Plan Review Details - Permit 16010287
Plan Review Stops For Permit 16010287
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-16 Cont ID  
Sent By aclange Date 2016-02-16 Time 16:18 Rev Time 0.00
Received By aclange Date 2016-02-16 Time 16:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-08 Cont ID  
Sent By aclange Date 2016-02-08 Time 16:11 Rev Time 0.00
Received By aclange Date 2016-02-08 Time 16:11 Sent To  
Notes
2016-02-08 16:12:13****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 NO NEW INFORMATION SUBMITTED FOR REVIEW:
  
 1. PLEASE PROVIDE TIE DOWN ENGINEERING COMPLYING WITH
 FBC 1603.1.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-21 Cont ID  
Sent By aclange Date 2016-01-21 Time 16:58 Rev Time 0.00
Received By aclange Date 2016-01-21 Time 16:58 Sent To E
Notes
2016-01-21 17:01:43****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 1. PLEASE PROVIDE TIE DOWN ENGINEERING COMPLYING WITH
 FBC 1603.1.4.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-05 Cont ID  
Sent By vperez Date 2016-02-05 Time 10:02 Rev Time 0.00
Received By vperez Date 2016-02-05 Time 10:01 Sent To  
Notes
2016-02-05 10:03:34SENT TO CAROLYN/LAURA DESK

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-28 Cont ID  
Sent By albarran Date 2016-01-28 Time 14:35 Rev Time 0.00
Received By albarran Date 2016-01-28 Time 14:08 Sent To I
Notes
2016-01-28 14:39:301ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. ACCORDING TO THE MANUFACTURER?S SPECS THIS UNIT HAS
 A 125 AMP PANEL, (ASSUMED TO BE 120/240 VAC 1?
 SERVICE), THE REQUIRED EXTERNAL LIGHT AND GFCI
 PROTECTED OUTLET.
 2. YOU NEED TO SUBMIT AN ELECTRICAL RISER DIAGRAM AS
 REQUIRED BY NEC 215.5. THIS DIAGRAM MUST INCLUDE
 CONDUCTOR SIZING AND TYPE. THE CONDUCTORS MUST BE SIZED
 TO SO AS NOT TO PERMIT GREATER THAN 3% VOLTAGE DROP.
 3. YOU NEED TO MARK ON THE SITE PLAN THE LOCATION OF
 THE POWER SOURCE FOR THE UNIT.
 4. IF A SERVICE RACK IS GOING TO BE ERECTED, PROTECTION
 FROM PHYSICAL DAMAGE MUST BE PROVIDED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-16 Cont ID  
Sent By aclange Date 2016-02-16 Time 16:18 Rev Time 0.00
Received By aclange Date 2016-02-11 Time 10:25 Sent To  
Notes
2016-02-11 10:25:57RESUB ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-08 Cont ID  
Sent By aclange Date 2016-02-08 Time 16:12 Rev Time 0.00
Received By aclange Date 2016-02-02 Time 12:54 Sent To  
Notes
2016-02-02 12:54:43RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-28 Cont ID  
Sent By albarran Date 2016-01-28 Time 14:39 Rev Time 0.00
Received By albarran Date 2016-01-12 Time 14:35 Sent To  
Notes
2016-01-28 14:48:351/28/16 FAILED TRADE REVIEWS. CONTRACTOR NOTIFIED VIA
 EMAIL TO [email protected]. SENT FILE TO SMALL
 DENIED BIN "L".MA
2016-01-12 14:35:40ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-20 Cont ID  
Sent By jroach Date 2016-01-20 Time 14:29 Rev Time 0.00
Received By jroach Date 2016-01-20 Time 14:29 Sent To B
Notes
2016-01-20 14:30:27PROVISO
  
 ALL CONSTRUCTION TRAILERS SHALL BE REMOVED WITHIN SEVEN
 DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE CITY
 AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 QUESTIONS/COMMENTS, CONTACT
 JOHN ROACH, PRINCIPAL PLANNER, AT
 [email protected] OR (561) 822-1448.
  