Plan Review Details - Permit 16010174
Plan Review Stops For Permit 16010174
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-06 Cont ID  
Sent By jwitmer Date 2016-06-06 Time   Rev Time 0.00
Received By jwitmer Date 2016-06-06 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-06 Cont ID  
Sent By jwitmer Date 2016-04-06 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2016-04-06 Time   Sent To  
Notes
2016-04-06 16:32:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010174
 ADD: 3715 S. DIXIE HWY.
 CONT: TYDAN CONSTRUCTION
 TEL: 561-339-5564
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 06/ 2016
 ACTION: BUILDING PROVISO
  
 1) THE NEW STAINLESS STEEL HOOD AND EXHAUST SYSTEM,
 THIS SYSTEM WILL REQUIRE A SEPARATE PERMIT, PLEASE
 INCLUDE THE PRODUCT APPROVALS FOR THE ROOF TOP CURB AND
 INTAKE AND EXHAUST HOODS. M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-25 Cont ID  
Sent By jwitmer Date 2016-01-25 Time 13:51 Rev Time  
Received By jwitmer Date 2016-01-25 Time 10:33 Sent To  
Notes
2016-01-25 13:50:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010174
 ADD: 3715 S. DIXIE HWY.
 CONT: TYDAN CONSTRUCTION
 TEL: 561-339-5564
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 25/ 2016
 ACTION: DENIED
  
 1) SHEET C-1 PLEASE REVIEW THE CODE EDITION, THE PLANS
 INDICATE THE 2010 EXISITNG FLORIDA BUILDING CODE. THE
 2014 FAMILY OF FLORIDA CODES WAS ADOPTED STATEWIDE ON
 JUNE 30, 2015.
  
 2) THE C-1 COVERSHEET INDICATES THE OCCUPANT LOAD OF 15
 OCCUPANTS AND A OCCUPANCY TYPE A2 ASSEMBLY OCCUPANCY.
 PLEASE NOTE IN THE 2014 FBC-B 303.1.1 303.1.1 SMALL
 BUILDINGS AND TENANT SPACES. A BUILDING OR TENANT SPACE
 USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF
 LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP B
 OCCUPANCY.
  
 3) SHEET 1.0A INDICATES NEW FRONT ENTRY DOORS. PLEASE
 SUBMIT A PRODUCT APPROVAL FOR THE NEW DOOR. 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS.
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE NEW
 DOOR. 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 6) PLEASE NOTE THE PLANS INDICATE A NEW STAINLESS STEEL
 HOOD AND EXHAUST SYSTEM. THIS SYSTEM WILL REQUIRE A
 SEPARATE PERMIT, PLEASE INCLUDE THE PRODUCT AAPPREOVALS
 FOR THE ROOF TOP CURB AND INTAKE AND EXHAUST HOODS.
 PLEASE NOTE THAT THE RAFTERS/ CEILING JOIST MAY NEED TO
 BE MODIFIED FOR THE INTAKE AND EXHAUST. 107.2.1.3
 ADDTIONAL INFORMATION IS REQUIRED. ? M- 301.15 WIND
 RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 7) PLANS DO NOT SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE FOR:
 7A) 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 7B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 7C) 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL
 BE 38 INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 904.4.1 PARALLEL APPROACH. A PORTION OF THE COUNTER
 SURFACE THAT IS 36 INCHES (915 MM) LONG MINIMUM AND 36
 INCHES (915 MM) HIGH MAXIMUM ABOVE THE FINISH FLOOR
 SHALL BE PROVIDED. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE POSITIONED FOR A PARALLEL
 APPROACH ADJACENT TO THE 36 INCH (915 MM) MINIMUM
 LENGTH OF COUNTER.
  
 904.4.2 FORWARD APPROACH. A PORTION OF THE COUNTER
 SURFACE THAT IS 30 INCHES (760 MM) LONG MINIMUM AND 36
 INCHES (915 MM) HIGH MAXIMUM SHALL BE PROVIDED. KNEE
 AND TOE SPACE COMPLYING WITH 306 SHALL BE PROVIDED
 UNDER THE COUNTER. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE POSITIONED FOR A FORWARD
 APPROACH TO THE COUNTER.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-15 Cont ID  
Sent By mvaldes Date 2016-06-15 Time 13:47 Rev Time 0.00
Received By mvaldes Date 2016-06-15 Time 13:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-28 Cont ID  
Sent By vperez Date 2016-03-28 Time 09:13 Rev Time 0.00
Received By vperez Date 2016-03-28 Time 09:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 14:05 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 14:05 Sent To  
Notes
2016-02-10 14:27:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. UPDATE ALL APPLICABLE CODES TO REFLECT NEW FBC 2014
 5TH EDITION SET AND NFPA 70 NEC 2011
 2. PROVIDE A NOTE TO COMPLY WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE.
 3. SHOW WINDOW RECEPTACLES REQUIRED PER NEC 220.14G AND
 210.62
 4. HOOD SUPPRESSION TO BE UNDER SEPARATE PERMIT. A NOTE
 WILL SUFFICE
 5. PER FBC 107 MINIMUM PLAN REVIEW CRITERIA, SHOW ALL
 EXISTING AND NEW OUTLETS WITH CIRCUIT DESIGNATIONS.
 6. LABEL PANEL SCHEDULE PER SPECIFIC PURPOSE OR USE.
 GENERAL LIGHTING AND RECEPTACLE ID DOES NOT MEET THE
 INTENT. NEC 408.4A
 7. LABEL ALL KITCHEN OUTLETS TO BE GFCI PROTECTED ON
 FLOOR PLAN. FBC 107 NEC 210.8B
 8. PLEASE SHOW THE GEC SIZE AT THE NEW SERVICE AND
 PROVIDE AN INTERSYSTEM BONDING TERMINATION. NEC 250.94
 AND NEC 250.66
 9. PLEASE CLARIFY IF THIS BUILDING IS BEING SERVED BY
 MULTIPLE ELECTRICAL SERVICES, AS A NEW ONE IS SHOWN.
 NEC 230.2
 10. SHOW AIC AND VOLTAGE DROP CALCULATIONS FOR THE NEW
 SERVICE PER FBC EC 405.7
 11. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-04 Cont ID  
Sent By rlindow Date 2016-04-04 Time   Rev Time 0.00
Received By rlindow Date 2016-04-04 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-20 Cont ID  
Sent By rlindow Date 2016-01-20 Time   Rev Time 0.00
Received By rlindow Date 2016-01-20 Time   Sent To B
Notes
2016-01-20 08:55:06 
  
 SERPARATE PERMIT AND DRAWINGS ARE REQUIRED FOR FIRE
 SUPPRESSION SYSTEM.
 SEPARATE PERMIT AND DRAWINGS ARE REQUIRED FOR EXHAUST
 HOOD.
 R. LINDOW, 1/20/2016
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-06-15 Cont ID  
Sent By gjohnson Date 2016-06-15 Time 11:10 Rev Time 0.00
Received By gjohnson Date 2016-06-15 Time 11:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-06-06 Cont ID  
Sent By gjohnson Date 2016-06-02 Time 14:39 Rev Time 0.00
Received By gjohnson Date 2016-06-02 Time 14:39 Sent To  
Notes
2016-06-02 14:42:45 
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING PROVISO
 1. PROVIDE A SANITARY RISER DIAGRAM TO BE REVIEWED AND
 APPROVED BEFORE FIRST ROUGH INSPECTION.
 PER WPB AMEND.TO FBC 107.2.1
  
 2. PROVIDE COMBUSTION AIR CALCULATION FOR GAS
 APPLIANCES TO BE REVIEWED AND APPROVED BEFORE FIRST
 ROUGH INSPECTION.
 PER WPB AMEND.TO FBC 107.2.1
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By gjohnson Date 2016-04-11 Time 15:51 Rev Time 0.00
Received By gjohnson Date 2016-04-11 Time 15:50 Sent To  
Notes
2016-04-11 16:13:26REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. THE FLOOR PLAN SHOWS THE TANKLESS HEATER BEFORE
 ANSUL VALVE ON THE EXTERIOR OF THE BUILDING. THE RISER
 SHOWS TANKLESS HEATER AFTER THE ANSUL VALVE PLEASE
 CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
  
 2. NOTE ON GAS PLAN STILL IS REFERENCING A TABLE FOR 10
 PSI PROPANE GAS PLEASE CORRECT.
 PER WPB AMEND. TO FBC SEC 107.2.1
  
 3.SYSTEM IS UNDERSIZED PER FBC FUEL GAS TABLE 402.4(2)
  
 4. 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-15 Cont ID  
Sent By skennedy Date 2016-06-15 Time 17:13 Rev Time 0.00
Received By skennedy Date 2016-05-24 Time 12:48 Sent To  
Notes
2016-05-25 12:49:07C12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-11 Cont ID  
Sent By gjohnson Date 2016-04-11 Time 16:13 Rev Time 0.00
Received By gjohnson Date 2016-03-23 Time 09:13 Sent To  
Notes
2016-03-24 09:13:55C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 14:28 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 14:28 Sent To  
Notes
2016-02-10 14:29:10SENT TO CAROLINE/LAURA
2016-01-08 13:28:32C12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-04-06 Cont ID  
Sent By jwitmer Date 2016-04-06 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2016-04-06 Time 16:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-25 Cont ID  
Sent By jwitmer Date 2016-01-25 Time   Rev Time  
Received By jwitmer Date 2016-01-25 Time 10:33 Sent To  
Notes
2016-01-25 10:58:33IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-06-15 Cont ID  
Sent By ccole Date 2016-06-15 Time 17:01 Rev Time 0.00
Received By ccole Date 2016-06-15 Time 17:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-06-07 Cont ID  
Sent By ccole Date 2016-06-07 Time 07:58 Rev Time 0.00
Received By ccole Date 2016-06-07 Time 07:58 Sent To  
Notes
2016-06-07 07:59:59MECHANICAL PROVISO:
 6/7/16
  
 1) REVISED ENERGY CALCULATIONS SHALL BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT PRIOR TO 1ST
 INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-05-31 Cont ID  
Sent By ccole Date 2016-05-31 Time 16:06 Rev Time 0.00
Received By ccole Date 2016-05-31 Time 16:06 Sent To  
Notes
2016-05-31 16:09:193RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010174
 5/31/16
  
 1) THE ARCHITECT'S REVISED AC CALCULATIONS INDICATE A
 6-TON HEAT LOAD, HOWEVER THE PLAN IS SPECIFYING ONLY A
 3-TON SYSTEM AND AN EXISTING THROUGH-THE-WALL UNIT.
 PLEASE INDICATE THE COOLING CAPACITY OF THE EXISTING
 UNIT ON THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-28 Cont ID  
Sent By ccole Date 2016-03-28 Time 14:47 Rev Time 0.00
Received By ccole Date 2016-03-28 Time 14:47 Sent To  
Notes
2016-03-28 14:50:192ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010174
 3/28/16
  
 1) AC LOAD SUMMARY CALCULATIONS CAN BE SUBMITTED ONLY
 BY A REGISTERED ENGINEERED WHO MUST PLACE HIS/HER
 SIGNATURE AND SEAL ON THE DOCUMENT- SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 2) NO COMPLIANCE DATA WAS LISTED IN THE ENERGY
 COMPLIANCE FORM FOR THE NEW MINI-SPLIT SYSTEM.
 3) 2ND REQUEST FOR VENITLATION AND AIR BALANCE
 CALCULATIONS TO BE PLACED ON THE PLANS. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF O/A FOR OCCUPANTS AND EXHAUST CFMS FOR THE KITCHEN.
 3) INDICATE ON THE PLANS IF THE CONDENSATE DRAINING TO
 THE EXTERIOR IS TO PERMEABLE GROUND OR TO A DRYWELL.
 4) CLARIFY WHERE THE CONDENSER FOR THE MINI-SPLIT
 SYSTEM IS BEING INSTALLED- ON THE WALL OR ON A SLAB? IF
 ON THE GROUND PROVIDE A DETAIL FOR INSTALLATION OF A
 MOUNTING PAD, IF ON THE WALL PROVIDE A DETAIL USING A
 WALL BRACKET AND SUBMIT AN NOA OR PRODUCT APPROVAL.
 PLEASE INCLUDE THE WIND LOAD DESIGN CRITERIA AS
 OUTLINED IN SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-12 Cont ID  
Sent By ccole Date 2016-01-12 Time 11:54 Rev Time 0.00
Received By ccole Date 2016-01-12 Time 11:54 Sent To  
Notes
2016-01-12 12:24:521ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010174
 01/12/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 MINI-SPLIT SYSTEM IN COMPLIANCE WITH SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 2) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING AND
 PROVIDE VENTILATION AND AIR BALANCE CALCULATIONS ON THE
 PLAN IN ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
 PLEASE NOTE THE EXHAUST SYSTEM FOR THE KITCHEN HOOD
 MUST BE INCLUDED IN THE CALCULATIONS.
 3) PLACE A NOTE ON THE PLAN INDICATING THE KITCHEN HOOD
 AND FIRE SUPPRESSION WILL BE DONE UNDER SEPARATE
 PERMIT.
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 MINI-SPLIT AIR HANDLER IN THE DINING ROOM- SHOW THE
 PIPING RUN AND DISCHARGE LOCATION.
 5) PROVIDE WIND LOAD TIE-DOWN ENGINEERING FPOR THE MINI
 SPLIT CONDENSER PER SECTION 301.15 FBC-14 MECHANICAL.
 6) PROVIDE AN EXHAUST VENTILATION SYTEM FOR THE NEW
 TOILET ROOM PER TABLE 403.3.
 7) IN ACCORDANCE WITH SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION, PROVIDE ENERGY CALCULATIONS USING EITHER
 THE PERFORMANCE OR PRESCRIPTIVE COMPLIANCE PATHS- SEE
 SECTION C101.5.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-06-15 Cont ID  
Sent By gjohnson Date 2016-06-15 Time 11:10 Rev Time 0.00
Received By gjohnson Date 2016-06-15 Time 11:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-06 Cont ID  
Sent By gjohnson Date 2016-06-02 Time 14:38 Rev Time 0.00
Received By gjohnson Date 2016-06-01 Time 18:15 Sent To  
Notes
2016-06-02 14:38:28 
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING PROVISO
 1. PROVIDE A SANITARY RISER DIAGRAM TO BE REVIEWED AND
 APPROVED BEFORE FIRST ROUGH INSPECTION.
 PER WPB AMEND.TO FBC 107.2.1
  
 2. PROVIDE COMBUSTION AIR CALCULATION FOR GAS
 APPLIANCES TO BE REVIEWED AND APPROVED BEFORE FIRST
 ROUGH INSPECTION.
 PER WPB AMEND.TO FBC 107.2.1
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-11 Cont ID  
Sent By gjohnson Date 2016-04-11 Time 15:34 Rev Time 0.00
Received By gjohnson Date 2016-04-11 Time 15:34 Sent To  
Notes
2016-04-11 15:50:232ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SCHIER WILL PROVIDE A SITE SPECIFIC CALCULATIONS FOR
 THE INTERCEPTOR YOUR USING, THAT IS WHAT WE ARE LOOKING
 FOR ,ON ANY HYDROMECHANICAL GREASE INTERCEPTOR. YOU CAN
 CONTACT LEE SCHEEWEISS AT 1-800-538-4792 FOR DETAILS
 PER WPB AMEND.TO FBC SEC.107.2.1
  
 2. THE FLOOR SINK SHALL CONNECT TO GREASE INTERCEPTOR.
 PER FBC PL SEC. 1003.1
  
 3. THE HAND SINK IN KITCHEN SHALL CONNECT TO SANITARY
 DOWN STREAM OF BATHROOM GROUP.
 PER FBC PL SEC. 1003.2 + 912.1
  
  
 4. SHOW CLEAN OUTS AND AND SAMPLING PORT ON RISER
 DIAGRAM.
 PER WPB AMEND. TO FBC SEC. 107.2.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-22 Cont ID  
Sent By tklarge Date 2016-01-22 Time 14:15 Rev Time 0.00
Received By tklarge Date 2016-01-22 Time 11:19 Sent To  
Notes
2016-01-22 13:42:401) SINCE THE OCCCUPANT LOAD IS UNDER 50 PERSONS, THIS
 IS CONSIDERED A "B" OCCUPANCY, NOT AN A-2. 2014 FBC
 SEC.303.1.1.
 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZE OF THE GREASE TRAP.2014 FPC 1003.2.CONTACT LEE
 SCHNEEWEISS AT 1-800-538-4792.
 3) THE PLAN NOTES THAT THE GAS IS LP BUT THERE IS ALSO
 AN EXISTING GAS METER. CLARIFY.
 4) THE PLANS CALL OUT AN11" WATER COLUMN WITH 0.5 INCH
 PRESSURE DROP BUT THE GAS TABLE THAT IS REFERENCED IS
 FOR A 10 PSI SYSTEM WITH A PRESSURE DROP OF 3 PSI.
 CLARIFY.
 5) THE PLANS NOTE A DEVELOPED LENGTH OF 80 FT. BUT THE
 RISER SHOWS 100 FT. CLARIFY.
 6) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE LINE OF
 THE GREASE INTERCEPTOR AND MUST BE ACCESSIBLE FROM THE
 EXTERIOR OF THE BUILDING.A DETAIL FROM THE CITY'S
 ENGINEERING DEPT. HAS BEEN INCLUDED IN THE PLAN PACKAGE
 FOR YOUR REVIEW.
 7) THE SANITARY RISER SHOWS THE FLOOR SINK ON A WET
 VENT. THIS VIOLATES 2014 FPC SEC.912.1.
 8) THE CAN WASH IS NOT VENTED.
 9) SIZE ALL THE VENTS ON THE SANITARY RISER.
 10) SUBMIT MANUF. SPECIFICATIONS FOR THE GAS
 APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED. 2014
 FGC SEC.301.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-25 Cont ID  
Sent By llouie Date 2016-03-25 Time 09:49 Rev Time 0.00
Received By llouie Date 2016-03-25 Time 08:49 Sent To  
Notes
2016-03-25 09:52:20CHANGE OF OCCUPANCY ONLY. PROPERTY IS ZONED NC;
 RESTAURANTS SERVING THE GENERAL PUBLIC (NOT DRIVE IN OR
 DRIVE THROUGH) IS PERMITTED IN THE NC ZONING DISTRICT.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-21 Cont ID  
Sent By llouie Date 2016-01-21 Time 15:24 Rev Time 0.00
Received By llouie Date 2016-01-21 Time 14:36 Sent To  
Notes
2016-01-21 15:26:26PROPERTY ZONED NC. RESTAURANTS SERVING THE GENERAL
 PUBLIC (NOT DRIVE-IN OR DRIVE-THROUGH) PERMITTED IN THE
 NC ZONING DISTRICT.