Plan Review Details - Permit 16010176
Plan Review Stops For Permit 16010176
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-27 Cont ID  
Sent By jwitmer Date 2016-02-27 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2016-02-27 Time 08:31 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-02-25 Cont ID  
Sent By jwitmer Date 2016-02-25 Time 07:13 Rev Time 0.00
Received By jwitmer Date 2016-02-25 Time 06:45 Sent To  
Notes
2016-02-25 07:18:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010176
 ADD: 330 CLEMATIS ST. SUITE # 102
 CONT: C. S. STOPEHENGE CONTRACTOR
 TEL: 305-989-1987
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. FEB. 25/ 2016
 ACTION: DENIED
  
 1) 3D REQUEST. THE VALUE IS LOW, THE SUB-CONTRACTORS
 WORK IS TO BE INCLUDED IN THE VALUE OF THE PROJECT. THE
 1ST PERMIT APPLICATION CAME IN AT A VALUE OF $15,000.00
 THE 2ND APPLICATION AT #2,500.00.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 108.3* BUILDING PERMIT VALUATION. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) COMPLIED.
  
 3) 3RD REQUEST. 2014 EXISTING BUILDING CODE LEVEL II
 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 SHEET A-2 THE NEW WALL AND DOOR (DOOR # 3) THAT IS
 ADDED JUST OUTSIDE OF THE RESTROOM CREATES A CODE
 VIOLATION TO THE 2014 FBC-ACCESSIBIITY CODE SECTION
 404.2. MANEUVERING CLEARANCES, FIGURE 404.2.1(A).
 PLEASE REVIEW FIGURE 404.2.1(A) THE DOOR SWINGS INTO
 THE WORK ROOM, THE 18 INCHES IS TO BE TAKEN ON THE PULL
 SIDE OF THE DOOR THE LATCH SIDE.
  
 4) COMPLIED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-09 Cont ID  
Sent By jwitmer Date 2016-02-09 Time   Rev Time 0.00
Received By jwitmer Date 2016-02-09 Time   Sent To  
Notes
2016-02-09 14:53:02BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010176
 ADD: 330 CLEMATIS ST. SUITE # 102
 CONT: C. S. STOPEHENGE CONTRACTOR
 TEL: 305-989-1987
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 09/ 2016
 ACTION: DENIED
  
 1)2ND REQUEST. THE VALUE IS LOW, THE SUB-CONTRACTORS
 WORK IS TO BE INCLUDED IN THE VALUE OF THE PROJECT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 108.3* BUILDING PERMIT VALUATION. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) COMPLIED.
  
 3) 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SHEET A-2 THE NEW WALL AND DOOR (DOOR # 3) THAT IS
 ADDED JUST OUTSIDE OF THE RESTROOM CREATES A CODE
 VIOLATION TO THE 2014 FBC-ACCESSIBIITY CODE SECTION
 404.2. MANEUVERING CLEARANCES, FIGURE 404.2.1(A).
  
 4) COMPLIED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-14 Cont ID  
Sent By jwitmer Date 2016-01-14 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2016-01-14 Time 07:15 Sent To  
Notes
2016-01-14 08:08:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010176
 ADD: 330 CLEMATIS ST. SUITE # 102
 CONT: C. S. STOPEHENGE CONTRACTOR
 TEL: 305-989-1987
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 14/ 2016
 ACTION: DENIED
  
 1) THE VALUE IS LOW, THE SUB-CONTRACTORS WORK IS TO BE
 INCLUDED IN THE VALUE OF THE PROJECT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 108.3* BUILDING PERMIT VALUATION. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SHEET A-2 THE NEW WALL THAT IS ADDED JUST OUTSIDE OF
 THE RESTROOM CREATES A CODE VIOLATION TO THE 2014
 FBC-ACCESSIBIITY CODE SECTION 404.2. MANEUVERING
 CLEARANCES, FIGURE 404.2.1(A).
  
 3) SHEET A-2 THE DOOR LABELED # 2 IS SHOWN AS A 2-8
 WIDE DOOR. PLEASE REVIEW THE 2014 FBC-B 1008.1.1 SIZE
 OF DOOR, THIS DOOR NEEDS TO BE A 3-0 DOOR NOT A 2-8.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 4) SHEET A-2 THE CASHIERS COUNTER DOES NOT SHOW
 COMPLIANCE WITH THE: 2014 FBC-ACCESSIBLITY CODE 904.4
 SALES AND SERVICE COUNTERS. SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE
 ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND THE
 SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-29 Cont ID  
Sent By mvaldes Date 2016-02-29 Time 15:36 Rev Time 0.00
Received By mvaldes Date 2016-02-29 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-17 Cont ID  
Sent By mvaldes Date 2016-02-17 Time 15:27 Rev Time 0.00
Received By mvaldes Date 2016-02-17 Time 15:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-21 Cont ID  
Sent By mvaldes Date 2016-01-21 Time 17:29 Rev Time 0.00
Received By mvaldes Date 2016-01-21 Time 17:29 Sent To  
Notes
2016-01-21 17:31:411ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 JOB PERMIT NUMBER: 16010176
 JOB ADDRESS: 330 CLEMATIS ST U-102
 WEST PALM BEACH ( GELATO)
 DATE: JAN 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1- PLEASE SITE CURRENT CODE STANDARDS NEC 2011 AND FBC
 2014
 2- PROVIDE PROPER PANEL BOARD MARKINGS IS THIS SINGLE
 OR THREE PHASE SYSTEM? NEC 408.58
 3- THE BRANCH CIRCUIT FEEDING THE EMERGENCY EQUIPMENT
 SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
 LOCAL SWITCHES. NEC 700.12 F (SHOW ON PLANS OR ADD
 NOTE.)
 4- PADDLE FAN INSTALLED OUTSIDE MUST BE PROPERLY
 SUPPORTED IN ACCORDANCE WITH NEC 314.27 C
 5- PROVIDE SHOW WINDOW OUTLET FOR EVERY 12 LINEAR FEET
 OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT ITS
 MAXIMUM WIDTH. NEC 210.62
 6- PROVIDE FIXTURE MEANS OF SUPPORT DETAIL OR NOTE ON
 TO PLANS. NEC 410.36
 7- MANDATORY INTERIOR LIGHTING CONTROLS ARE REQUIRED AS
 PER FBC-E C405 BATHROOMS MUST BE ON OCCUPANCY SENSORS
 8- MANDATORY EXTERIOR LIGHTING CONTROLS FOR SIGNS MUST
 BE ON ASTRONOMICAL TIMER OR COMBINATION OF PHOTOCELL
 AHEAD OF TIMER. FBC-E C405
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-10 Cont ID  
Sent By pleduc Date 2016-02-10 Time   Rev Time 0.00
Received By pleduc Date 2016-02-10 Time 10:17 Sent To  
Notes
2016-02-10 10:29:412ND REVIEW
  
 1ST REVIEW COMMENTS RESTATED
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THERE IS AN INCORECT REFERENCE TO THE FIRE CODE ON
 THE SUBMITTED PLANS. HOWEVER, IT DOES NPOT APPEAR TO
 NEGATIVELY IMPACT THE SUBMITTAL. A MORE DETAILED REVIEW
 MAY BE NECESSARY.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 2. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRE AN EVALUATION.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-08 Cont ID  
Sent By pleduc Date 2016-01-08 Time   Rev Time 0.00
Received By pleduc Date 2016-01-08 Time 13:12 Sent To  
Notes
2016-01-08 13:16:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THERE IS AN INCORECT REFERENCE TO THE FIRE CODE ON
 THE SUBMITTED PLANS. HOWEVER, IT DOES NPOT APPEAR TO
 NEGATIVELY IMPACT THE SUBMITTAL. A MORE DETAILED REVIEW
 MAY BE NECESSARY.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 2. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRE AN EVALUATION.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-29 Cont ID  
Sent By mvaldes Date 2016-02-29 Time 15:37 Rev Time 0.00
Received By mvaldes Date 2016-02-29 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-25 Cont ID  
Sent By   Date 2016-02-25 Time 07:15 Rev Time 0.00
Received By cpuell Date 2016-02-22 Time 08:58 Sent To  
Notes
2016-02-23 08:58:22TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-23 Cont ID  
Sent By cpuell Date 2016-02-23 Time 08:52 Rev Time 0.00
Received By cpuell Date 2016-02-03 Time 10:06 Sent To  
Notes
2016-02-04 10:06:33B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-22 Cont ID  
Sent By lmarchan Date 2016-01-22 Time 08:32 Rev Time 0.00
Received By lmarchan Date 2016-01-07 Time 14:21 Sent To  
Notes
2016-01-07 14:22:07B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-01-14 Cont ID  
Sent By jwitmer Date 2016-01-14 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2016-01-14 Time 08:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-02-11 Cont ID  
Sent By ccole Date 2016-02-11 Time 12:12 Rev Time 0.00
Received By ccole Date 2016-02-11 Time 12:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-20 Cont ID  
Sent By ccole Date 2016-01-20 Time 14:31 Rev Time 0.00
Received By ccole Date 2016-01-12 Time 07:40 Sent To  
Notes
2016-01-12 08:17:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010176
 1/12/16
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED NEW GELATO SHOP IN ACCORDANCE WITH TABLE 403.3
 FBC-14 MECHANICAL. REFER TO SECTION 809.1 RECONFIGURED
 OR CONVERTED SPACES.
 ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL
 SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN
 ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
 SHOW ON THE PLAN THE REQUIRED AMOUNT OF OUTDOOR AIR
 CFM'S PER THE TABLE, AND THE AMOUNT PROVIDED BY THE
 EXISTING HVAC SYSTEMS.
 2) PROVIDE A SCOPE OF WORK AND DETAILS FOR ALL PROPOSED
 ALTERATIONS TO THE EXISITNG HVAC SYSTEMS (IF APPLICABLE
 TO THE PROJECT).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-02-27 Cont ID  
Sent By jwitmer Date 2016-02-27 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2016-02-27 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By tklarge Date 2016-02-24 Time 06:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-09 Cont ID  
Sent By tklarge Date 2016-02-09 Time 06:29 Rev Time 0.00
Received By tklarge Date 2016-02-09 Time 05:59 Sent To  
Notes
2016-02-09 06:07:501) INDICATE THE EXISTING AND PROPOSED OCCUPANCY TYPE OF
 THIS SPACE ON THE PLANS PER 2014 FBC SEC.303.
 2) PROVIDE FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZE OF THE GREASE INTERCEPTOR. 2014 FPC SEC.
 1003.2.CONTACT LEE SCHNEEWEISS AT 561-632-3123.2ND
 REQUEST.
 3) A 4X4X3 TEE IS NOT ACCEPTABLE AS A SAMPLING PORT.
 EITHER A MANUFACTURED SAMPLING PORT CAN BE INSTALLED OR
 A 6 INCH TWO WAY CLEANOUT CAN BE INSTALLED PER THE CITY
 OF WPB ENGINEERING DEPT. STANDARD DWG. GS-7 & GS-7.1.
 4) SHOW THE DEVELOPED LENGTH OF THE HOT WATER SYSTEM. A
 RECIRCULATION LINE MAY BE REQUIRED PER THE 2014 FPC
 SEC.607.2.
 5) SHT. P-2 - FLOOR DRAIN DETAIL - THE MINIMUM REQUIRED
 AIR GAP SHALL BE NOT LESS THAN TWICE THE EFFECTIVE
 OPENING OF THE INDIRECT WASTE PIPE PER 2014 FPC SEC.
 802.2.1.
 6) THE HYDROMECHANICAL GREASE INTERCEPTOR SHALL BE
 VENTED IN ACCORDANCE WITH 2014 FPC SEC.1003.3.4.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-15 Cont ID  
Sent By gjohnson Date 2016-01-15 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2016-01-15 Time 12:45 Sent To  
Notes
2016-01-15 13:06:141ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE COST BREAKDOWN TO SHOW COMPLIANCE
 WITH FBC ACC SEC 202.4.1-202.4.2
 2.PLEASE PROVIDE INSTALLATION GUIDE AND SPEC SHEETS FOR
 TANKLESS WATER HEATER.PER WPB AMEND TO FBC 107.2.1
 3. BACKFLOW IS REQUIRED FOR COFFE MAKER PER FBC PL SEC
 608.16.10
 4 PLEASE PROVIDE SIZING CALCULATIONS FROM SCHIER FOR
 GREASE INTERCEPTOR YOU CAN CONTACT LEE SCHNEEWEISS PH.
 561-632-3123
 5. THE SAMPLING POINTE SHALL BE MIN. OF 6IN WITH NO
 SUMP ON THE BOTTOM WE RECOMMEND USING A 6IN TWOWAY
 CLEANOUT WITH 3X6 REDUCING COUPLINGS.
 6. THE FLOOR SINK THAT IS SERVING P5+P6 IS NOT VENTED
 PER FBC PL SEC 901.2.1 YOU CAN USE THE VENT ON P6 AND
 DRAIN P5 INTO THE FLOOR SINK.


Account Summary | Usage Policy | Privacy Policy