Plan Review Details - Permit 16010210
Plan Review Stops For Permit 16010210
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-04 Cont ID  
Sent By jwitmer Date 2016-03-04 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2016-03-04 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-15 Cont ID  
Sent By jwitmer Date 2016-01-15 Time 10:26 Rev Time 0.00
Received By jwitmer Date 2016-01-15 Time 09:28 Sent To  
Notes
2016-01-15 10:26:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010210
 ADD: 1811 N. DIXIE HWY.
 CONT: RISH CONSTRUCTION.
 TEL: 305-962-1901
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 15/ 2016
 ACTION: DENIED
  
 1) WORK AREA # 5 IS TO RETROFIT A EXISTING 12 X 16 INCH
 COLUMN. THE PLANS DO NOT STATE HOW BADLY THE COLUMN IS
 DAMAGED? IS THERE SUFFICIENT DAMAGE TO THE COLUMN WHEN
 THE REPAIR IS BEING MADE THAT THE BEAMS ABOVE WILL NEED
 TO BE SHORED? IF SO WHAT TYPE OF SHORING IS TO BE
 INCORPORATED INTO THE COLUMN REPAIR, AND HOW LONG WILL
 THE SHORING NEED TO BE IN PLACE AFTER THE REPAIR IS
 COMPLETED ? 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 CLOSING
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-04 Cont ID  
Sent By vperez Date 2016-03-04 Time 06:01 Rev Time 0.00
Received By vperez Date 2016-03-04 Time 06:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 14:56 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 14:35 Sent To  
Notes
2016-02-10 14:56:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADD A NOTE TO DRAWINGS INDICATING THAT NO NEW
 LOADS ARE BEING ADDED UNDER THE SCOPE OF WORK. A NOTE
 WILL SUFFICE. FBC 107 MINIMUM PLAN REVIEW CRITERIA
 2. DELETE FROM GENERAL NOTES NON-APPLICABLE ITEMS SUCH
 AS THOSE THAT APPLY TO DWELLINGS OCCUPANCIES. FBC 107
 MINIMUM PLAN REVIEW CRITERIA
 3. SHOW ON PLANS THE EXISTING PANEL BOARD WHERE THE
 EXISTING CIRCUITS ORIGINATE, TO THE RESTROOMS AREAS. NO
 LOAD CALCULATIONS ARE REQUIRED DUE TO NO LOADS BEING
 ALTERED. FBC 107 MINIMUM PLAN REVIEW CRITERIA
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-03 Time   Rev Time 0.00
Received By pleduc Date 2016-03-03 Time 12:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-15 Cont ID  
Sent By pleduc Date 2016-01-15 Time   Rev Time 0.00
Received By pleduc Date 2016-01-15 Time 14:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-22 Cont ID  
Sent By ccole Date 2016-03-22 Time 16:39 Rev Time 0.00
Received By ccole Date 2016-03-22 Time 09:01 Sent To  
Notes
2016-03-22 09:01:13RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-15 Cont ID  
Sent By lmarchan Date 2016-03-15 Time 07:44 Rev Time 0.00
Received By lmarchan Date 2016-03-01 Time 13:04 Sent To  
Notes
2016-03-04 06:10:243/4 TO BIN B27
2016-03-01 13:04:45B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 14:57 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 14:57 Sent To  
Notes
2016-02-10 14:57:35TO CAROLINE/LAURA
2016-01-11 11:16:24B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-01-15 Cont ID  
Sent By jwitmer Date 2016-01-15 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2016-01-15 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-03-22 Cont ID  
Sent By ccole Date 2016-03-22 Time 16:39 Rev Time 0.00
Received By ccole Date 2016-03-22 Time 16:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 16:01 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 16:01 Sent To  
Notes
2016-03-10 16:11:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010210
 3/10/16
  
 1) PLEASE REFER TO TABLE 403.3 FBC-14 MECHANICAL, AND
 SEE TOILET ROOMS- PUBLIC AND FOOTNOTE E: 50 CFM EXHAUST
 AIRFLOW RATE REQUIRED FOR EACH TOILET OR URINAL. THE
 EXHAUST FAN SCHEDULE ON SHEET M-1 INDICATES THE CFM
 CAPACITIES OF THE FANS ARE INADEQUATE: A) WORK AREA 1
 REQUIRES MINIMUM 300 CFM'S OF EXHAUST. B) WORK AREA 2
 REQUIRES 400 CFM'S OF EXHAUST. C) WORK AREA 3 REQUIRES
 100 CFM'S OF EXHAUST.
 2) M-1: PLEASE CLARIFY WHY OUTDOOR AIR CALCULATIONS ARE
 SHOWN FOR LAUNDRY AREAS: THERE ARE NO LAUNDRIES SHOWN
 ON THE PLAN. IF LAUNDRY IS TO BE INCLUDED UNDER THIS
 PERMIT, PROVIDE COMPLETE PLANS AND SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-14 Cont ID  
Sent By ccole Date 2016-01-14 Time 14:11 Rev Time 0.00
Received By ccole Date 2016-01-14 Time 14:11 Sent To  
Notes
2016-01-14 14:18:041ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16010210
  
 1) PROVIDE EQUIPMENT SCHEDULES ON THE PLAN FOR THE
 TOILET ROOM EXHAUST FANS- LIST THE MAKES, MODELS, AND
 CFM CAPACITIES. REFER TO TABLE 403.3 FBC-14 MECHANICAL
 FOR REQUIRED EXHAUST CFM'S. PLEASE NOTE THE 4" EXHAUST
 DUCT MAY BE UNDERSIZED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-12 Cont ID  
Sent By tklarge Date 2016-03-12 Time 06:06 Rev Time 0.00
Received By tklarge Date 2016-03-12 Time 05:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By tklarge Date 2016-01-19 Time 05:32 Rev Time 0.00
Received By tklarge Date 2016-01-19 Time 04:26 Sent To  
Notes
2016-01-19 05:32:041) INDICATE THE LEVEL OF ALTERATION ON THE PLANS PER
 THE 2014 FBC-EXISTING, SEC. 301.1.
 2) INDICATE THE OCCUPANCY TYPE ON THE PLANS PER THE
 2014 FBC SEC. 301, 302.
 3) SHT. A-1 - PROPOSED WORK AREA #1 IS CALLED OUT AS A
 MEN'S RESTROOM BUT A-3 NOTES THIS AS A WOMEN'S RESTROOM
 ON THE PLAN VIEW.THE SAME DISCREPANCY OCCURS FOR WORK
 AREA #2. CLARIFY.
 4) SUBMIT THE OCCUPANT LOAD OF THIS BUILDING TO ENSURE
 THERE WILL NOT BE ANY PLUMBING CODE VIOLATIONS DUE TO
 THE CHANGES IN THE TYPES AND AMOUNT OF PLUMBING
 FIXTURES.WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. A-2 - WORK AREA 3 - MEN'S RESTROOM - CLARIFY
 THE SCOPE OF WORK BEING DONE IN THIS RESTROOM. THE
 PLANS STATE "ENLARGE MEN'S RESTROOM BUT THE LAYOUT
 APPEARS UNCHANGED.
 6) SHT. P-1 - FIXTURE SCHEDULE NOTE #1 - THE WORK SHALL
 COMPLY WITH THE 2014 FBC, NOT THE 2010. 2014
 FBC-EXISTING SEC.801.3.
 7) SHT. P-1 - FIXTURE SCHEDULE NOTE #2 - THE MAXIMUM
 TEMPERATURE AT THE FIXTURE OUTLET SHALL BE 110 DEGREES.
 FBC-PLUMBING SEC.607.1.2.
 8) SHT. P-1 - WORK AREAS #1, 2, 3, 4 - THE PLANS SHOW
 EXISTING 3/4" CW & 1/2" CW. THIS IS OBVIOUSLY AN ERROR.
 PLEASE CORRECT.
 9) A SANITARY AND WATER RISER IS REQUIRED FOR ALL THE
 CHANGES BEING MADE TO THE SANITARY AND WATER SYSTEMS.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  