Plan Review Details - Permit 16010343
Plan Review Stops For Permit 16010343
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-10 Cont ID  
Sent By skennedy Date 2016-02-10 Time 13:04 Rev Time 0.00
Received By skennedy Date 2016-02-10 Time 13:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By cthroop Date 2016-01-19 Time 09:45 Rev Time 0.00
Received By cthroop Date 2016-01-19 Time 09:45 Sent To  
Notes
2016-01-19 09:55:59CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 DUE TO THE STRUCTURAL NATURE OF THE PROPOSED WORK,
 PROVIDE FLOOR PLAN WITH DETAIL OF EACH AREA OF WORK.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 DUE TO THE RE-CONFIGURATION OF THE FLOOR PLAN IN AREAS
 THAT CLOSETS ARE TO BE REMOVED, AN ADDITIONAL
 ELECTRICAL PERMIT WILL BE REQUIRED.
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
 R314.1 SMOKE DETECTION AND NOTIFICATION.
 ALL SMOKE ALARMS SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH UL 217 AND INSTALLED IN ACCORDANCE WITH
 THE PROVISIONS OF THIS CODE AND THE HOUSEHOLD FIRE
 WARNING EQUIPMENT PROVISIONS OF NFPA 72.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2016-02-10 Cont ID  
Sent By skennedy Date 2016-02-10 Time 13:04 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By skennedy Date 2016-01-19 Time 09:29 Rev Time 0.00
Received By skennedy Date 2016-01-19 Time 09:29 Sent To  
Notes
2016-01-19 10:02:081ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE FLOOR PLAN ALTERATIONS PROPOSED WILL RESULT IN A
 NEED FOR ALTERATION TO THE ELECTRICAL OUTLET SPACINING
 ALONG THE WALLS.
  
 PROVIDE A PLAN PER FBC 107 TO SHOW THE FOLLOWING:
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 NEW DEVICES SHALL MEET THE THE TWO CRITERIA BELOW:
  
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES
  
 THE FOLLOWING CRITERIA SHALL BE DEMONSTRATED AS
 EXISTING OR NEW:
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-19 Cont ID  
Sent By cthroop Date 2016-01-19 Time 09:45 Rev Time 0.00
Received By cthroop Date 2016-01-13 Time 13:45 Sent To  
Notes
2016-01-13 13:46:03BLDG <5K