER:
 ROUND UP TO 33
 COMMENTARY:
 OCCUPANTS ONLY COME AS A WHOLE.
  
 2C) WITHIN THIS SET OF PLANS THERE IS NO LIFE SAFETY
 PLAN THAT PROVIDES:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (6.) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED(SEPARATION).
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
 )7.) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 2D) PLEASE BREAK DOWN THE OCCUPANT LOADS FOR THE 1ST
 FLOOR AND 2ND FLOOR (MEZZANINE) BY FLOOR AND BY
 OCCUPANCY TYPE. THE 2ND FLOOR, (MEZZANINE) INDICATES
 555 SQ. FT. OF CHANGE OF OCCUPANCY, BUT DOES NOT
 INDICATE THE OVERALL SQUARE FEET OF THE 2ND FLOOR
 (MEZZANINE). I HAVE ADDED UP THE SQUARE FOOTAGE OF THE
 2ND FLOOR AREA AND IS APPROXIMATELY 1050 SQUARE FEET.
 1050/100= 11 OCCUPANTS. THE AREA BELOW THE 2ND FLOOR IS
 AN ENCLOSED AREA AND DOES NOT COMMUNICATE (THE AIR)
 WITH A MEZZANINE, NOR DOES THE 2ND FLOOR WHICH NOW IS
 FULLY ENCLOSED. THE OCCUPANT LOAD IS GREATER THAN 10
 AND DOES NOT MEET THE EXCEPTIONS OF 505.2.3 AND WILL
 NEED TO BE CONSIDERED A 2ND FLOOR.
 PLEASE REVIEW SECTIONS IN THE 2014 FBC-B:
 FBC-B 1009.3 EXCEPTION # 1.
 FBC-B 1016.3.1
 FBC-B TABLE 1016.2 ALLOWABLE TRAVEL DISTANCE.
  
 NOTE THE TABLE 508.4 BUSINESS AND S1 OCCUPANCIES
 INDICATES NO OCCUPANCY SEPARATION. PLEASE REVIEW BOAF
 INFORMAL INTERPRETATION: 7357
  
 DATE: TUE JUL 1 2014
 REPORT: 7357
 CODE: BUILDING CODE YEAR: 2010
 SECTION: TABLE 508.4
 QUESTION:
 IS IT THE INTENT OF TABLE 508.4 TO REQUIRE A (1HR (S),
 2HR (NS)) SEPARATION BETWEEN B AND S-2 OCCUPANCY AND NO
 SEPARATION
 REQUIREMENT BETWEEN B AND S-1 OCCUPANCY?
 COMMENT:
 PER CHAPTER 3, S-2 OCCUPANCY ARE DEFINED AS LOW- HAZARD
 STORAGE, WHERE AS S-1 OCCUPANCY IS DEFINED AS
 MODERATE-HAZARD OCCUPANCY. THE STORED MATERIALS LIST
 FOR S-1 OCCUPANCY IS MUCH MORE HAZARDOUS THAN THE LIST
 FOR S-2 OCCUPANCY AND ONE WOULD THINK THAT THE S-1
 OCCUPANCY WOULD REQUIRE THE SEPARATION AND THE S-2
 OCCUPANCY WOULD NOT.
 ANSWER:
 BASED ON THE INFORMATION REVIEWED, IT APPEARS YOU ARE
 CORRECT THAT A TYPO EXISTS. THE BEST APPROACH FOR THIS
 PARTICULAR ISSUE WOULD BE EITHER A FORMAL
 INTERPRETATION WHICH HAS STANDING OR A DEC STATEMENT
 FROM THE FLORIDA BUILDING COMMISSION. PLEASE SEE THE
 COMMENTARY BELOW.
 COMMENTARY:
 TABLE 508.4 DOES APPEAR TO HAVE A TYPO. THE 2001
 FLORIDA BUILDING CODE, TABLE 704.1 REQUIRED A 3 HOUR
 SEPARATION FOR S1 AND A 2 HOUR SEPARATION FOR S2. IN
 THE 2004 CODE TABLE 706.3.7 ALSO REQUIRES 3 HOURS FOR
 S1 AND 2 HOURS FOR S2. THE TYPO APPEARS TO HAVE BEEN
 INTRODUCED WITH TABLE 508.4 IN THE 2007 CODE. TABLE
 508.4 APPEARS TO HAVE BEEN WRONG SINCE ITS INCEPTION.
 SUBMITTING A REQUEST FOR A FORMAL INTERPRETATION WOULD
 PERMIT APPLICATION OF CORRECTION TO THIS ISSUE UNTIL A
 CODE CHANGE CAN BE MADE, IF IT IS NOT ALREADY IN THE
 WORKS.
  
 YOU CAN?T TAKE THE OCCUPANTS OF A BUSINESS OCCUPANCY
 THROUGH A OCCUPANCY WITH A HIGHER OCCUPANCY HAZARD
 WITHOUT THE STAIR BEING IN A 1 HOUR ENCLOSURE.
  
 2E) THE TABLE FOR FIRE RESISTANCE RATINGS FOR BUILDING
 ELEMENTS, INDICATES ZERO HOURS FIRE RATING FOR THE ROOF
 CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS. IN THE
 2014 FBC-B TABLE 601 INDICATES FOR BUILDING TYPE 1B OR
 IIA, 1 HOUR FIRE RATING REQUIRED, MEZZANINE LEVEL, SEE
 EXCEPTION ?B?.
  
 2F) THIS IS AN EXISTING BUILDING AND IS SUBJECT TO THE
 2014 EXISTING BUILDING CODE SECTION 301.1. THE DESIGNER
 OF RECORD WILL NEED TO SHOW THE PLANS WERE DESIGNED
 UNDER ONE OF THE METHODS LISTED, 301.1.1THROUGH
 301.1.3. IF THE WORK AREA METHOD IS PICKED THEN TO WHAT
 LEVEL OF ALTERATION WERE THE PLANS DESIGNED?
  
 2G) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 3) SHEET A4.0 :
 3A) WITH AN OCCUPANT LOAD OF 11 ON THE 2ND FLOOR PLEASE
 PROVIDE AN ACCESSIBLE MEANS OF EGRESS TO THE 2ND FLOOR.
 2014 FBC-ACCESSIBILITY CODE 201.1.1 VERTICAL
 ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 3B) 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION). SEE AREA OF RESCUE
 ASSISTANCE AND REQUIREMENTS.
  
 3C) ON THE 2ND FLOOR LEVEL THE NEW STAIR SHOWS AN AREA
 OF RESCUE ASSISTANCE BEHIND THE DOOR. HOW IS THE PERSON
 IN THE WHEELCHAIR TO GAIN ENTRY TO THE AREA OF RESCUE
 ASSISTANCE? ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.3.
  
 3D) THE WINDOWS AND DOORS THAT ARE IN THE OCCUPANCY
 SEPARATION WALL, WHERE TABLE 508.4 REQUIRES A 1 HOUR
 FIRE SEPARATION, PLEASE PROVIDE HOW COMPLIANCE WITH
 OPENING PROTECTIVE IN TABLE 716.5 OTHER FIRE BARRIERS ?
 HR. FIRE RATING.
  
 3E) THE 1 HR. OCCUPANCY SEPARATION WALL (FIRE BARRIER)
 WILL NEED TO SHOW THE ONE HOUR FIRE RATING PER TABLE
 504.8. PLEASE ALSO SHOW COMPLIANCE WITH :
 FBC-B 707.5 CONTINUITY.
 FIRE BARRIERS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE AND SHALL BE SECURELY ATTACHED THERETO. SUCH FIRE
 BARRIERS SHALL BE CONTINUOUS THROUGH CONCEALED SPACE,
 SUCH AS THE SPACE ABOVE A SUSPENDED CEILING. JOINTS AND
 VOIDS AT INTERSECTIONS SHALL COMPLY WITH SECTIONS 707.8
 AND 707.9
  
 FBC-B 707.5.1 SUPPORTING CONSTRUCTION.
 THE SUPPORTING CONSTRUCTION FOR A FIRE BARRIER SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE FIRE BARRIER SUPPORTED. HOLLOW VERTICAL SPACES
 WITHIN A FIRE BARRIER SHALL BE FIREBLOCKED IN
 ACCORDANCE WITH SECTION 718.2 AT EVERY FLOOR LEVEL.
  
 4) SHEET A6.0 SHOWS MICROWAVES AT A ELEVATION EQUAL TO
 THE UPPER CABINETS. PLEASE SHOW COMPLIANCE WITH THE
 2014 FBC-ACCESSIBILITY CODE: OPERABLE PARTS SHALL
 COMPLY WITH 309.
  
 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED.
  
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By rlecky Date 2016-03-07 Time 12:49 Rev Time 0.00
Received By rlecky Date 2016-03-07 Time 12:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-08 Cont ID  
Sent By rlecky Date 2016-02-08 Time 12:17 Rev Time 0.00
Received By rlecky Date 2016-02-08 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By scaldero Date 2016-03-14 Time 11:50 Rev Time 0.00
Received By scaldero Date 2016-03-14 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-01-26 Cont ID  
Sent By scaldero Date 2016-01-26 Time 12:22 Rev Time 0.00
Received By scaldero Date 2016-01-26 Time 12:13 Sent To  
Notes
2016-01-26 12:22:52PERMIT # 16010403
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 4) ADDRESS ALL BUILDING PLAN REVIEWER COMMENTS.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-12 Cont ID  
Sent By jwitmer Date 2016-05-12 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2016-04-13 Time 12:45 Sent To  
Notes
2016-04-14 12:45:43C17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 06:23 Rev Time 0.00
Received By jwitmer Date 2016-03-04 Time 10:03 Sent To  
Notes
2016-03-04 10:04:22C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-08 Cont ID  
Sent By rlecky Date 2016-02-08 Time 12:17 Rev Time 0.00
Received By rlecky Date 2016-01-14 Time 13:32 Sent To  
Notes
2016-01-19 13:32:59C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-01-26 Cont ID  
Sent By jwitmer Date 2016-01-26 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2016-01-26 Time 05:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-04-18 Cont ID  
Sent By ccole Date 2016-04-18 Time 15:33 Rev Time 0.00
Received By ccole Date 2016-04-18 Time 15:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-11 Cont ID  
Sent By ccole Date 2016-03-11 Time 08:35 Rev Time 0.00
Received By ccole Date 2016-03-11 Time 08:35 Sent To  
Notes
2016-03-11 08:57:132ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010403
 3/11/16
  
 1) 2ND REQUEST FOR AC CALCULATIONS FOR THE AHU/CU-1
 SYSTEM- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 2) CLARIFY HOW SUPPLY AIR TO THE AREAS OF STATIONS B,
 C, D, E, & F IS BEING RETURNED TO THE AIR HANDLER. IT
 APPEARS BY THE ARCHITECTURAL DETAILS THAT THE WALLS
 ENCLOSING THE OFFICE WALLS RUN TO THE CEILINGS AND
 THERE IS A SOLID WOOD DOOR AT THE MECHANICAL ROOM
 ENTRANCE. IS THE AA/775 RETURN GRILL IN THE OFFICE TO
 BE USED BECAUSE IT APPEARS TO BE NOT ACCESSIBLE FOR THE
 AIR TO RETURN THROUGH? PLEASE NOTE THAT IF THE MECH
 CLOSET IS A PLENUM CHAMBER THE WOOD DOOR SHOWN ON THE
 SCHEDULE MUST BE CHANGED TO A NON-COMBUSTIBLE TYPE-
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. PLEASE
 SEE SECTION 601.2 FBC-14 MECHANCIAL: CORRIDORS SHALL
 NOT SERVE AS RETURN DUCTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-21 Cont ID  
Sent By ccole Date 2016-01-21 Time 14:31 Rev Time 0.00
Received By ccole Date 2016-01-21 Time 14:31 Sent To  
Notes
2016-01-21 14:39:021ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010403
 1/21/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MEZZANINE AND LUNCHROOM SYSTEM- REFERENCE SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION, CALCULATION OF
 HEATING AND COOLING LOADS.
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 RENOVATED AREAS IN ACCORDANCE WITH SECTION 809.1 FBC-14
 EXISTING BUILDING CODE, AND TABLE 403.3 FBC-14
 MECHANICAL.
 3) SUBMIT THE NOA FOR THE CONDENSER STAND WITH A REVIEW
 AND APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD.
 4) ADVISORY: A NON-COMBUSTIBLE DOOR IS REQUIRED FOR
 MECHANICAL CLOSETS THAT FORM THE PRIMARY AIR
 CONTAINMENT FOR AIR DISTRIBUTION SYSTEMS- SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-05-11 Cont ID  
Sent By gjohnson Date 2016-05-11 Time 10:01 Rev Time 0.00
Received By gjohnson Date 2016-05-11 Time 10:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-04-27 Cont ID  
Sent By gjohnson Date 2016-04-27 Time 11:08 Rev Time 0.00
Received By gjohnson Date 2016-04-27 Time 11:08 Sent To  
Notes
2016-04-27 11:08:083ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. IT APPEARS THAT THERE IS STILL A SHOWER BEING
 INSTALLED IN MENS BATHROOM . TO DELETE THE SHOWER FROM
 THE SCOPE OF WORK YOU SHALL REMOVE THE FOLLOWING .PER
 WPB AMEND. TO FBC SEC. 107.2.1
  
 (A) SHT.P0.1 ON THE PLUMBING FIXTURE SCHEDULE THE NOTE
 FOR SHOWER MIXING VALVE.
  
 (B) SHT. P2.1 THE 3IN. FLOOR DRAIN NOTE 2 ,THE DRAWING
 OF THE SHOWER VALVE AND THE ABBREVIATION SH , FD .
  
 (C) SHT. P3.1 WATER LINES FOR SHOWER VALVE NOTE 1.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-14 Cont ID  
Sent By tklarge Date 2016-03-14 Time 08:34 Rev Time 0.00
Received By tklarge Date 2016-03-14 Time 06:24 Sent To  
Notes
2016-03-14 06:58:551) SHT.A3.0 - MEN'S RESTROOM NOTES "EXISTING TO REMAIN,
 NO WORK REQD." BUT THE PLUMBING PLANS SHOW A NEW SHOWER
 IN THE MEN'S RESTROOM. CLARIFY.
 2) SHOW THE SHOWER AND THE SHOWER DIMENSIONS ON THE
 ARCHITECTURAL PLANS. THE SHOWER SHALL COMPLY WITH THE
 FL. ACCESSIBILITY CODE SEC.213.2,608.2.2, 608.2.3.
 3) SUBMIT A SANITARY AND WATER RISER FOR THE SHOWER.
 FBC 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-23 Cont ID  
Sent By tklarge Date 2016-01-23 Time 10:23 Rev Time 0.00
Received By tklarge Date 2016-01-23 Time 10:11 Sent To  
Notes
***NONE***