Plan Review Details - Permit 16010391
Plan Review Stops For Permit 16010391
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-10 Cont ID  
Sent By mvaldes Date 2016-02-10 Time 10:17 Rev Time 0.00
Received By mvaldes Date 2016-02-10 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-03 Cont ID  
Sent By mvaldes Date 2016-02-03 Time 14:32 Rev Time 0.00
Received By mvaldes Date 2016-02-03 Time 14:32 Sent To  
Notes
2016-02-03 14:50:14JOB PERMIT NUMBER: 16010391
 JOB ADDRESS: 1819 OKEECHOBEE ROAD
 WEST PALM BEACH
 DATE: FEB 3 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1 ? NFPA 72 10.5.5.3 MECHANICAL PROTECTION. THE
 DEDICATED BRANCH CIRCUIT(
 S) AND CONNECTIONS SHALL BE PROTECTED AGAINST PHYSICAL
 DAMAGE. ( BREAKER LOCK ON 20 AMP CIRCUIT FEEDING FIRE
 CONTROL PANEL.) MUST BE RED !
 2- NFPA 72 10.5.8.2 THE LOCATION OF ANY REMOTELY
 LOCATED POWER SUPPLY
 SHALL BE IDENTIFIED AT THE MASTER CONTROL UNIT.
 3- LOCATION OF EXISTING FIRE ALARM CONTROL IS NOT SHOWN
 ON PLANS SO VOLTAGE DROP COULD BE A ISSUE ?
 FURTHERMORE CEILING HEIGHT ISN'T SPECIFIED SO HOW ARE
 CEILING STROBE / HORNS TO BE MOUNTED ? ( OPEN WAREHOUSE
 )
 THIS INFORMATION IS NEEDED FOR FURTHER REVIEW FBC
 SECTION 907 FIRE PROTECTION SYSTEM ( SHOP DRAWINGS )
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 1ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700 EXT 6713
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By Stallwor Date 2016-01-22 Time   Rev Time 0.00
Received By fstal Date 2016-01-22 Time 10:00 Sent To E
Notes
2016-01-22 09:47:25NFPA 1-18.2.2.1: PROVIDE KNOX BOX.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-03 Cont ID  
Sent By cpuell Date 2016-02-03 Time 16:18 Rev Time 0.00
Received By cpuell Date 2016-01-14 Time 11:23 Sent To  
Notes
2016-01-19 11:23:37ROUTED TO FIRE