| 2016-02-01 13:48:33 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010290 |
| | ADD: 805 N. RAILROAD AVE. |
| | CONT: PALM BEACH CAST STONE |
| | TEL: 561-835-4085 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 01/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE SITE PLAN SHOWS THE PROPERTY LINE ALL THE WAY TO |
| | THE STREET, IT APPEARS THE CITY SIDEWALK IS ON PRIVATE |
| | PROPERTY AND NOT IN THE RIGHT OF WAY. PLEASE PROVIDE A |
| | SURVEY THAT IDENTIFIES THE ACTUAL CORNERS OF THE |
| | PROPERTY. |
| | |
| | 2) SHEET A2.1 ON THE FRONT ENTRY, IT APPEARS THE NEW |
| | DOORS ARE SWINGING OUT OVER THE PROPERTY LINE. PLEASE |
| | SHOW COMPLIANCE WITH 2014 FBC-B 3202.2.2 DOORS AND |
| | WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC |
| | RIGHT-OF-WAY. |
| | |
| | 3) THE STRUCTURAL SHEET 5.1 SHOWS NEW STEEL COLUMNS |
| | BEING WELDED TO AN EXISITNG W20X BEAM AS WELL AS NEW |
| | STEEL COLUMNS BEING WELDED ON THE 2ND FLOOR TO THE |
| | EXISITNG W20X BEAM. NORMALLY THIS WOULD REQUIRE A |
| | RESIDENT INSPECTOR FOR BOLTED AND WELDED CONNECTIONS. |
| | 110.3.9 OTHER INSPECTIONS SERVICES7. FOR BUILDINGS AND |
| | STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION, BOLTED AND WELDED CONNECTIONS. PLEASE |
| | CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD TO SEE |
| | IF HE WILL REQUIRE THE RESIDENT INSPECTOR OR IF A |
| | WELDING CERTIFICATE FROM THE ONSITE WELDER WILL SUFFICE |
| | AND THE USE OF CITY BUILDING INSPECTORS. |
| | KEN CONRAD TEL: 561-805-6666. |
| | |
| | 4) PLEASE NOTE SHEETS A2.1 AND A2.2 THE 1ST FLOOR PLAN |
| | AND 2ND FLOOR PLAN DO HAVE WALL IDENTIFICATION TAGS AND |
| | THE LEGEND ON BOTH SHEETS INDICATES WALL TYPE IN THE |
| | LEGEND IS ON SHEET A7.1. THE PLANS SUBMITTED ONLY HAS |
| | PAGES UP TO A6.1 AS DOES THE INDEX. WALL FIRE RATINGS |
| | CAN NOT BE IDENTIFIED AT THIS TIME. |
| | |
| | 5A) SHEET A2.1 SHOWS (2) ROOMS LOCATED BENEATH THE |
| | STAIRS, THE RESTROOM 102 AND THE MECHANICAL ROOM 103. |
| | NOT HAVING A WALL LEGEND THAT IDENTIFIES THE TYPE OF |
| | WALLS PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B; |
| | 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. |
| | THE WALLS CEILINGS AND SOFFITS WITHIN ENCLOSED USABLE |
| | SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| | SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR |
| | ENCLOSURE. |
| | |
| | 5B) THE BATHROOM AND MECHANICAL ROOM BENEATH THE |
| | ENCLOSED STAIR ENCLOSURE HAVING TO HAVE 1 HOUR FIRE |
| | RATING THE DOORS WILL ALSO NEED TO HAVE A FIRE RATING |
| | OPENING PROTECTIVES PER 2014 FBC-B TABLE 716.5. |
| | |
| | 6) PLEASE BE AWARE OF AN ERROR IN FBC-B TABLE 508.4 FOR |
| | FIRE RATINGS BETWEEN S1 AND S2 OCCUPANCIES. PLEASE |
| | REVIEW THE BUILDING OFFICIALS ASSOCIATION INFORMAL |
| | INTERPRETATION: |
| | DATE: TUE JUL 1 2014 |
| | REPORT: 7357 |
| | CODE: BUILDING CODE YEAR: 2010 |
| | SECTION: TABLE 508.4 |
| | QUESTION: |
| | IS IT THE INTENT OF TABLE 508.4 TO REQUIRE A (1HR (S), |
| | 2HR (NS)) SEPARATION BETWEEN B AND S-2 OCCUPANCY AND NO |
| | SEPARATION REQUIREMENT BETWEEN B AND S-1 OCCUPANCY? |
| | COMMENT: |
| | PER CHAPTER 3, S-2 OCCUPANCY ARE DEFINED AS LOW- HAZARD |
| | STORAGE, WHERE AS S-1 OCCUPANCY IS DEFINED AS |
| | MODERATE-HAZARD OCCUPANCY. THE STORED MATERIALS LIST |
| | FOR S-1 OCCUPANCY IS MUCH MORE HAZARDOUS THAN THE LIST |
| | FOR S-2 OCCUPANCY AND ONE WOULD THINK THAT THE S-1 |
| | OCCUPANCY WOULD REQUIRE THE SEPARATION AND THE S-2 |
| | OCCUPANCY WOULD NOT. |
| | ANSWER: |
| | BASED ON THE INFORMATION REVIEWED, IT APPEARS YOU ARE |
| | CORRECT THAT A TYPO EXISTS. THE BEST APPROACH FOR THIS |
| | PARTICULAR ISSUE WOULD BE EITHER A FORMAL |
| | INTERPRETATION WHICH HAS STANDING OR A DEC STATEMENT |
| | FROM THE FLORIDA BUILDING COMMISSION. PLEASE SEE THE |
| | COMMENTARY BELOW. |
| | COMMENTARY: |
| | TABLE 508.4 DOES APPEAR TO HAVE A TYPO. THE 2001 |
| | FLORIDA BUILDING CODE, TABLE 704.1 REQUIRED A 3 HOUR |
| | SEPARATION FOR S1 AND A 2 HOUR SEPARATION FOR S2. IN |
| | THE 2004 CODE TABLE 706.3.7 ALSO REQUIRES 3 HOURS FOR |
| | S1 AND 2 HOURS FOR S2. THE TYPO APPEARS TO HAVE BEEN |
| | INTRODUCED WITH TABLE 508.4 IN THE 2007 CODE. TABLE |
| | 508.4 APPEARS TO HAVE BEEN WRONG SINCE ITS INCEPTION. |
| | SUBMITTING A REQUEST FOR A FORMAL INTERPRETATION WOULD |
| | PERMIT APPLICATION OF CORRECTION TO THIS ISSUE UNTIL A |
| | CODE CHANGE CAN BE MADE, IF IT IS NOT ALREADY IN THE |
| | WORKS. |
| | NOTICE: |
| | THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN |
| | COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC, |
| | AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS |
| | INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE |
| | INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE. |
| | THIS INTERPRETATION IS INFORMAL, NON-BINDING AND |
| | SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL |
| | BUILDING OFFICIAL. |
| | |
| | 7A) SHEET A2.2 SHOWS ON THE 2ND FLOOR A WAREHOUSE, |
| | PLEASE PROVIDE THE DESIGN LIVE LOADS PER 2014 FBC-B |
| | TABLE 1607.1(31) STORAGE WAREHOUSES. |
| | |
| | 7B) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 106.1 LIVE LOADS POSTED. WHERE THE LIVE |
| | LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A |
| | COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN |
| | DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH DESIGN |
| | LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE OWNER |
| | IN THAT PART OF EACH STORY IN WHICH THEY APPLY, USING |
| | DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR DEFACE |
| | SUCH NOTICES. |
| | |
| | 7C) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 106.2 ISSUANCE OF CERTIFICATE OF |
| | OCCUPANCY. A CERTIFICATE OF OCCUPANCY REQUIRED BY |
| | SECTION 111 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD |
| | SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 8A) THE PLANS INDICATE NEW EXTERIOR OPENINGS OF THE |
| | SHELL OF THE BUILDING. PLEASE PROVIDE COMPLIANCE WITH: |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | |
| | 8B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 9) SHEET A3.3 : |
| | 9A) SHOWS A NEW ROOF TOP A/C STAND, PLEASE PROVIDE THE |
| | WIND DESIGN CRITERIA AND PRESSURES FOR THE REQUIRED |
| | ANCHORING OF THE A/C CONDENSOR STAND TO THE ROOF. |
| | PLEASE INDICATE HOW THE STAND WILL BE ANCHORED TO THE |
| | ROOF FRAMING MEMBERS. TIE INTO THE MAIN WINF FORCE |
| | RESISTING SYSTEM. |
| | |
| | 9B) PLEASE PROVIDE DOCUMENTATION THERE IS A PARAPET OF |
| | SUFFICIENT HEIGHT OR CODE COMPLIANCE WITH FBC-B 1013.6 |
| | MECHANICAL EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 9C) THE PLANS SHOW AN EXISITNG ROOF TOP HATCH BUT THERE |
| | IS NO MENTION OF COMPLIANCE WITH: ? 1509.6.4 EQUIPMENT |
| | AND APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| | ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| | ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| | 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| | CRITERIA: |
| | 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| | ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| | 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| | INCHES (356 MM) ON CENTER. |
| | 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN |
| | 6-INCHES (152 MM) DEEP. |
| | 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| | BETWEEN RAILS. |
| | 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| | DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| | (136.1 KG) LOAD. |
| | 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| | PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| | WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2). |
| | 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| | APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| | REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610 |
| | MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR |
| | SERVICE PLATFORMS. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |